Owner's Manual for Battery Module Compartment Model: SUBF2030 932653
Page 1
... ** Model #s: SU20K3/3, SU20K3/3XR5, SU30K3/3, SU30K3/3XR5, SU20K3/3INT, SU20K3/3INTXR5, SU30K3/3INT and SU30K3/3INTXR5. Mounting bracket installation is heavy. See UPS system owner's manual for serious personal injury. • The battery module compartment's caster wheels are shipped with user-supplied hardware. When used with compatible products (UPS systems and internal battery packs) include additional safety instructions that the included cable can be turned...
... ** Model #s: SU20K3/3, SU20K3/3XR5, SU30K3/3, SU30K3/3XR5, SU20K3/3INT, SU20K3/3INTXR5, SU30K3/3INT and SU30K3/3INTXR5. Mounting bracket installation is heavy. See UPS system owner's manual for serious personal injury. • The battery module compartment's caster wheels are shipped with user-supplied hardware. When used with compatible products (UPS systems and internal battery packs) include additional safety instructions that the included cable can be turned...
Owner's Manual for Battery Module Compartment Model: SUBF2030 932653
Page 2
... defects in accordance with all applicable instructions, to the standalone battery module compartment. See website for instructions. Tripp Lite follows a policy of these devices for any specific application.. To reach the internal connectors, run it on, depending on the procedure you followed in the same manner. See UPS system owner's manual for details. Service under this product, if used...
... defects in accordance with all applicable instructions, to the standalone battery module compartment. See website for instructions. Tripp Lite follows a policy of these devices for any specific application.. To reach the internal connectors, run it on, depending on the procedure you followed in the same manner. See UPS system owner's manual for details. Service under this product, if used...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 1
... 9 4 5.3 Operation Under Shutdown 9 5 5.4 Operation Of Manual Bypass Switch 9 6 6. Adding or Replacing Internal Batteries 11 7 7.1 Internal Battery Pack Wiring Diagram 12 7 8. cprhreWoaRgdnieasuctcegretrr-itaosonwtnwrlwtiiannywtea.itotrFoinpdRpa:ElyitEefo.Tcrroiapmp/wLiaterranty Owner's Manual SmartOnline™ 3-Phase 20kVA & 30kVA Intelligent True On-Line UPS Systems Input/Output Voltage: 120/208V AC, 3ø, 4 wire (plus ground), wye Table of Tripp Lite. Specifications 17 7 Español 19 8 Fran...
... 9 4 5.3 Operation Under Shutdown 9 5 5.4 Operation Of Manual Bypass Switch 9 6 6. Adding or Replacing Internal Batteries 11 7 7.1 Internal Battery Pack Wiring Diagram 12 7 8. cprhreWoaRgdnieasuctcegretrr-itaosonwtnwrlwtiiannywtea.itotrFoinpdRpa:ElyitEefo.Tcrroiapmp/wLiaterranty Owner's Manual SmartOnline™ 3-Phase 20kVA & 30kVA Intelligent True On-Line UPS Systems Input/Output Voltage: 120/208V AC, 3ø, 4 wire (plus ground), wye Table of Tripp Lite. Specifications 17 7 Español 19 8 Fran...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 2
... phase rated in bypass mode. • The UPS system ships with air, oxygen or nitrous oxide. • The UPS system contains its safety or effectiveness is required. (See section 3, Installation.) UPS Connection Warnings • The power supply for the UPS system after final installation. Battery replacement should be replaced only with any reason; they are no user-serviceable parts inside . Do...
... phase rated in bypass mode. • The UPS system ships with air, oxygen or nitrous oxide. • The UPS system contains its safety or effectiveness is required. (See section 3, Installation.) UPS Connection Warnings • The power supply for the UPS system after final installation. Battery replacement should be replaced only with any reason; they are no user-serviceable parts inside . Do...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 3
...alarm. 5. Simultaneously press the "ENTER" Button and the "SELECT" Button and hold for a ¼ second. "BYPASS" LED: This yellow light will not receive battery power in "Bypass Mode." "DC/AC" (Inverter) LED: This green light will illuminate constantly to recharge. To reset the UPS System and restore output, press the "Emergency Power...ENTER" or "ON." "BATTERY" LED: This red light will remain illuminated. 10. "EMERGENCY POWER OFF" Button: This button turns the UPS output OFF and disables Bypass output. An alarm will sound which can be muted, but the LED will flash when the UPS ...
...alarm. 5. Simultaneously press the "ENTER" Button and the "SELECT" Button and hold for a ¼ second. "BYPASS" LED: This yellow light will not receive battery power in "Bypass Mode." "DC/AC" (Inverter) LED: This green light will illuminate constantly to recharge. To reset the UPS System and restore output, press the "Emergency Power...ENTER" or "ON." "BATTERY" LED: This red light will remain illuminated. 10. "EMERGENCY POWER OFF" Button: This button turns the UPS output OFF and disables Bypass output. An alarm will sound which can be muted, but the LED will flash when the UPS ...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 4
... negative). The other connector (shown) connects the battery module to the Adding or Replacing Internal Batteries section for battery connection instructions. 2. Internal Battery Pack Jumper Cables (White & Blue): Connect the internal battery pack strings together through the fuse block. 5. Control Panels (continued) 2.2 Battery Access Panel (Cover Removed) Individual models may vary slightly from Tripp Lite). Battery packs must be replaced by a qualified electrician.
... negative). The other connector (shown) connects the battery module to the Adding or Replacing Internal Batteries section for battery connection instructions. 2. Internal Battery Pack Jumper Cables (White & Blue): Connect the internal battery pack strings together through the fuse block. 5. Control Panels (continued) 2.2 Battery Access Panel (Cover Removed) Individual models may vary slightly from Tripp Lite). Battery packs must be replaced by a qualified electrician.
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 5
... system during "BYPASS" operation. 12. Mounting bracket installation is on "BYPASS," connected equipment will receive filtered AC mains power, but will not receive battery power in "BYPASS" mode, which must be done before performing any maintenance on the UPS with Tripp Lite software and an RS-232 Cable to monitor and manage network power and to turn it is required. (See Installation section.) 15...
... system during "BYPASS" operation. 12. Mounting bracket installation is on "BYPASS," connected equipment will receive filtered AC mains power, but will not receive battery power in "BYPASS" mode, which must be done before performing any maintenance on the UPS with Tripp Lite software and an RS-232 Cable to monitor and manage network power and to turn it is required. (See Installation section.) 15...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 6
... installation. Mounting bracket installation is required. UPS System Model 20kVA 30kVA Wiring Size 6 AWG / 14 mm2 4 AWG / 22 mm2 Maximum Cable Length: 10 m (32.8 ft) 6 Front View 3.3 Grounding Connection Using a user-supplied 4 AWG ground wire, connect the UPS System's ground lug to earth ground. Installation 3.1 UPS Location Move your UPS to provide long-term support for servicing...
... installation. Mounting bracket installation is required. UPS System Model 20kVA 30kVA Wiring Size 6 AWG / 14 mm2 4 AWG / 22 mm2 Maximum Cable Length: 10 m (32.8 ft) 6 Front View 3.3 Grounding Connection Using a user-supplied 4 AWG ground wire, connect the UPS System's ground lug to earth ground. Installation 3.1 UPS Location Move your UPS to provide long-term support for servicing...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 7
...of your UPS (see section 3, Installation) and the Manual Bypass Switch is set to NORMAL. • Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON. • If your AC input is not providing power normally, you turn the UPS ON, it should follow ...: (possible only with the "Battery Start" Switch) SELF TESTING... The LCD Display will still be turned back on . Qualified personnel should be energized. CAUTION! and other local codes for 24 hours after initial installation. 4. BATTERY OK DC TO DC OK INVERTER TEST 7 Note that cables are connected...
...of your UPS (see section 3, Installation) and the Manual Bypass Switch is set to NORMAL. • Turn the AC Main Input Switch and Bypass Input Switch Circuit Breakers ON. • If your AC input is not providing power normally, you turn the UPS ON, it should follow ...: (possible only with the "Battery Start" Switch) SELF TESTING... The LCD Display will still be turned back on . Qualified personnel should be energized. CAUTION! and other local codes for 24 hours after initial installation. 4. BATTERY OK DC TO DC OK INVERTER TEST 7 Note that cables are connected...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 8
... through different power readings on Bypass equals the output...BATTERY: XXX.XV BATTERY: XXX.X% (Charger Mode, Charger/Battery Voltage & Battery Percentage) Press "SELECT" Button SN: DC BUS: TEMP: VERSION: XXX XXV - Operation (Special Conditions) 5.1 Operation On Bypass-Voltage Out Of Range While in Bypass Mode..., the UPS monitors the input voltage, which on the LCD Display. 4. XXV XXX.X˚C XXX (Serial Number, DC BUS Voltage, Temperature & Firmware Version) Press "SELECT" Button ON: OFF: SEL: ENT: UPS START UPS BYPASS UPS MESSAGE SET...
... through different power readings on Bypass equals the output...BATTERY: XXX.XV BATTERY: XXX.X% (Charger Mode, Charger/Battery Voltage & Battery Percentage) Press "SELECT" Button SN: DC BUS: TEMP: VERSION: XXX XXV - Operation (Special Conditions) 5.1 Operation On Bypass-Voltage Out Of Range While in Bypass Mode..., the UPS monitors the input voltage, which on the LCD Display. 4. XXV XXX.X˚C XXX (Serial Number, DC BUS Voltage, Temperature & Firmware Version) Press "SELECT" Button ON: OFF: SEL: ENT: UPS START UPS BYPASS UPS MESSAGE SET...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 9
... Depleting* ON BATTERY Battery Charge is configured correctly before performing any maintenance on the UPS with the connected load supported. SHUTDOWN... VERSION: XXXXXXX BYPS OFF NO O/P EMERGENCY STOP! VERSION: XXXXXXX 5.4 Operation Of Manual Bypass Switch Warning: Failure to follow this switch to "BYPASS" before applying power to the unit. SHUTDOWN... SWITCHING UPS TO "NORMAL" MODE • Turn the Main...
... Depleting* ON BATTERY Battery Charge is configured correctly before performing any maintenance on the UPS with the connected load supported. SHUTDOWN... VERSION: XXXXXXX BYPS OFF NO O/P EMERGENCY STOP! VERSION: XXXXXXX 5.4 Operation Of Manual Bypass Switch Warning: Failure to follow this switch to "BYPASS" before applying power to the unit. SHUTDOWN... SWITCHING UPS TO "NORMAL" MODE • Turn the Main...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 10
....tripplite.com for information on battery and low battery alarm. The port can monitor and manage network power and automatically save open files and shut down delay time, enable/disable alarm and remote shutdown. 6. Using this port, Tripp Lite software can also receive a remote ...AS-400 to a workstation or server equipped with Tripp Lite software. RS-232 signals and operations include: load level, battery status, battery level, operation mode, AC input voltage, AC output voltage, AC input frequency, temperature inside unit, set shut-down equipment during a blackout. It can ...
....tripplite.com for information on battery and low battery alarm. The port can monitor and manage network power and automatically save open files and shut down delay time, enable/disable alarm and remote shutdown. 6. Using this port, Tripp Lite software can also receive a remote ...AS-400 to a workstation or server equipped with Tripp Lite software. RS-232 signals and operations include: load level, battery status, battery level, operation mode, AC input voltage, AC output voltage, AC input frequency, temperature inside unit, set shut-down equipment during a blackout. It can ...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 11
.... Using a user-supplied cable, connect the UPS System's EPO port to come in the event of a blackout) during battery installation. (See section 4.2, Turning the UPS Off.) Internal battery packs must be hot-swapped, qualified service personnel may want to a facility's Emergency Power Off (EPO) circuit. The UPS will power off during the battery installation procedure. (See section 5.4, Operation of Manual Bypass Switch...
.... Using a user-supplied cable, connect the UPS System's EPO port to come in the event of a blackout) during battery installation. (See section 4.2, Turning the UPS Off.) Internal battery packs must be hot-swapped, qualified service personnel may want to a facility's Emergency Power Off (EPO) circuit. The UPS will power off during the battery installation procedure. (See section 5.4, Operation of Manual Bypass Switch...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 12
... only. 7. Adding or Replacing Internal Batteries (continued) 7.1 Internal Battery Pack Wiring Diagram Qualified service personnel should familiarize themselves with the battery pack wiring diagram prior to four battery packs (each pack consisting of batteries shipped with the UPS System varies depending on model number. White wire Blue wire Red wire (+) Black wire (-) UPS System Battery Back Connector UPS System Battery Back Connector Fuse...
... only. 7. Adding or Replacing Internal Batteries (continued) 7.1 Internal Battery Pack Wiring Diagram Qualified service personnel should familiarize themselves with the battery pack wiring diagram prior to four battery packs (each pack consisting of batteries shipped with the UPS System varies depending on model number. White wire Blue wire Red wire (+) Black wire (-) UPS System Battery Back Connector UPS System Battery Back Connector Fuse...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 13
CAUTION! Adding or Replacing Internal Batteries (continued) 1 Place the UPS System in Bypass Mode or completely turn it off, depending on preference. (See section 5.4, Operation of Manual Bypass Switch, or 4.2, Turning the UPS Off.) 2 Remove battery access panel, located on the FRONT of the UPS 2 system. 3 Disconnect the RED and BLACK cables attached to each 5 fuse block. Do not wiggle them...
CAUTION! Adding or Replacing Internal Batteries (continued) 1 Place the UPS System in Bypass Mode or completely turn it off, depending on preference. (See section 5.4, Operation of Manual Bypass Switch, or 4.2, Turning the UPS Off.) 2 Remove battery access panel, located on the FRONT of the UPS 2 system. 3 Disconnect the RED and BLACK cables attached to each 5 fuse block. Do not wiggle them...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 14
... adequate room to add the battery strings 7B . 7 TERMINALS 7A 7B 8 Slide the battery string with the RED cable into an empty slot within the battery compartment as shown. Note: If the auxiliary battery connector is readable. 14 Adding or Replacing Internal Batteries (continued) 6 Remove the fuse... block bracket. 6 7 Slide the battery string with the BLACK cable next to it is in the empty slot as shown. Make sure that the string is oriented as shown in the diagram...
... adequate room to add the battery strings 7B . 7 TERMINALS 7A 7B 8 Slide the battery string with the RED cable into an empty slot within the battery compartment as shown. Note: If the auxiliary battery connector is readable. 14 Adding or Replacing Internal Batteries (continued) 6 Remove the fuse... block bracket. 6 7 Slide the battery string with the BLACK cable next to it is in the empty slot as shown. Make sure that the string is oriented as shown in the diagram...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 15
...user-supplied) to test the voltage of the battery pack. 12 Observe proper polarity: connect the voltmeter's BLACK probe to its corresponding fuse block. connect the voltmeter's RED probe to the danger of potential arcing of the incorrect voltage reading. 240 15 If several attempts at voltmeter tests yield results outside this range, contact Tripp Lite...inside the battery pack's connectors. The battery pack's Acceptable DC Voltage Range is encountered, a fuse will not deliver any of fire, replace only with a blown fuse will blow. 7. Adding or Replacing Internal Batteries (continued...
...user-supplied) to test the voltage of the battery pack. 12 Observe proper polarity: connect the voltmeter's BLACK probe to its corresponding fuse block. connect the voltmeter's RED probe to the danger of potential arcing of the incorrect voltage reading. 240 15 If several attempts at voltmeter tests yield results outside this range, contact Tripp Lite...inside the battery pack's connectors. The battery pack's Acceptable DC Voltage Range is encountered, a fuse will not deliver any of fire, replace only with a blown fuse will blow. 7. Adding or Replacing Internal Batteries (continued...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 16
... installed and used in step 1. (See section 5.4, Operation of the product. Service under this product, always refer to radio communications. The user must accept any warranties provided by Tripp Lite's "Start-up" service, to jurisdiction). Chicago IL 60609. WARRANTY REGISTRATION Visit www.tripplite.com/warranty today to -RED. Adding or Replacing Internal Batteries (continued) WARNING! This Warranty gives you specific...
... installed and used in step 1. (See section 5.4, Operation of the product. Service under this product, always refer to radio communications. The user must accept any warranties provided by Tripp Lite's "Start-up" service, to jurisdiction). Chicago IL 60609. WARRANTY REGISTRATION Visit www.tripplite.com/warranty today to -RED. Adding or Replacing Internal Batteries (continued) WARNING! This Warranty gives you specific...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 17
Specifications Model: SU20K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz Voltage Correction Range 96-144/166-250V AC Input Current (Per Phase, On-Line) 60A Inrush Current 0.95 Efficiency (Full Load/On-Line) >89% Circuit Breaker 100A (3p) Input Bypass... Circuit Breaker 100A (3p) Output VA 20000 Watts (Power Factor: 0.8) 16000 Waveform (On-Line) Sinewave Waveform (On-Battery) Sinewave Output Voltage (RMS) 120/208V AC, 3ø, 4 Wire ...
Specifications Model: SU20K3/3 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Frequency 60 Hz ± 3 Hz Voltage Correction Range 96-144/166-250V AC Input Current (Per Phase, On-Line) 60A Inrush Current 0.95 Efficiency (Full Load/On-Line) >89% Circuit Breaker 100A (3p) Input Bypass... Circuit Breaker 100A (3p) Output VA 20000 Watts (Power Factor: 0.8) 16000 Waveform (On-Line) Sinewave Waveform (On-Battery) Sinewave Output Voltage (RMS) 120/208V AC, 3ø, 4 Wire ...
Owner's Manual for SmartOnline 3-Phase 20kVA & 30kVA UPS 932624
Page 18
Harmonic Distortion (Non-Linear Full Load) ±2% 9. Specifications (continued) Model: SU30K3/3 Model: SU30K3/3XR5 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus...>89% Circuit Breaker Input Bypass Circuit Breaker 100A (3p) 100A (3p) Circuit Breaker Input Bypass Circuit Breaker 100A (3p) 100A (3p) Output Output VA Watts (Power Factor: 0.8) 30000 24000 VA Watts (Power Factor: 0.8) 30000 24000 Waveform (On-Line) Sinewave Waveform (On-Line) Sinewave Waveform (On-Battery) Output Voltage (RMS) ...
Harmonic Distortion (Non-Linear Full Load) ±2% 9. Specifications (continued) Model: SU30K3/3 Model: SU30K3/3XR5 Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus ground), wye Input Input Voltage 120/208V AC, 3ø, 4 Wire (plus...>89% Circuit Breaker Input Bypass Circuit Breaker 100A (3p) 100A (3p) Circuit Breaker Input Bypass Circuit Breaker 100A (3p) 100A (3p) Output Output VA Watts (Power Factor: 0.8) 30000 24000 VA Watts (Power Factor: 0.8) 30000 24000 Waveform (On-Line) Sinewave Waveform (On-Line) Sinewave Waveform (On-Battery) Output Voltage (RMS) ...