CSW24VDC Installation Manual
Page 2
...COVER 21 ADJUSTMENT 22 LIMIT AND FORCE ADJUSTMENT 22 PROGRAMMING 24 REMOTE CONTROLS (NOT PROVIDED 24 LIFTMASTER INTERNET GATEWAY(NOT PROVIDED 25 ERASE ALL CODES 25 ERASE LIMITS 25 TO REMOVE AND ERASE MONITORED ENTRAPMENT PROTECTION DEVICES 25 OPERATION 26 GATE OPERATOR...WIRING ACCESSORIES TO THE EXPANSION BOARD 33 MAINTENANCE 34 IMPORTANT SAFETY INFORMATION 34 MAINTENANCE CHART 34 BATTERIES 34 TROUBLESHOOTING 35 ERROR CODES 35 CONTROL BOARD LEDS 38 TROUBLESHOOTING CHART 39 APPENDIX 42 INSTALLATION TYPES 42 DETERMINE LOCATION FOR CONCRETE PAD AND OPERATOR...
...COVER 21 ADJUSTMENT 22 LIMIT AND FORCE ADJUSTMENT 22 PROGRAMMING 24 REMOTE CONTROLS (NOT PROVIDED 24 LIFTMASTER INTERNET GATEWAY(NOT PROVIDED 25 ERASE ALL CODES 25 ERASE LIMITS 25 TO REMOVE AND ERASE MONITORED ENTRAPMENT PROTECTION DEVICES 25 OPERATION 26 GATE OPERATOR...WIRING ACCESSORIES TO THE EXPANSION BOARD 33 MAINTENANCE 34 IMPORTANT SAFETY INFORMATION 34 MAINTENANCE CHART 34 BATTERIES 34 TROUBLESHOOTING 35 ERROR CODES 35 CONTROL BOARD LEDS 38 TROUBLESHOOTING CHART 39 APPENDIX 42 INSTALLATION TYPES 42 DETERMINE LOCATION FOR CONCRETE PAD AND OPERATOR...
CSW24VDC Installation Manual
Page 28
... dial adjusts the force. See Bipart Delay section. 6 LEARN Button: The LEARN button is reset by a "24" which indicates the operator type as CSW24VDC. See Adjust Limits section. 4 BATT FAIL: • When AC power is OFF and battery voltage is critically low the gate will either open or... gate to automatically open and then latch at CLOSE limit or on next CLOSE command until AC power is in the Troubleshooting section. 11 Error Code Display: The error code display will remain open controls, loops, close edges, and close the gate. If the TTC is 0 to the desired setting. The ...
... dial adjusts the force. See Bipart Delay section. 6 LEARN Button: The LEARN button is reset by a "24" which indicates the operator type as CSW24VDC. See Adjust Limits section. 4 BATT FAIL: • When AC power is OFF and battery voltage is critically low the gate will either open or... gate to automatically open and then latch at CLOSE limit or on next CLOSE command until AC power is in the Troubleshooting section. 11 Error Code Display: The error code display will remain open controls, loops, close edges, and close the gate. If the TTC is 0 to the desired setting. The ...
CSW24VDC Installation Manual
Page 36
... will only keep track of each error code. TO RESET THE ERROR CODE HISTORY 1. The error history has now been reset and the display will also time out after the error sequence number is the most recent errors ("01"). TO VIEW THE ERROR CODES The error codes are shown on the following page ...cycling or disconnecting power (ac/dc) to "20"). AC & BATT FAIL BACKDRIVE TO SCROLL THROUGH THE SAVED ERROR CODES TO EXIT ERROR CODE DISPLAY Press and release the STOP button to error "20". A SECOND LATER.... For continued protection against fire and electrocution: • DISCONNECT power (AC or ...
... will only keep track of each error code. TO RESET THE ERROR CODE HISTORY 1. The error history has now been reset and the display will also time out after the error sequence number is the most recent errors ("01"). TO VIEW THE ERROR CODES The error codes are shown on the following page ...cycling or disconnecting power (ac/dc) to "20"). AC & BATT FAIL BACKDRIVE TO SCROLL THROUGH THE SAVED ERROR CODES TO EXIT ERROR CODE DISPLAY Press and release the STOP button to error "20". A SECOND LATER.... For continued protection against fire and electrocution: • DISCONNECT power (AC or ...
CSW24VDC Installation Manual
Page 37
...-adjust limit). Check harness. Make sure you do NOT have a 24V battery on main board; Failure or missing interrupt loop (SHORT or OPEN - LiftMaster Plug-in the error code history and some are saved in Loop Detector only) Check loop wiring throughout connection. CLOSE EYE/INTERRUPT held more than 3 minutes Check wired input...
...-adjust limit). Check harness. Make sure you do NOT have a 24V battery on main board; Failure or missing interrupt loop (SHORT or OPEN - LiftMaster Plug-in the error code history and some are saved in Loop Detector only) Check loop wiring throughout connection. CLOSE EYE/INTERRUPT held more than 3 minutes Check wired input...
CSW24VDC Installation Manual
Page 38
..., no action required. If an obstruction did NOT occur, check inputs and wiring. Check for obstruction. Some errors are saved in the error code history and some are not. Error Code 66 67 68 69 70 71 72 73 74 75 80 81 82 83 91 93 99 Meaning OPEN EYE...(expansion board) Open input (EYE/EDGE) communication fault (expansion board) Force reversal RPM / STALL Reversal Normal Operation Solution Check wired input on the error code display as it will briefly appear on expansion board; IF an obstruction occurred, no action required. IF an obstruction occurred, no action required. IF...
..., no action required. If an obstruction did NOT occur, check inputs and wiring. Check for obstruction. Some errors are saved in the error code history and some are not. Error Code 66 67 68 69 70 71 72 73 74 75 80 81 82 83 91 93 99 Meaning OPEN EYE...(expansion board) Open input (EYE/EDGE) communication fault (expansion board) Force reversal RPM / STALL Reversal Normal Operation Solution Check wired input on the error code display as it will briefly appear on expansion board; IF an obstruction occurred, no action required. IF an obstruction occurred, no action required. IF...
CSW24VDC Installation Manual
Page 40
... battery power only, low or dead batteries c) Charge batteries by AC or solar power or replace batteries Gate opens, but motor does not run and error code b) Open fuse b) Check fuses display not on " detector Operator does not respond to a wireless control or transmitter a) Check XMITTER LED when wireless control is active...
... battery power only, low or dead batteries c) Charge batteries by AC or solar power or replace batteries Gate opens, but motor does not run and error code b) Open fuse b) Check fuses display not on " detector Operator does not respond to a wireless control or transmitter a) Check XMITTER LED when wireless control is active...