... shorter than 7.5m(25ft) for tri - Max total length Max length of Capacity (Btu/h) of all pipes each indoor line. zone 5 additional ft X 0.22 ounces per meter(foot). Charging Charging s Each outdoor unit is factory charged (nameplate charge) for the... evaporator as well as a 7.5m(25ft) line set for tri-zone) line set length the refrigerant charge has to be adjusted. Any time total line set is used either added or ...5m(25ft) 20g/m(0.22oz/ft) Example: A 80ft line set is used for each indoor unit. 38 Multi type Air Conditioner
... shorter than 7.5m(25ft) for tri - Max total length Max length of Capacity (Btu/h) of all pipes each indoor line. zone 5 additional ft X 0.22 ounces per meter(foot). Charging Charging s Each outdoor unit is factory charged (nameplate charge) for the... evaporator as well as a 7.5m(25ft) line set for tri-zone) line set length the refrigerant charge has to be adjusted. Any time total line set is used either added or ...5m(25ft) 20g/m(0.22oz/ft) Example: A 80ft line set is used for each indoor unit. 38 Multi type Air Conditioner