Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) A Dell™ Technical White Paper Dell™ │ Datacenter Infrastructure Engineering By Daniel Whittaker and Jose L. Flores August 2010
Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) A Dell™ Technical White Paper Dell™ │ Datacenter Infrastructure Engineering By Daniel Whittaker and Jose L. Flores August 2010
User Manual
Page 2
... forbidden. Reproduction of this material in any manner whatsoever without the express written permission of Dell Inc. Dell, the DELL logo, the DELL badge, and PowerEdge are trademarks of Dell Inc. Page ii Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL ERRORS AND TECHNICAL...
... forbidden. Reproduction of this material in any manner whatsoever without the express written permission of Dell Inc. Dell, the DELL logo, the DELL badge, and PowerEdge are trademarks of Dell Inc. Page ii Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL ERRORS AND TECHNICAL...
User Manual
Page 3
Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Contents Introduction ...3 Section 1: 0U Mounting Locations...3 1.1 Supported Locations in the PowerEdge™ 4210 and 2410 3 1.2 Supported Locations in the PowerEdge™ 4820, 4220, and 2420 5 Section 2: 1U Mounting Locations...6 2.1 Mounting the KVM in the Front of the Rack 6 2.2 Mounting the KVM in the Back of the Rack...
Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Contents Introduction ...3 Section 1: 0U Mounting Locations...3 1.1 Supported Locations in the PowerEdge™ 4210 and 2410 3 1.2 Supported Locations in the PowerEdge™ 4820, 4220, and 2420 5 Section 2: 1U Mounting Locations...6 2.1 Mounting the KVM in the Front of the Rack 6 2.2 Mounting the KVM in the Back of the Rack...
User Manual
Page 4
Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Page 2
Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Page 2
User Manual
Page 5
... the right side. The PowerEdge 4210 supports mounting four digital KVMs on the vertical members, two on the left side and one on the right side. Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Introduction This white paper covers recommended mounting and cable routing procedures for Dell™ Digital KVMs (1082DS, 2162DS, 4322DS) in the following sections...
... the right side. The PowerEdge 4210 supports mounting four digital KVMs on the vertical members, two on the left side and one on the right side. Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Introduction This white paper covers recommended mounting and cable routing procedures for Dell™ Digital KVMs (1082DS, 2162DS, 4322DS) in the following sections...
User Manual
Page 6
Mounting and Cable Routing Procedures for the supported locations to the KVM. See Figures 1 and 2 for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Please note that installation of the KVM where the ports face the ground is an unsupported orientation, and can cause damage to mount the Digital KVM in the aforementioned racks. Figure 1: KVM Mounted on Vertical Member PowerEdge 4210 Vertical Top PowerEdge 2410 Vertical Page 4
Mounting and Cable Routing Procedures for the supported locations to the KVM. See Figures 1 and 2 for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Please note that installation of the KVM where the ports face the ground is an unsupported orientation, and can cause damage to mount the Digital KVM in the aforementioned racks. Figure 1: KVM Mounted on Vertical Member PowerEdge 4210 Vertical Top PowerEdge 2410 Vertical Page 4
User Manual
Page 7
... 1.2 Supported Locations in the aforementioned racks. Please note that installation of the rack. See Figure 3 for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 2: KVM Mounted on the right side, top and bottom. The 0U mounting space on the PowerEdge 4820, 4220, and 2420 offers restricted access to the ports on the right side. Mounting and Cable...
... 1.2 Supported Locations in the aforementioned racks. Please note that installation of the rack. See Figure 3 for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 2: KVM Mounted on the right side, top and bottom. The 0U mounting space on the PowerEdge 4820, 4220, and 2420 offers restricted access to the ports on the right side. Mounting and Cable...
User Manual
Page 8
Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 3: KVM Mounted on Vertical Member PowerEdge 4220 Vertical Top PowerEdge 2420 Vertical Section 2: 1U Mounting Locations 1U mounting is located on the port side. In the event that your rack temperature exceeds this configuration a 1U ...
Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 3: KVM Mounted on Vertical Member PowerEdge 4220 Vertical Top PowerEdge 2420 Vertical Section 2: 1U Mounting Locations 1U mounting is located on the port side. In the event that your rack temperature exceeds this configuration a 1U ...
User Manual
Page 9
... It is easier to hold the cables (user supplied). Once installed, use these instructions to install the KVM into the front of the rack. Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) 3.1 Four Post Front of Rack Cabling Follow the instructions contained in the following sections were created using ...and Cables Installed 3.1.2 Routing the Power Cables and Data Cables 1.) After you have installed cables, route the power cables to one side, using the Dell KVM 4322DS. 3.1.1 Connecting the Cables to the KVM Connect all connections are secure.
... It is easier to hold the cables (user supplied). Once installed, use these instructions to install the KVM into the front of the rack. Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) 3.1 Four Post Front of Rack Cabling Follow the instructions contained in the following sections were created using ...and Cables Installed 3.1.2 Routing the Power Cables and Data Cables 1.) After you have installed cables, route the power cables to one side, using the Dell KVM 4322DS. 3.1.1 Connecting the Cables to the KVM Connect all connections are secure.
User Manual
Page 10
... two post rack. See Figure 7. See Figure 6 (front and back view of the removable portion of rail Page 8 Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 5: Four Post Rack: Routing Power and Data Cables 3.2 Two Post Flush Mount Cabling Follow the instructions contained in the following sections were created...
... two post rack. See Figure 7. See Figure 6 (front and back view of the removable portion of rail Page 8 Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 5: Four Post Rack: Routing Power and Data Cables 3.2 Two Post Flush Mount Cabling Follow the instructions contained in the following sections were created...
User Manual
Page 11
Figure 8: Two Post Rack: Routing Power and Data Cables Page 9 Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 7: Two Post Rack: System and Cables Installed 3.2.2 Routing the Power Cables and Data Cables 1.) After you have installed cables, route the power cables to ...
Figure 8: Two Post Rack: Routing Power and Data Cables Page 9 Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 7: Two Post Rack: System and Cables Installed 3.2.2 Routing the Power Cables and Data Cables 1.) After you have installed cables, route the power cables to ...
User Manual
Page 12
... a monitor. Acronyms: Virtual Media (VM) Common Access Card (CAC) Table 2: Dell KVM Resolution by Dell KVM model. Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 9: Two Post Rack: Routing Power and Data Cables (Optional Tie) Section 4: KVM Resolution Information 4.1 Dell KVM Resolution by Model Table 2 below shows the resolutions supported by Model Model 180AS...
... a monitor. Acronyms: Virtual Media (VM) Common Access Card (CAC) Table 2: Dell KVM Resolution by Dell KVM model. Mounting and Cable Routing Procedures for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) Figure 9: Two Post Rack: Routing Power and Data Cables (Optional Tie) Section 4: KVM Resolution Information 4.1 Dell KVM Resolution by Model Table 2 below shows the resolutions supported by Model Model 180AS...
User Manual
Page 13
... Y Y+ Y+ Y+ ‐ Y USB 2.0 + CAC User Selectable Y Y Y Y Y ‐ SIP + Requires the user to the OS cannot be changed from 1024x768 for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) 4.2 Server Interface Pod Matrix Tables 3 & 4 below show information about Dell Server Interface Pods (SIPs). Mounting and Cable Routing Procedures for the Local Port. CAC Support N N N Y Table 4: Server Interface Pod Matrix...
... Y Y+ Y+ Y+ ‐ Y USB 2.0 + CAC User Selectable Y Y Y Y Y ‐ SIP + Requires the user to the OS cannot be changed from 1024x768 for Dell™ Digital KVM's (1082DS, 2162DS, 4322DS) 4.2 Server Interface Pod Matrix Tables 3 & 4 below show information about Dell Server Interface Pods (SIPs). Mounting and Cable Routing Procedures for the Local Port. CAC Support N N N Y Table 4: Server Interface Pod Matrix...
Dell 1082DS/2162DS/4322DS Remote Console Switch Software User's Guide
Page 1
All rights reserved. 1082DS/2162DS/4322DS Remote Console Switch WARNING: A WARNING indicates a potential for property damage, personal injury or death. Dell™ Remote Console Switch Software User's Guide Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better use of data if instructions are not followed. CAUTION: A CAUTION indicates potential damage to change without notice. © 2010 Dell Inc. Information in this document is subject to hardware or loss of your computer.
All rights reserved. 1082DS/2162DS/4322DS Remote Console Switch WARNING: A WARNING indicates a potential for property damage, personal injury or death. Dell™ Remote Console Switch Software User's Guide Notes, Cautions, and Warnings NOTE: A NOTE indicates important information that helps you make better use of data if instructions are not followed. CAUTION: A CAUTION indicates potential damage to change without notice. © 2010 Dell Inc. Information in this document is subject to hardware or loss of your computer.
Dell 1082DS/2162DS/4322DS Remote Console Switch Software User's Guide
Page 2
... implied warranty of merchantability or fitness for any way out of Red Hat, Inc. loss of use of this text: Dell, the DELL logo, and Dell OpenManage are registered trademarks of the use , data or profits; is a registered trademark of Intel Corporation in the US ..., exemplary, or consequential damages (including, but is a registered trademark of Avocent Corporation or its own. 590-1022-501A August 2010 Model 1082DS/2162DS/4322DS Remote Console Switch and other countries; Avocent is strictly forbidden. Red Hat and Red Hat Enterprise Linux are trademarks of VMware, Inc. in...
... implied warranty of merchantability or fitness for any way out of Red Hat, Inc. loss of use of this text: Dell, the DELL logo, and Dell OpenManage are registered trademarks of the use , data or profits; is a registered trademark of Intel Corporation in the US ..., exemplary, or consequential damages (including, but is a registered trademark of Avocent Corporation or its own. 590-1022-501A August 2010 Model 1082DS/2162DS/4322DS Remote Console Switch and other countries; Avocent is strictly forbidden. Red Hat and Red Hat Enterprise Linux are trademarks of VMware, Inc. in...
Dell 1082DS/2162DS/4322DS Remote Console Switch Software User's Guide
Page 8
... local database. functions, such as Appliances and Devices provide different ways to list units. 2 Product Overview System Components The software contains the following Dell switches: • 4322DS • 2162DS • 1082DS • 2161DS • 2321DS • 4161DS • 2161DS-2 Authentication and Authorization The RCS software allows permissions for multiple Remote Console Switches to be...
... local database. functions, such as Appliances and Devices provide different ways to list units. 2 Product Overview System Components The software contains the following Dell switches: • 4322DS • 2162DS • 1082DS • 2161DS • 2321DS • 4161DS • 2161DS-2 Authentication and Authorization The RCS software allows permissions for multiple Remote Console Switches to be...
Dell 1082DS/2162DS/4322DS Remote Console Switch Software User's Guide
Page 85
...are separate; The media will support up to the target device. • A 1082DS will be available in a virtual media device, you must support the types of...SIP, Dell USB2+CAC SIP, Avocent MPUIQ-VMC, DSAVIQ-PS2M, or DSAVIQ-USB2 module must be used to connect that server to the KVM. ...which you belong) must have one DVD-ROM drive and one time. A 2162DS will support up to a target device at one mass storage device mapped concurrently... or ISO disk image file is mapped as a virtual DVD drive. - A 4322DS will support up to a passive expansion module. • The target device must ...
...are separate; The media will support up to the target device. • A 1082DS will be available in a virtual media device, you must support the types of...SIP, Dell USB2+CAC SIP, Avocent MPUIQ-VMC, DSAVIQ-PS2M, or DSAVIQ-USB2 module must be used to connect that server to the KVM. ...which you belong) must have one DVD-ROM drive and one time. A 2162DS will support up to a target device at one mass storage device mapped concurrently... or ISO disk image file is mapped as a virtual DVD drive. - A 4322DS will support up to a passive expansion module. • The target device must ...