Quick Start Guide
Page 7
... the unit in a partially filled rack, load the rack from the bottom. Installing the Chassis To install the C150/300 chassis, Dell Force10 recommends that you must take all site preparation has been performed before installing the chassis. Install the chassis into a 19-inch equipment rack...NOTE: Unless stated otherwise, the installation instructions below . Installing the Chassis in the order presented below apply to both the C150 and C300 chassis. Lifting by the chassis shelves or power supply openings might damage the chassis. WARNING: To prevent bodily injury when mounting or ...
... the unit in a partially filled rack, load the rack from the bottom. Installing the Chassis To install the C150/300 chassis, Dell Force10 recommends that you must take all site preparation has been performed before installing the chassis. Install the chassis into a 19-inch equipment rack...NOTE: Unless stated otherwise, the installation instructions below . Installing the Chassis in the order presented below apply to both the C150 and C300 chassis. Lifting by the chassis shelves or power supply openings might damage the chassis. WARNING: To prevent bodily injury when mounting or ...
Quick Start Guide
Page 11
... a minimum of the chassis. Installing the Hardware 9 AC Power Supplies • The C150 requires only one AC power supply to operate, but Dell Force10 recommends a one-plus-one redundancy configuration, so a minimum of two power supplies is recommended. • To protect against high-voltage shock, install...Power Entry Modules (PEMs). If there is used on the building's installation for short-circuit (overcurrent) protection. WARNING: The C300 does not have been installed. The C300 has eight power supply slots at the bottom front of three power supplies is recommended. • The...
... a minimum of the chassis. Installing the Hardware 9 AC Power Supplies • The C150 requires only one AC power supply to operate, but Dell Force10 recommends a one-plus-one redundancy configuration, so a minimum of two power supplies is recommended. • To protect against high-voltage shock, install...Power Entry Modules (PEMs). If there is used on the building's installation for short-circuit (overcurrent) protection. WARNING: The C300 does not have been installed. The C300 has eight power supply slots at the bottom front of three power supplies is recommended. • The...
Quick Start Guide
Page 12
...qualified chassis installer or a qualified electrician. Those DC PEMs are inserted in slots 0 and 2. • The C300 requires at least one DC PEM for operation, but Dell Force10 recommends a one-plus -one redundancy configuration. Leakage Current (High Touch Current) in AC-powered systems with more ...• The C150 requires at least one DC PEM for operation, but Dell Force10 recommends a one-plus -one redundancy configuration. Those DC PEMs are inserted in all unused PSU slots. WARNING: The C300 operates in the OFF (left -most power supply slot. Each range supports ...
...qualified chassis installer or a qualified electrician. Those DC PEMs are inserted in slots 0 and 2. • The C300 requires at least one DC PEM for operation, but Dell Force10 recommends a one-plus -one redundancy configuration. Leakage Current (High Touch Current) in AC-powered systems with more ...• The C150 requires at least one DC PEM for operation, but Dell Force10 recommends a one-plus -one redundancy configuration. Those DC PEMs are inserted in all unused PSU slots. WARNING: The C300 operates in the OFF (left -most power supply slot. Each range supports ...
Quick Start Guide
Page 13
.... 4 Slide the PEM into slots 1 and 2 (for the C150) or slots 0 and (for the C300) NOTE: Fill all unused power supply slots. Please contact the Dell Force10 TAC if you experience any difficulty during installation Step Task 1 Turn the remote power source (the circuit breaker panel... Over-Current Switch Safety Cover Handle Retaining Latch BLNK fn003lp fn003lp fn00012lpp BLNK BLNK BLNK Power Supply Blank C300 Power Entry Module Installation fn0002lp Installing the Hardware 11 CAUTION: Some CH-C300 chassis may require Dell Force10 assistance when using some DC power supplies.
.... 4 Slide the PEM into slots 1 and 2 (for the C150) or slots 0 and (for the C300) NOTE: Fill all unused power supply slots. Please contact the Dell Force10 TAC if you experience any difficulty during installation Step Task 1 Turn the remote power source (the circuit breaker panel... Over-Current Switch Safety Cover Handle Retaining Latch BLNK fn003lp fn003lp fn00012lpp BLNK BLNK BLNK Power Supply Blank C300 Power Entry Module Installation fn0002lp Installing the Hardware 11 CAUTION: Some CH-C300 chassis may require Dell Force10 assistance when using some DC power supplies.
Quick Start Guide
Page 18
...C300 operates in all unused power supply slots. Each range supports a different supply configuration. Install blank panels in either of power supplies (given by the table below), as this causes high leakage current. To supply power to the system: Step Task 1 Verify that you supply power to the chassis, Dell Force10...of two voltage ranges. Power Up Sequence Before you reinspect your equipment rack and chassis. CAUTION: Never operate the system without a fan tray. C300 0 1 2 3 R0 R1 4 5 6 7 fnC0003mp NOTE: The fan tray LED will remain lit when the chassis is powered up and ...
...C300 operates in all unused power supply slots. Each range supports a different supply configuration. Install blank panels in either of power supplies (given by the table below), as this causes high leakage current. To supply power to the system: Step Task 1 Verify that you supply power to the chassis, Dell Force10...of two voltage ranges. Power Up Sequence Before you reinspect your equipment rack and chassis. CAUTION: Never operate the system without a fan tray. C300 0 1 2 3 R0 R1 4 5 6 7 fnC0003mp NOTE: The fan tray LED will remain lit when the chassis is powered up and ...
C300 Hardware Installation Guide
Page 7
...der Klasse 1 WARNING: This equipment contains optical transceivers, which comply with all of the necessary components, including slot blanks for installing the Dell Force10 C300 chassis, fan tray, power supply units (supplies), route processor modules (RPMs), and line cards. Read this guide before servicing. This ... this equipment. 1 About this document to bring attention to laser radiation and do not stare into open apertures. The C300 system is connected. Please read these alerts and heed their warnings and cautions. Information Symbols Symbol Warning Description Note This ...
...der Klasse 1 WARNING: This equipment contains optical transceivers, which comply with all of the necessary components, including slot blanks for installing the Dell Force10 C300 chassis, fan tray, power supply units (supplies), route processor modules (RPMs), and line cards. Read this guide before servicing. This ... this equipment. 1 About this document to bring attention to laser radiation and do not stare into open apertures. The C300 system is connected. Please read these alerts and heed their warnings and cautions. Information Symbols Symbol Warning Description Note This ...
C300 Hardware Installation Guide
Page 12
... (factory installed) 1 Fan tray 1 RPM 1 Line card 1 AC Power Supply 2 DC Power Entry Module 2 Maximum 1 1 2 8 8 8 Field-Replaceable No Yes Yes Yes Yes Yes C300 System Installation Process The Dell Force10 recommended installation process is described below. Relevant Section in a rack. 4 Install the fan tray. 5 Install the RPMs and line cards. 6 Connect console and...
... (factory installed) 1 Fan tray 1 RPM 1 Line card 1 AC Power Supply 2 DC Power Entry Module 2 Maximum 1 1 2 8 8 8 Field-Replaceable No Yes Yes Yes Yes Yes C300 System Installation Process The Dell Force10 recommended installation process is described below. Relevant Section in a rack. 4 Install the fan tray. 5 Install the RPMs and line cards. 6 Connect console and...
C300 Hardware Installation Guide
Page 14
..., supplies, and RPMs) installed in the chassis. That is, use a level to ensure the chassis is installed level. Place the components in your C300 System and components immediately, Dell Force10 recommends you properly store components (including all extra field-replaceable parts) until you install the chassis, use a minimum of three supplies; Shipping components...
..., supplies, and RPMs) installed in the chassis. That is, use a level to ensure the chassis is installed level. Place the components in your C300 System and components immediately, Dell Force10 recommends you properly store components (including all extra field-replaceable parts) until you install the chassis, use a minimum of three supplies; Shipping components...
C300 Hardware Installation Guide
Page 15
...the installation site and the chassis itself are two types of the chassis. 4 Installing C300 Fan Tray The C300 chassis contains one field-replaceable fan tray. For both types of trays, air flows through the C300 system toward the fans (right to left) and is accessible from the front of... system. The fan tray is exhausted on system temperature, Fan Tray CC-C300-FAN contains six fans that run at a constant speed. Inserting the Fan Tray 0 1 2 3 R0 R1 4 5 6 7 fnC0003mp Installing C300 Fan Tray | 15 Contact Dell Force10 Technical Support if you have an air filter so take special care in ...
...the installation site and the chassis itself are two types of the chassis. 4 Installing C300 Fan Tray The C300 chassis contains one field-replaceable fan tray. For both types of trays, air flows through the C300 system toward the fans (right to left) and is accessible from the front of... system. The fan tray is exhausted on system temperature, Fan Tray CC-C300-FAN contains six fans that run at a constant speed. Inserting the Fan Tray 0 1 2 3 R0 R1 4 5 6 7 fnC0003mp Installing C300 Fan Tray | 15 Contact Dell Force10 Technical Support if you have an air filter so take special care in ...
C300 Hardware Installation Guide
Page 27
...Power Supply Units (PSUs) or DC Power Entry Modules (PEMs). • Dell Force10 does not support the use of a combination of AC and DC power supplies. • If you select AC, the C300 requires a minimum of the installer to the appropriate branch circuit protection as ...Installing AC Power Supplies | 27 Additional power supplies are required to operate, but Dell Force10 recommends a two-plus-one redundancy configuration, so a minimum of the chassis (Figure 7-1). 7 Installing AC Power Supplies The C300 has eight power supply slots at the front-bottom of three power supplies is ...
...Power Supply Units (PSUs) or DC Power Entry Modules (PEMs). • Dell Force10 does not support the use of a combination of AC and DC power supplies. • If you select AC, the C300 requires a minimum of the installer to the appropriate branch circuit protection as ...Installing AC Power Supplies | 27 Additional power supplies are required to operate, but Dell Force10 recommends a two-plus-one redundancy configuration, so a minimum of the chassis (Figure 7-1). 7 Installing AC Power Supplies The C300 has eight power supply slots at the front-bottom of three power supplies is ...
C300 Hardware Installation Guide
Page 30
...range supports a different power supply configuration. You can install any power supply slot. The following are Dell Force10 supplied plug types. All power plugs must also conform to your local electrical codes. To install ... 2 redundant 3 primary + 1 redundant NOTE: For system input power requirements see System Specifications on page 62. Dell Force10 recommends installing power supplies starting from the left most power supply slot. See Figure 7-1 for correct orientation. 3...220: N6-15 30 | Installing AC Power Supplies WARNING: The C300 operates in all unused PSU slots.
...range supports a different power supply configuration. You can install any power supply slot. The following are Dell Force10 supplied plug types. All power plugs must also conform to your local electrical codes. To install ... 2 redundant 3 primary + 1 redundant NOTE: For system input power requirements see System Specifications on page 62. Dell Force10 recommends installing power supplies starting from the left most power supply slot. See Figure 7-1 for correct orientation. 3...220: N6-15 30 | Installing AC Power Supplies WARNING: The C300 operates in all unused PSU slots.
C300 Hardware Installation Guide
Page 33
... codes. Input voltage Input Ranges -44V (minimum) -48V (typical) -55V (maximum) Table 8-2. Please contact the Dell Force10 TAC if you select DC, the C300 requires at the front-bottom of AC and DC. • If you experience any difficulty during installation. 8 Installing ...DC Power Entry Modules The C300 has eight supply slots at least one DC PEM for operation, but Dell Force10 recommends a one-plus-one redundancy configuration. Recommended Normal Operating Conditions Table 8-1. Installing DC Power ...
... codes. Input voltage Input Ranges -44V (minimum) -48V (typical) -55V (maximum) Table 8-2. Please contact the Dell Force10 TAC if you select DC, the C300 requires at the front-bottom of AC and DC. • If you experience any difficulty during installation. 8 Installing ...DC Power Entry Modules The C300 has eight supply slots at least one DC PEM for operation, but Dell Force10 recommends a one-plus-one redundancy configuration. Recommended Normal Operating Conditions Table 8-1. Installing DC Power ...
C300 Hardware Installation Guide
Page 39
Supplying WARNING: Never operate the C300 System without a fan tray. consider the nameplate rating of the unit. • Make sure the equipment is properly grounded. Verify that you re-inspect your ... (bottom) position. • The remote source complies with the input specifications in the section System Specifications on page 62. • Cables connect to the chassis, Dell Force10 recommends that : • The equipment rack or properly secured and grounded. • The chassis is bolted and secured into your equipment rack and chassis. 9 Powering...
Supplying WARNING: Never operate the C300 System without a fan tray. consider the nameplate rating of the unit. • Make sure the equipment is properly grounded. Verify that you re-inspect your ... (bottom) position. • The remote source complies with the input specifications in the section System Specifications on page 62. • Cables connect to the chassis, Dell Force10 recommends that : • The equipment rack or properly secured and grounded. • The chassis is bolted and secured into your equipment rack and chassis. 9 Powering...
C300 Hardware Installation Guide
Page 57
...complex configurations, you can read or write operations. NOTE: Use only a Dell Force10 Compact memory card in run-time mode. Additional memory cards can be oriented so you can use the Compact Flash Card to other C300 systems in RPM fnC0010mp Compact Flash S/N 012345678 2 Insert the flash card... RPM flash slot until the card is completely seated with the serial number facing up (the numbers should be purchased from Dell Force10. You can copy your C300 System. 13 The Compact Flash Card Each RPM is designed with a slot (slot0:) to prevent improper installation. To install...
...complex configurations, you can read or write operations. NOTE: Use only a Dell Force10 Compact memory card in run-time mode. Additional memory cards can be oriented so you can use the Compact Flash Card to other C300 systems in RPM fnC0010mp Compact Flash S/N 012345678 2 Insert the flash card... RPM flash slot until the card is completely seated with the serial number facing up (the numbers should be purchased from Dell Force10. You can copy your C300 System. 13 The Compact Flash Card Each RPM is designed with a slot (slot0:) to prevent improper installation. To install...
C300 Hardware Installation Guide
Page 63
... following two conditions: (1) this equipment in a residential area is subject to Part 15 of the FCC Rules. Agency Compliance The C300 system is not installed and used in accordance to radio communications. This device complies with the limits for the latest information. System ...that requirement is a function of the number and type of this device may cause undesired operation. Operation of PoE devices connected. Dell Force10 is not responsible for PoE, as that may not cause harmful interference, and (2) this device must be required to take whatever ...
... following two conditions: (1) this equipment in a residential area is subject to Part 15 of the FCC Rules. Agency Compliance The C300 system is not installed and used in accordance to radio communications. This device complies with the limits for the latest information. System ...that requirement is a function of the number and type of this device may cause undesired operation. Operation of PoE devices connected. Dell Force10 is not responsible for PoE, as that may not cause harmful interference, and (2) this device must be required to take whatever ...
FTOS Command Line Reference Guide FTOS 8.4.2.7 E-Series TeraScale, C-Series, S-Series (S50/S25)
Page 601
... E-Series ExaScale E600i Introduced on E-Series ExaScale Introduced on C-Series Introduced on E-Series Usage The following figure shows a line card that is not certified by Dell Force10 is not set MTU 1554 bytes, IP MTU 1500 bytes LineSpeed 10000 Mbit ARP type: ARPA, ARP Timeout 04:00:00 Last clearing of "show...-byte pkts, 0 over 127-byte pkts --More-- show interfaces linecard c e Display information on all interfaces on a specific physical interface or virtual interface. C-Series Range: 0-7 for C300; 0-3 for the line card slot.
... E-Series ExaScale E600i Introduced on E-Series ExaScale Introduced on C-Series Introduced on E-Series Usage The following figure shows a line card that is not certified by Dell Force10 is not set MTU 1554 bytes, IP MTU 1500 bytes LineSpeed 10000 Mbit ARP type: ARPA, ARP Timeout 04:00:00 Last clearing of "show...-byte pkts, 0 over 127-byte pkts --More-- show interfaces linecard c e Display information on all interfaces on a specific physical interface or virtual interface. C-Series Range: 0-7 for C300; 0-3 for the line card slot.
FTOS Command Line Reference Guide FTOS 8.4.2.7 E-Series TeraScale, C-Series, S-Series (S50/S25)
Page 1496
...EXEC Privilege Command History Version 7.5.10 Introduction Usage Information Warning: Use this command only when you are working directly with Dell Force10 TAC (Technical Assistance Center) while troubleshooting a problem. Enter the keyword rpm to clear counters on a line card....Dell Force10 TAC for assistance: E-mail Direct Support: [email protected] Web: www.force10networks.com/support/ Telephone support: US and Canada customers: 866-965-5800 International customers: 408-965-5800 clear hardware rpm mac counters Clear receive and transmit Ethernet statistics for the C300...
...EXEC Privilege Command History Version 7.5.10 Introduction Usage Information Warning: Use this command only when you are working directly with Dell Force10 TAC (Technical Assistance Center) while troubleshooting a problem. Enter the keyword rpm to clear counters on a line card....Dell Force10 TAC for assistance: E-mail Direct Support: [email protected] Web: www.force10networks.com/support/ Telephone support: US and Canada customers: 866-965-5800 International customers: 408-965-5800 clear hardware rpm mac counters Clear receive and transmit Ethernet statistics for the C300...
FTOS Command Line Reference Guide FTOS 8.4.2.7 E-Series TeraScale, C-Series, S-Series (S50/S25)
Page 1519
... followed by the slot/port information. • For a 10-Gigabit Ethernet interface, enter the keyword TenGigabitEthernet followed by the Dell Force10 Technical Assistance Center (TAC) to troubleshoot a problem. Command Mode EXEC EXEC Privilege Command History Version 4.2.1.0 Introduction Usage Information Warning... console lp • show cpu-traffic-stats • show hardware linecard fpga • show Layer 2 information for the C300 Defaults None. Trace Logging Commands Trace logging is a critical debugging tool most often used by the slot/port information. Enter...
... followed by the slot/port information. • For a 10-Gigabit Ethernet interface, enter the keyword TenGigabitEthernet followed by the Dell Force10 Technical Assistance Center (TAC) to troubleshoot a problem. Command Mode EXEC EXEC Privilege Command History Version 4.2.1.0 Introduction Usage Information Warning... console lp • show cpu-traffic-stats • show hardware linecard fpga • show Layer 2 information for the C300 Defaults None. Trace Logging Commands Trace logging is a critical debugging tool most often used by the slot/port information. Enter...
FTOS Command Line Reference Guide FTOS 8.4.2.7 E-Series TeraScale, C-Series, S-Series (S50/S25)
Page 1520
... keyword all to specify all number (OPTIONAL) Enter the keyword linecard to view CPU traffic statistics for the C300 Defaults Disabled Command Modes EXEC Privilege Command History Version 4.2.1.0 Introduced Usage Information This command can be enabled before ...of CPU traffic statistics from system boot). Related Commands show command-history Parameters None Defaults None 1520 | C-Series Diagnostics and Debugging Dell Force10 recommends that collection of all commands entered by CPU and traffic will automatically turn on CPU traffic statistics collection either on a ...
... keyword all to specify all number (OPTIONAL) Enter the keyword linecard to view CPU traffic statistics for the C300 Defaults Disabled Command Modes EXEC Privilege Command History Version 4.2.1.0 Introduced Usage Information This command can be enabled before ...of CPU traffic statistics from system boot). Related Commands show command-history Parameters None Defaults None 1520 | C-Series Diagnostics and Debugging Dell Force10 recommends that collection of all commands entered by CPU and traffic will automatically turn on CPU traffic statistics collection either on a ...
FTOS Command Line Reference Guide FTOS 8.4.2.7 E-Series TeraScale, C-Series, S-Series (S50/S25)
Page 1521
...number. Enter the keyword all to help identify the root cause of an RPM failover. This file can be analyzed by the Dell Force10 TAC to specify all number (OPTIONAL) Enter the keyword linecard to view CPU traffic statistics for a line card processor. Command Mode...-stats [linecard {all | number}] Parameters linecard all line cards. Enter a line card number Range: 0-7 for the C300; 0-3 for each command. Range: 0-7 for the C300; 0-3 for the C150 Defaults None Command Mode EXEC EXEC Privilege Command History H Version 7.5.1.0 Introduction Usage This log displays initialization...
...number. Enter the keyword all to help identify the root cause of an RPM failover. This file can be analyzed by the Dell Force10 TAC to specify all number (OPTIONAL) Enter the keyword linecard to view CPU traffic statistics for a line card processor. Command Mode...-stats [linecard {all | number}] Parameters linecard all line cards. Enter a line card number Range: 0-7 for the C300; 0-3 for each command. Range: 0-7 for the C300; 0-3 for the C150 Defaults None Command Mode EXEC EXEC Privilege Command History H Version 7.5.1.0 Introduction Usage This log displays initialization...