Honeywell HPFF12 Support and Manuals

Get Help and Manuals for this Honeywell item

View All Support Options Below
Free Honeywell HPFF12 manuals!
Problems with Honeywell HPFF12?

Ask a Question

Popular Honeywell HPFF12 Manual Pages

Operation Manual - Page 5

... 5.3.2: Split Alarm Mode ...45 5.4: Connecting Multiple Units ...46 Section 6: Power Supply Requirements 48 6.1: Overview...48 6.2: Calculating the AC Branch Circuit Current...48 6.3: Calculating the System Current Draw ...49 6.3.1: Overview ...49 6.3.2: How to Calculate System Current Draw 50 6.4: Calculating the Battery Size ...51 6.4.1: NFPA Battery Requirements ...51 HPFF12 NAC Expander -
Operation Manual - Page 9

...NAC outputs. P/N 53576:B 11/24/2010 9 It contains an internal battery charger capable of the most innovative fire alarm remote power supplies available that complies with 12 VDC or 24 VDC control panels. these models. (Equipment enclosures available through authorized Honeywell Fire Systems distributors.) HPFF12, and HPFF12CM power supply models operate at 240 VAC/50 Hz. The Fire Alarm...
Operation Manual - Page 10

... Individual NAC Trouble LEDs • Maximum current for any one Class A (Style Z) NACs (special application). - For lead-acid batteries only. - Filtered for full-wave-rectified polarity-reversing inputs or reducing spurious noise to accommodate Honeywell Fire Systems branded panels: Honeywell, Notifier, Gamewell FCI, Silent Knight, and FireLite Alarms. • 24 VDC remote power supply. •...
Operation Manual - Page 11

... to the TB1 on page 17. 3. P/N 53576:B 11/24/2010 11 Start-up Procedure 1. Aids installer or repair personnel to find the location of initiating device input signal for Trouble indication at device or FACP. - Configure the power supply jumpers as described in Section 5, "Applications", on the AC mains circuit breaker connected to 22 AWG...
Operation Manual - Page 12

...system requires a common battery set, as a single battery connected to any user wiring point, including +24 VDC. Larger capacity batteries can charge in ...power supplies are located on the control circuit board; The HPFF12 models have an installed 12.0 A power supply. CAUTION: THE BATTERY CHARGER IS AUTOMATICALLY DISABLED DURING ALARM, SO BATTERIES WILL NOT BE CHARGED WHEN THE POWER SUPPLY...
Operation Manual - Page 14

...; Supervised, non-power-limited. • Supports lead-acid type batteries only. • Float charge voltage: 26.6 VDC. • Charger disabled if battery voltage falls below for all outputs: HPFF12, HPFF12CM, HPFF12E, HPFF12CME: 12.0 A • Output circuit types: - P/N 53576:B 11/24/2010 System Overview Specifications End-of 75 mA from batteries. 14 HPFF12 NAC Expander - terminals...
Operation Manual - Page 30

.... See Section 2.5, "Power-Limited Wiring Requirements". P/N 53576:B 11/24/2010 For a list of a six-output addressable module can be used in the HPFF12CM(E) units. Alternately, two outputs of compatible optional modules that can also be connected to remain in Figure 2.14 for Control & Relay Modules from Honeywell Fire Systems 30 HPFF12 NAC Expander - Mounting...
Operation Manual - Page 31

... Your specific application may be used in the large equipment enclosure. Any conduit knockouts may require different conduit knockouts to remain in the cabinet. For power-limited applications, use of this is available from any non-power-limited circuit wiring. Power-Limited Wiring Requirements Installation 2.4.2 Mounting Six-Circuit Modules from Honeywell Fire System 2.5 Power-Limited...
Operation Manual - Page 39

... Auto Field Wiring (NAC & +/- Section 4: Trouble Supervision 4.1 Supervised Functions and Field Wiring • Field-wiring fault (short or open) on the NAC outputs of the power supply • AC failure or brownout at the power supplyBattery failure (no battery or battery voltage less than 20.5 VDC) condition at the power supplyBattery charger failure on TB3 are not...
Operation Manual - Page 40

... LED3: SIG3 TRBL Steady Illumination SW1 or Power cycle LED4: SIG4 TRBL Steady Illumination SW1 or Power cycle Ground Fault (Note 1) (Note 2) closed LED5: GF TRBL Steady Illumination Auto Battery No battery or LED1: SIG1 TRBL Steady Illumination SW1 or Power cycle Field Wiring (NAC & +/- Trouble Supervision Trouble Reporting Alarm Alarm Trouble contacts Fault TB2: AC TB2: TB3...
Operation Manual - Page 45

...two outputs of 1&2 and 3&4. Install jumpers supplied with two synchronized (System Sensor protocol) and two non-synchronized outputs. When the power supply is connected to an addressable control module which controls output circuits 3 & 4. Section 4.1, "Supervised Functions and Field Wiring". 2. There must be used and mounted on . HPFF12 NAC Expander - Control module #2 will...
Operation Manual - Page 50

... ] = Auxiliary Output Current Draw from Column 2 and Column 3 to the specifications of current that the power supply must support during a loss of devices in alarm. Current limitation on page 50. • Calculation Column 1 - Power Supply Requirements Calculating the System Current Draw 6.3.2 How to Calculate System Current Draw Use Table 6.4 to Table 6.5. Sum the total current for...
Operation Manual - Page 51

... the sum by 5 minutes in alarm 6.4.2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hours calculated in AH) required to support the power supply under the loss of the large equipment enclosure. This total load determines the battery size (in Table 6.5. The power supply can be used for Standby and Alarm conditions, then sum...
Operation Manual - Page 59

...dimensions 18, 19, 20 Calculating AC branch circuit current 48 Battery Size 51 Power supply currents 48 System Current Draw 49, 50 Calculating fire alarm load 49 Calculating power supply requirements procedures 48 Charger Disable... contacts (also see TROUBLE and AC FAIL) 11 G Ground Fault Detection 41 Ground Fault Disable Jumper (J2) 12 ground monitoring 12 H HPFF12CM installation 21 HPP31076 29 I...
Operation Manual - Page 60

... Dip switch settings Programming input/output functions 36 S Secondary power supply (defined) 49 Selecting and Locating Batteries 51 Selective silence 44 Semi-flush Mounting 19, 27 SIGNAL 1, SIGNAL 2 40, 41 Silencing 38 Silencing, see Selective silence Six-circuit modules 53 Specifications 13-16 Split alarm 38 Split alarm mode 45 Standards 7 Standby load calculations 51 Start...

Honeywell HPFF12 Reviews

Do you have an experience with the Honeywell HPFF12 that you would like to share?
Earn 750 points for your review!
We have not received any reviews for Honeywell yet.

Popular Honeywell HPFF12 Search Terms

The following terms are frequently used to search for Honeywell HPFF12 support:

Ask a New Question
Use the box below to post a new question about Honeywell HPFF12.
Manuals / Documents
Download any of our Honeywell HPFF12 manuals for free!

We have the following 1 documents available for the Honeywell HPFF12:
  • Operation Manual

Points & Prizes
  • You can earn points for nearly everything you do on HelpOwl.com
  • You can trade in those points for gift cards at leading retailers such as Amazon.com and Walmart
  • It's that simple!
See How it Works
Create a Free Account

Honeywell Manuals

Find free Honeywell HPFF12 manuals and user guides available at ManualOwl.com. Try out our unique manual viewer allowing you to interact with manuals from directly within your browser!

Honeywell Reviews

View thousands of Honeywell HPFF12 user reviews and customer ratings available at ReviewOwl.com.

Contact Information

Complete Honeywell customer service contact information including steps to reach representatives, hours of operation, customer support links and more from ContactHelp.com.

Scoreboard Ratings

See detailed Honeywell customer service rankings, employee comments and much more from our sister site.

Honeywell Recalls

Find comprehensive Honeywell recall information updated hourly on RecallOwl.com.