Owners Guide
Page 2
Patents pending. © 9-06 Honeywell International Inc. Need Help? All rights reserved. 69-2005EF Read and save these instructions. ® U.S. Registered Trademark. For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502.
Patents pending. © 9-06 Honeywell International Inc. Need Help? All rights reserved. 69-2005EF Read and save these instructions. ® U.S. Registered Trademark. For assistance with this product please visit http://yourhome.honeywell.com or call Honeywell Customer Care toll-free at 1-800-468-1502.
Owners Guide
Page 3
Table of contents User's section About your new thermostat 1 Screen display ...2 Power-up / modes of operation 3 User's configuration menu 4 Temperature display and setting 6 Installer's section Installation...7 Configuration switches 8 Installer's configuration menu 9 Appendix Technical specifications 12 2-year limited warranty 13 69-2005EF
Table of contents User's section About your new thermostat 1 Screen display ...2 Power-up / modes of operation 3 User's configuration menu 4 Temperature display and setting 6 Installer's section Installation...7 Configuration switches 8 Installer's configuration menu 9 Appendix Technical specifications 12 2-year limited warranty 13 69-2005EF
Owners Guide
Page 4
...be used to control the ambient air temperature or floor temperature. About your new thermostat Honeywell's AQ1000TN2 hydronic zoning thermostat can choose among the following temperature control modes (see page 8): A mode: • controls and displays the ambient air temperature F mode: • controls and displays the floor temperature using an external temperature sensor AF mode: • • controls and displays the ambient air temperature maintains the floor temperature within desired limits using an external temperature sensor 1 Screen Temperature adjustment buttons Backlight...
...be used to control the ambient air temperature or floor temperature. About your new thermostat Honeywell's AQ1000TN2 hydronic zoning thermostat can choose among the following temperature control modes (see page 8): A mode: • controls and displays the ambient air temperature F mode: • controls and displays the floor temperature using an external temperature sensor AF mode: • • controls and displays the ambient air temperature maintains the floor temperature within desired limits using an external temperature sensor 1 Screen Temperature adjustment buttons Backlight...
Owners Guide
Page 5
The backlight button and the buttons can still be used to activate the backlight and to indicate that the thermostat settings cannot be displayed only if the data is On Keypad lock 2 Freeze Protection mode (see next page) Comfort / Unoccupied mode (see next page) 1 The outdoor temperature will be modified as the hydronic zoning controller has locked the keypad. Screen display The arrow appears when the setpoint is displayed Temperature control mode Indoor temperature Outdoor temperature 1 Heating is available. 2 This icon appears to display the setpoint. 2 69-2005EF
The backlight button and the buttons can still be used to activate the backlight and to indicate that the thermostat settings cannot be displayed only if the data is On Keypad lock 2 Freeze Protection mode (see next page) Comfort / Unoccupied mode (see next page) 1 The outdoor temperature will be modified as the hydronic zoning controller has locked the keypad. Screen display The arrow appears when the setpoint is displayed Temperature control mode Indoor temperature Outdoor temperature 1 Heating is available. 2 This icon appears to display the setpoint. 2 69-2005EF
Owners Guide
Page 6
... thermostat can be placed in one of the 3 following modes of operation The thermostat is powered through the wires connecting it to the AQ2000 Series hydronic zoning controller. In this mode, the temperature is set in the Comfort mode. Freeze Protection Mode When the Freeze Protection mode is activated by the temperature setback value. This value is set using the buttons. Power-up / modes of operation: Comfort Mode The thermostat is normally in the Installer's configuration menu...
... thermostat can be placed in one of the 3 following modes of operation The thermostat is powered through the wires connecting it to the AQ2000 Series hydronic zoning controller. In this mode, the temperature is set in the Comfort mode. Freeze Protection Mode When the Freeze Protection mode is activated by the temperature setback value. This value is set using the buttons. Power-up / modes of operation: Comfort Mode The thermostat is normally in the Installer's configuration menu...
Owners Guide
Page 7
User's Configuration Menu 1. To exit the menu, press the backlight button for 3 seconds to 9 °C) Temporary Temporary / Permanent 4 69-2005EF Parameter Display mode Temperature setback Backlight Default setting Options Automatic Automatic, °F, °C 7 °F (4 °C) 0 to 16 °F (0 to access the configuration menu. To modify a parameter, press either of the buttons. 3. The parameters appear in the order shown in the following table. The first parameter...
User's Configuration Menu 1. To exit the menu, press the backlight button for 3 seconds to 9 °C) Temporary Temporary / Permanent 4 69-2005EF Parameter Display mode Temperature setback Backlight Default setting Options Automatic Automatic, °F, °C 7 °F (4 °C) 0 to 16 °F (0 to access the configuration menu. To modify a parameter, press either of the buttons. 3. The parameters appear in the order shown in the following table. The first parameter...
Owners Guide
Page 8
... controller models only), the temperature setpoint is selected, the thermostat displays the temperature format set back). When the automatic mode is lowered (set on the hydronic zoning controller. Display Format Use this parameter to choose between temporary and permanent backlight. Backlight Use this parameter to specify the amount of temperature setback. When temporary backlight is selected, the screen is lit for 12 seconds every time any button is selected, the thermostat displays...
... controller models only), the temperature setpoint is selected, the thermostat displays the temperature format set back). When the automatic mode is lowered (set on the hydronic zoning controller. Display Format Use this parameter to choose between temporary and permanent backlight. Backlight Use this parameter to specify the amount of temperature setback. When temporary backlight is selected, the screen is lit for 12 seconds every time any button is selected, the thermostat displays...
Owners Guide
Page 9
... of the buttons once. To scroll faster, press and hold the button. Verify the thermostat and external (floor) sensor connections. 6 69-2005EF The measured temperature is below the thermostat's display range. To display the setpoint temperature, press one of the buttons until the desired temperature is displayed. Error Messages The measured temperature is above the thermostat's display range. To change the setpoint, press one of the setpoint temperature display. Temperature Display and Setting The thermostat generally displays the actual...
... of the buttons once. To scroll faster, press and hold the button. Verify the thermostat and external (floor) sensor connections. 6 69-2005EF The measured temperature is below the thermostat's display range. To display the setpoint temperature, press one of the buttons until the desired temperature is displayed. Error Messages The measured temperature is above the thermostat's display range. To change the setpoint, press one of the setpoint temperature display. Temperature Display and Setting The thermostat generally displays the actual...
Owners Guide
Page 10
... AF mode; Terminal Description 1 TH 2 TH 3 SENSOR 4 SENSOR AQ2000 Series hydronic zoning controller connections External sensor connections for floor temperature measurement (required only if the thermostat is set to observe). Set the configuration switches (see pages 1 and 8) 4. Re-attach the faceplate to the wall or onto an electrical box. 3. Installation 1. Insert the wires through the center hole of the faceplate up. NOTE: Keep the thermostat's air vents clean and unobstructed at all times...
... AF mode; Terminal Description 1 TH 2 TH 3 SENSOR 4 SENSOR AQ2000 Series hydronic zoning controller connections External sensor connections for floor temperature measurement (required only if the thermostat is set to observe). Set the configuration switches (see pages 1 and 8) 4. Re-attach the faceplate to the wall or onto an electrical box. 3. Installation 1. Insert the wires through the center hole of the faceplate up. NOTE: Keep the thermostat's air vents clean and unobstructed at all times...
Owners Guide
Page 11
Installer Configuration Menu (switch 2) Use DIP switch 2 to select the temperature control mode (A, F or AF). NOTE : F or AF mode should be used . NOTE : DIP switch 1 is not used only when an external (floor) sensor is connected to the thermostat (see page 7). 8 69-2005EF Configuration switches The configuration (DIP) switches are located behind the thermostat faceplate. Temperature Control Mode (switches 3 & 4) Use DIP switches 3 and 4 to set the thermostat in either Installer or User mode.
Installer Configuration Menu (switch 2) Use DIP switch 2 to select the temperature control mode (A, F or AF). NOTE : F or AF mode should be used . NOTE : DIP switch 1 is not used only when an external (floor) sensor is connected to the thermostat (see page 7). 8 69-2005EF Configuration switches The configuration (DIP) switches are located behind the thermostat faceplate. Temperature Control Mode (switches 3 & 4) Use DIP switches 3 and 4 to set the thermostat in either Installer or User mode.
Owners Guide
Page 12
... Freeze Protection temperature range is displayed. 4. Installer's Configuration Menu The parameters in the installer's configuration menu must be modified by the minimum and maximum setpoint temperatures. Place switch 2 on the back of the buttons. 5. To modify a parameter, press either of the thermostat in the up position (Installer mode). 3. To view the next parameter, briefly press the backlight button. 6. The first parameter is set the Freeze Protection temperature lower than...
... Freeze Protection temperature range is displayed. 4. Installer's Configuration Menu The parameters in the installer's configuration menu must be modified by the minimum and maximum setpoint temperatures. Place switch 2 on the back of the buttons. 5. To modify a parameter, press either of the thermostat in the up position (Installer mode). 3. To view the next parameter, briefly press the backlight button. 6. The first parameter is set the Freeze Protection temperature lower than...
Owners Guide
Page 13
Freeze Protection Temperature This parameter is used to prevent frozen pipes inside the room where the thermostat is the maximum temperature at which the thermostat can be set . Maximum Setpoint Temperature This parameter is located. When the Freeze Protection mode is activated by the hydronic zoning controller, the thermostat is the minimum temperature at which the thermostat can be set . Minimum Setpoint Temperature This parameter is placed at the Freeze Protection temperature. 10 69-2005EF
Freeze Protection Temperature This parameter is used to prevent frozen pipes inside the room where the thermostat is the maximum temperature at which the thermostat can be set . Maximum Setpoint Temperature This parameter is located. When the Freeze Protection mode is activated by the hydronic zoning controller, the thermostat is the minimum temperature at which the thermostat can be set . Minimum Setpoint Temperature This parameter is placed at the Freeze Protection temperature. 10 69-2005EF
Owners Guide
Page 14
If the floor temperature is above that limit, the pump or valve will be activated regardless of the ambient temperature. 11 69-2005EF If the floor temperature is below that limit, the pump or valve will be deactivated regardless of the ambient temperature. Maximum Floor Limit Temperature This parameter is used only if the thermostat has been configured for AF temperature control. Minimum Floor Limit Temperature This parameter is used only if the thermostat has been configured for AF temperature control.
If the floor temperature is above that limit, the pump or valve will be activated regardless of the ambient temperature. 11 69-2005EF If the floor temperature is below that limit, the pump or valve will be deactivated regardless of the ambient temperature. Maximum Floor Limit Temperature This parameter is used only if the thermostat has been configured for AF temperature control. Minimum Floor Limit Temperature This parameter is used only if the thermostat has been configured for AF temperature control.
Owners Guide
Page 15
Technical Specifications Power supply: powered by the boiler controller Default setpoint range: 40 °F to 100 °F (5 °C to 38 °C) Default floor limit (AF model): 40 °F to 100 °F (5 °C to 38 °C) Setpoint interval: ± 1.0 °F (0.5 °C) Indoor temperature display range: 32 °F to 158 °F (0 °C to 70 °C) Outdoor temperature display range: -58 °F to 212 °F (-50 °...
Technical Specifications Power supply: powered by the boiler controller Default setpoint range: 40 °F to 100 °F (5 °C to 38 °C) Default floor limit (AF model): 40 °F to 100 °F (5 °C to 38 °C) Setpoint interval: ± 1.0 °F (0.5 °C) Indoor temperature display range: 32 °F to 158 °F (0 °C to 70 °C) Outdoor temperature display range: -58 °F to 212 °F (-50 °...
Owners Guide
Page 16
... 1-800-468-1502. This warranty does not cover removal or reinstallation costs. If the product is determined to be defective or malfunctions, Honeywell shall repair or replace it ; HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, 13 69-2005EF 2-year limited warranty Honeywell warrants this product, excluding battery, to be free from defects in the workmanship...
... 1-800-468-1502. This warranty does not cover removal or reinstallation costs. If the product is determined to be defective or malfunctions, Honeywell shall repair or replace it ; HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, 13 69-2005EF 2-year limited warranty Honeywell warrants this product, excluding battery, to be free from defects in the workmanship...
Owners Guide
Page 17
...warranty lasts, so the above limitation may not apply to you. THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES... OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE TWO-YEAR DURATION OF THIS WARRANTY... This warranty gives you specific legal rights, and you . In Canada, write Retail Products ON15-02H, Honeywell Limited/Honeywell Limité...
...warranty lasts, so the above limitation may not apply to you. THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING THE WARRANTIES... OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE TWO-YEAR DURATION OF THIS WARRANTY... This warranty gives you specific legal rights, and you . In Canada, write Retail Products ON15-02H, Honeywell Limited/Honeywell Limité...
Owners Guide
Page 18
Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 yourhome.honeywell.com ® U.S. Registered Trademark © 2006 Honeywell International Inc. 69-2005EF Rev. 9-06 Automation and Control Solutions Honeywell International Inc.
Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 yourhome.honeywell.com ® U.S. Registered Trademark © 2006 Honeywell International Inc. 69-2005EF Rev. 9-06 Automation and Control Solutions Honeywell International Inc.