Configuration Guide
Page 1
...or, with installation kit) or an optional RS-485 interface. Reader & Aux Power Reader and AUX power is supplied at the left by operational utility with up to 31 panels. NS2 Configuration Guide Contents Description 1 Specifications 1 Power 1 Backup Battery 1 Secondary Backup Battery 1 Reader & Aux Power 1 Reader Wiring 2 Supervised Input Wiring 2 Inputs 2 Outputs 3 Enclosure Specifications 4 Communications & Wiring 4 DIP Switch Settings 5 Connection Schematic 6 Configuration Diagrams 7 RS-232 Connection 7 RS-485 Connection 8 NSLAN1 Connection 9 LANSRL100 Connection 10...
...or, with installation kit) or an optional RS-485 interface. Reader & Aux Power Reader and AUX power is supplied at the left by operational utility with up to 31 panels. NS2 Configuration Guide Contents Description 1 Specifications 1 Power 1 Backup Battery 1 Secondary Backup Battery 1 Reader & Aux Power 1 Reader Wiring 2 Supervised Input Wiring 2 Inputs 2 Outputs 3 Enclosure Specifications 4 Communications & Wiring 4 DIP Switch Settings 5 Connection Schematic 6 Configuration Diagrams 7 RS-232 Connection 7 RS-485 Connection 8 NSLAN1 Connection 9 LANSRL100 Connection 10...
Configuration Guide
Page 2
... Power Fail are assigned default features but does support the NS2MEM module, the OL, OJ, and OH Options, as well as Anti-Passback (In card only mode). NS2 Configuration Guide Honeywell Access Systems Reader Wiring Each reader port supports a single 12-volt reader with Wiegand output format. NOTE: NS2 version 1.03.09 does not support the ABA card format or the Lock Down Time...
... Power Fail are assigned default features but does support the NS2MEM module, the OL, OJ, and OH Options, as well as Anti-Passback (In card only mode). NS2 Configuration Guide Honeywell Access Systems Reader Wiring Each reader port supports a single 12-volt reader with Wiegand output format. NOTE: NS2 version 1.03.09 does not support the ABA card format or the Lock Down Time...
Configuration Guide
Page 3
... not be configured by using either time zone control, or programmable pulse time via the host software. Locate this device as close as possible to control the Door 1 lock & Relay 2 is defaulted for the Door 2 lock. NOTE: Switching of inductive loads can be used as the S-4 suppressor is defaulted to the Door Strike / Maglock. 7-101004-01 3 Honeywell Access Systems NS2 Configuration Guide Outputs Four form-C relays...
... not be configured by using either time zone control, or programmable pulse time via the host software. Locate this device as close as possible to control the Door 1 lock & Relay 2 is defaulted for the Door 2 lock. NOTE: Switching of inductive loads can be used as the S-4 suppressor is defaulted to the Door Strike / Maglock. 7-101004-01 3 Honeywell Access Systems NS2 Configuration Guide Outputs Four form-C relays...
Configuration Guide
Page 4
NS2 Configuration Guide Honeywell Access Systems Enclosure Specifications Mounting One NS2 panel in a single 19-inch rack mountable enclosure Dimensions Board Enclosure 9-inch Length x 5.5-inch Wide x 1-inch High 12.5-inch Wide x 14.5-inch High x 3.5-inch Deep Environmental Temperature Humidity 35-110° F operational 0-85% RHNC Communications & Wiring Communication Type Description Maximum Panels Maximum Distance Feet / Meters Direct to COM Port CBL50, RS-232 Cable...
NS2 Configuration Guide Honeywell Access Systems Enclosure Specifications Mounting One NS2 panel in a single 19-inch rack mountable enclosure Dimensions Board Enclosure 9-inch Length x 5.5-inch Wide x 1-inch High 12.5-inch Wide x 14.5-inch High x 3.5-inch Deep Environmental Temperature Humidity 35-110° F operational 0-85% RHNC Communications & Wiring Communication Type Description Maximum Panels Maximum Distance Feet / Meters Direct to COM Port CBL50, RS-232 Cable...
Configuration Guide
Page 5
Honeywell Access Systems DIP Switch Settings NS2 Configuration Guide S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 SELECTION OFF OFF OFF OFF OFF Address 0 ON OFF OFF OFF OFF Address 1(default) OFF ON OFF OFF OFF Address 2 ON ON OFF OFF OFF Address 3 OFF OFF ON OFF OFF Address 4 ON OFF ON OFF OFF Address 5 OFF ON ON OFF OFF Address 6 ON ON ON...
Honeywell Access Systems DIP Switch Settings NS2 Configuration Guide S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 SELECTION OFF OFF OFF OFF OFF Address 0 ON OFF OFF OFF OFF Address 1(default) OFF ON OFF OFF OFF Address 2 ON ON OFF OFF OFF Address 3 OFF OFF ON OFF OFF Address 4 ON OFF ON OFF OFF Address 5 OFF ON ON OFF OFF Address 6 ON ON ON...
Configuration Guide
Page 7
... It is recommended to RJ-45 on NS2 Panel 7 EG RS-232 (DB9) 8 CBL50 (RS-232) Request To Send (RTS) RJ-45 2 5 Signal Ground (GND) 3 2 Receive Data (RXD) 4 3 Transmit Data (TXD) 5 7 Clear To Send (CTS) 7 9-Pin COM 1 or COM 2 to earth ground (EG) each COM port. Honeywell Access Systems Configuration Diagrams RS-232 Connection One NS2 panel for each NS2 enclosure individually.
... It is recommended to RJ-45 on NS2 Panel 7 EG RS-232 (DB9) 8 CBL50 (RS-232) Request To Send (RTS) RJ-45 2 5 Signal Ground (GND) 3 2 Receive Data (RXD) 4 3 Transmit Data (TXD) 5 7 Clear To Send (CTS) 7 9-Pin COM 1 or COM 2 to earth ground (EG) each COM port. Honeywell Access Systems Configuration Diagrams RS-232 Connection One NS2 panel for each NS2 enclosure individually.
Configuration Guide
Page 8
Honeywell Access Systems NStar Server COM Port RS-232 (50 Ft. NCP2441-TN) DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: ...OFF (Bias) S10: ON (485 EOL) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) NS2 Panel NS2 Panel See RS-485 Cable note. EG It is recommended to 485-PCI / NS2 Panel Connection Detail diagram. Max.) RS-485 (4,000 Ft.) N-485-PCI-2...
Honeywell Access Systems NStar Server COM Port RS-232 (50 Ft. NCP2441-TN) DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: ...OFF (Bias) S10: ON (485 EOL) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) NS2 Panel NS2 Panel See RS-485 Cable note. EG It is recommended to 485-PCI / NS2 Panel Connection Detail diagram. Max.) RS-485 (4,000 Ft.) N-485-PCI-2...
Configuration Guide
Page 9
HUB NStar Server DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF NS2 Panel NSLAN1 installed EG 100BaseT (CAT 5) 328 Ft. Max. Max. Max. Honeywell Access Systems NSLAN1 Connection One NSLAN1 for programing instructions. It is recommended to earth ground (EG) each NS2 panel, Maximum sixty-four IP connections. NS2 Configuration Guide NIC 100BaseT (CAT 5) 328 Ft. NS2 Panel NSLAN1 installed 100BaseT...
HUB NStar Server DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF NS2 Panel NSLAN1 installed EG 100BaseT (CAT 5) 328 Ft. Max. Max. Max. Honeywell Access Systems NSLAN1 Connection One NSLAN1 for programing instructions. It is recommended to earth ground (EG) each NS2 panel, Maximum sixty-four IP connections. NS2 Configuration Guide NIC 100BaseT (CAT 5) 328 Ft. NS2 Panel NSLAN1 installed 100BaseT...
Configuration Guide
Page 10
... Honeywell Access Systems NIC 100BaseT (CAT 5) 328 Ft. EG It is recommended to earth ground (EG) each drop line, Maximum sixty-four IP connections. LANSRL100 DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) Refer to 485-PCI / NS2 Panel Connection Detail diagram...
... Honeywell Access Systems NIC 100BaseT (CAT 5) 328 Ft. EG It is recommended to earth ground (EG) each drop line, Maximum sixty-four IP connections. LANSRL100 DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) Refer to 485-PCI / NS2 Panel Connection Detail diagram...
Configuration Guide
Page 11
... Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. Honeywell Access Systems LANSRLU1 Connection Thirty-one side of cable. NStar Server HUB 100BaseT (CAT...
... Cable RS-485 NS2 Panel NS2 Panel Red/White TB9-1 (RS485+) TB9-1 (RS485+) Black/Green TB9-2 (RS485-) TB9-2 (RS485-) RS-485 COM TB9-3 (RS485 COM) TB9-3 (RS485 COM) 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no. Honeywell Access Systems LANSRLU1 Connection Thirty-one side of cable. NStar Server HUB 100BaseT (CAT...
Configuration Guide
Page 12
...23 pf (NCI part no. NCP2441-TN) 12 7-101004-01 NS2 Configuration Guide Lease Line Modem Connection Thirty-one side of cable. EG Only Earth Ground (EG) EG one NS2 panels for each NS2 enclosure individually. EG It is recommended to 485-PCI / NS2 Panel Connection Detail diagram. N-485-PCI...-2 Null Modem Cable Cable (9-25 Pin) Male 9 Pin (RX) 2 (TX) 3 (Comm) 5 Female 25 Pin 2 (TX) 3 (RX) 7 (Comm) RS-232 (50 Ft.) M-9600-LA RS-485 (4,000 Ft.) Honeywell Access Systems Lease Line Phone Line DIP Switch Settings S1: ON S2...
...23 pf (NCI part no. NCP2441-TN) 12 7-101004-01 NS2 Configuration Guide Lease Line Modem Connection Thirty-one side of cable. EG Only Earth Ground (EG) EG one NS2 panels for each NS2 enclosure individually. EG It is recommended to 485-PCI / NS2 Panel Connection Detail diagram. N-485-PCI...-2 Null Modem Cable Cable (9-25 Pin) Male 9 Pin (RX) 2 (TX) 3 (Comm) 5 Female 25 Pin 2 (TX) 3 (RX) 7 (Comm) RS-232 (50 Ft.) M-9600-LA RS-485 (4,000 Ft.) Honeywell Access Systems Lease Line Phone Line DIP Switch Settings S1: ON S2...
Configuration Guide
Page 13
Honeywell Access Systems RS-485 Short Haul Modem Connection Thirty-one side of cable. EG It is recommended to 485-PCI/NS2 Panel Connection Detail diagram. Max. Male 9 Pin Male 25 Pin Refer to earth ground (EG) each drop line. RS232 Cable PC (DB-9) 2 TX 3 RX 5 Comm MODEM DTE (Straight) DCE (..., 23 pf (NCI part no. SHM-B-ASYNC Short Haul Modem DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) N-485-PCI-2 RS-232, 50 Ft. NStar Server RS-232, 50 Ft. NCP2441-TN) NS2 Configuration Guide SHM-B-ASYNC Short...
Honeywell Access Systems RS-485 Short Haul Modem Connection Thirty-one side of cable. EG It is recommended to 485-PCI/NS2 Panel Connection Detail diagram. Max. Male 9 Pin Male 25 Pin Refer to earth ground (EG) each drop line. RS232 Cable PC (DB-9) 2 TX 3 RX 5 Comm MODEM DTE (Straight) DCE (..., 23 pf (NCI part no. SHM-B-ASYNC Short Haul Modem DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON S6: OFF (Ack/Nak on) S7: ON S8: OFF (19,200 Baud Rate) N-485-PCI-2 RS-232, 50 Ft. NStar Server RS-232, 50 Ft. NCP2441-TN) NS2 Configuration Guide SHM-B-ASYNC Short...
Configuration Guide
Page 14
...-232 Short Haul Modem Connection One NS2 panel for each NS2 enclosure individually. 14 SHM-B-ASYNC Short Haul Modem (RS-232 50 Ft. SHM-B-ASYNC Short Haul Modem Honeywell Access Systems RS232 Cable PC (DB-9) 2 TX 3 RX 5 Comm MODEM DTE (Straight) DCE (Null) 2 (TX) 3 (RX) or 7 (GND) 2 (RX) 3 (TX) 7 (GND) DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485...
...-232 Short Haul Modem Connection One NS2 panel for each NS2 enclosure individually. 14 SHM-B-ASYNC Short Haul Modem (RS-232 50 Ft. SHM-B-ASYNC Short Haul Modem Honeywell Access Systems RS232 Cable PC (DB-9) 2 TX 3 RX 5 Comm MODEM DTE (Straight) DCE (Null) 2 (TX) 3 (RX) or 7 (GND) 2 (RX) 3 (TX) 7 (GND) DIP Switch Settings S1-S5: Panel Address S6: OFF (RS-485...
Configuration Guide
Page 15
...: ON (485 EOL) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) 7-101004-01 EG DB 9 / DB 25 Connectors Female Male NS2 Panel NS2 Panel See RS-485 Cable note. NCP2441-TN) 15 Honeywell Access Systems M-9600 Dial-up Modem, RS-485 Connection Thirty-one side of cable.
...: ON (485 EOL) DIP Switch Settings S1-S5: Panel Address S6: ON (RS-485 Enable) S7: N/A (Baud Rate) S8-S9: OFF (Bias) S10: OFF (485 EOL) 7-101004-01 EG DB 9 / DB 25 Connectors Female Male NS2 Panel NS2 Panel See RS-485 Cable note. NCP2441-TN) 15 Honeywell Access Systems M-9600 Dial-up Modem, RS-485 Connection Thirty-one side of cable.
Configuration Guide
Page 16
... (NCI part no. NS2 Configuration Guide M-56K Dial-up Modem, RS-485 Connection Thirty-one side of cable. Honeywell Access Systems NStar Server Refer to earth ground (EG) each drop line. Only Earth Ground (EG) EG one NS2 panels for each NS2 Enclosure individually. N-485-HUB-2 COM Port Female 9 Pin (RX) 2 (TX) 3 (Comm) 5 Straight Thru Cable M-56K FAX/MODEM Local DIP Switch Settings...
... (NCI part no. NS2 Configuration Guide M-56K Dial-up Modem, RS-485 Connection Thirty-one side of cable. Honeywell Access Systems NStar Server Refer to earth ground (EG) each drop line. Only Earth Ground (EG) EG one NS2 panels for each NS2 Enclosure individually. N-485-HUB-2 COM Port Female 9 Pin (RX) 2 (TX) 3 (Comm) 5 Straight Thru Cable M-56K FAX/MODEM Local DIP Switch Settings...
Configuration Guide
Page 17
Honeywell Access Systems Fiber Converter to RS-485 Connection Thirty-one NS2 panels for each NS2 enclosure individually. RS-232 (50 Ft. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD Fiber TXD Fiber Wire 10,000 Ft. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD ...(BLACK/GREEN) RS-485 Drain Wire to 485-PCI/NS2 Panel Connection Detail diagram. Max.) NStar Server N-485-PCI-2 FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. NS2 Configuration Guide COM Port Refer to earth ground RS-485 Drain not connected here (connected at panel side) NS2 Panel TB9-3 (RS485 Comm) TB9...
Honeywell Access Systems Fiber Converter to RS-485 Connection Thirty-one NS2 panels for each NS2 enclosure individually. RS-232 (50 Ft. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD Fiber TXD Fiber Wire 10,000 Ft. RS-485 Positive(+) RS-485 Negitive (-) Fiber RXD ...(BLACK/GREEN) RS-485 Drain Wire to 485-PCI/NS2 Panel Connection Detail diagram. Max.) NStar Server N-485-PCI-2 FC485 RS-485 Fiber Converter RXD PWR TXD RS-485 Comm. NS2 Configuration Guide COM Port Refer to earth ground RS-485 Drain not connected here (connected at panel side) NS2 Panel TB9-3 (RS485 Comm) TB9...
Configuration Guide
Page 18
Honeywell Access Systems 485 Interface Connection Types RS-485 N-485-PCI-2 N-485-HUB-2 N-485-PCI-2L NS2 Panel COM Port M-56K Modem LANSRL100 or LANSRLU1 GROUND SHIELD X DO NOT CONNECT or GROUND SHIELD 12345 NS2 - NS2 Configuration Guide 485-PCI/NS2 Panel Connection Detail DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON ...) S10: OFF (485 EOL) 485 - GREEN BLACK RED WHITE 18 7-101004-01 COMMON DO NOT CONNECT SHIELD X 485 Common Shield 485 + Ground only one side of cable shield 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no.
Honeywell Access Systems 485 Interface Connection Types RS-485 N-485-PCI-2 N-485-HUB-2 N-485-PCI-2L NS2 Panel COM Port M-56K Modem LANSRL100 or LANSRLU1 GROUND SHIELD X DO NOT CONNECT or GROUND SHIELD 12345 NS2 - NS2 Configuration Guide 485-PCI/NS2 Panel Connection Detail DIP Switch Settings S1: ON S2: ON S3: ON S4: ON S5: ON ...) S10: OFF (485 EOL) 485 - GREEN BLACK RED WHITE 18 7-101004-01 COMMON DO NOT CONNECT SHIELD X 485 Common Shield 485 + Ground only one side of cable shield 4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with shield, 120 ohm, 23 pf (NCI part no.
Configuration Guide
Page 19
... to WIN-PAK 2.0? Honeywell Access Systems recommends the PB-VC-15 or higher capture card. Please contact Honeywell Access Systems for RS-232 is via RS-485 or TCP/IP. What is designed to save on installation space? Can the NS2 panel be used with the NStar access control system? Yes, the NS2 panel is the maximum distance I can I upgrade my NStar software to run the RS-232 connection?
... to WIN-PAK 2.0? Honeywell Access Systems recommends the PB-VC-15 or higher capture card. Please contact Honeywell Access Systems for RS-232 is via RS-485 or TCP/IP. What is designed to save on installation space? Can the NS2 panel be used with the NStar access control system? Yes, the NS2 panel is the maximum distance I can I upgrade my NStar software to run the RS-232 connection?
Configuration Guide
Page 20
... NS2 panel support Anti-Passback? Power down again by removing backup battery then removing AC power. 5. It is solid. Honeywell Access Systems NS2 Configuration Guide Question: Can the NS2 panel run in this document have not been reviewed by Underwriters Laboratories. Yes. The XPort expansion port allows for ? Question: What is a "Plug and Play" memory board that any time zone assigned to download current data. The NS2MEM module is the NS2MEM used...
... NS2 panel support Anti-Passback? Power down again by removing backup battery then removing AC power. 5. It is solid. Honeywell Access Systems NS2 Configuration Guide Question: Can the NS2 panel run in this document have not been reviewed by Underwriters Laboratories. Yes. The XPort expansion port allows for ? Question: What is a "Plug and Play" memory board that any time zone assigned to download current data. The NS2MEM module is the NS2MEM used...