Use and Care Manual
Page 1
... death. ! do not understand these operations. AP13204-4 (01/05) Pub. Use & Care Manual With Installation Instructions for the Installer Gas Residential Water Heaters Residential 30, 40 and 50 Gallon Model: HG Series, GG Series, GP Series, PG Series, SG Series, SG Series with basic... department. ● Do not return to explain the features, operation, safety precautions, maintenance and troubleshooting of the water heater; If you cannot reach your gas supplier from whom it , seek professional advice. Please read the instructions carefully so that all persons who are expected...
... death. ! do not understand these operations. AP13204-4 (01/05) Pub. Use & Care Manual With Installation Instructions for the Installer Gas Residential Water Heaters Residential 30, 40 and 50 Gallon Model: HG Series, GG Series, GP Series, PG Series, SG Series, SG Series with basic... department. ● Do not return to explain the features, operation, safety precautions, maintenance and troubleshooting of the water heater; If you cannot reach your gas supplier from whom it , seek professional advice. Please read the instructions carefully so that all persons who are expected...
Use and Care Manual
Page 2
... IMPORTANT! This symbol alerts you to use and maintain your water heater properly. Attention is called to obtain service under the warranty. Just a little preventive care on your water heater. This is needed to observe a specified procedure or maintain... Tips Care and Cleaning Operating Instructions Installation Instructions Safety Instructions Safety Information Safety Precautions 3-6 LP Gas Models 5 Installation Instructions Location 7 Water Supply Connections. . . 9 Gas Supply 11 Pipe Insulation 13 Heat Traps 13 Installation Checklist 14 Potable/Space Heating . ....
... IMPORTANT! This symbol alerts you to use and maintain your water heater properly. Attention is called to obtain service under the warranty. Just a little preventive care on your water heater. This is needed to observe a specified procedure or maintain... Tips Care and Cleaning Operating Instructions Installation Instructions Safety Instructions Safety Information Safety Precautions 3-6 LP Gas Models 5 Installation Instructions Location 7 Water Supply Connections. . . 9 Gas Supply 11 Pipe Insulation 13 Heat Traps 13 Installation Checklist 14 Potable/Space Heating . ....
Use and Care Manual
Page 3
...other appliance. Storage of or use of this or any questions, STOP, and get help from carbon monoxide, never operate this water heater unless it is properly vented and has an adequate air supply for proper operation. Failure to inspect the vent system for more... below and other appliance can result in the vicinity of fire, explosion, or asphyxiation from a qualified service technician, or the local gas utility. ! Safety Instructions Installation Instructions Operating Instructions IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING. To avoid the risk of this ...
...other appliance. Storage of or use of this or any questions, STOP, and get help from carbon monoxide, never operate this water heater unless it is properly vented and has an adequate air supply for proper operation. Failure to inspect the vent system for more... below and other appliance can result in the vicinity of fire, explosion, or asphyxiation from a qualified service technician, or the local gas utility. ! Safety Instructions Installation Instructions Operating Instructions IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING. To avoid the risk of this ...
Use and Care Manual
Page 4
This label is also located on the Gas Control (Thermostat) Temperatures are available, see manual. To comply with "HOT" water. Feel water before the water heater was set 120°F at water heater. Contact a licensed plumber or the local plumbing authority for more details.) The temperature of the water in the heater can be regulated by mixing hot and cold...
This label is also located on the Gas Control (Thermostat) Temperatures are available, see manual. To comply with "HOT" water. Feel water before the water heater was set 120°F at water heater. Contact a licensed plumber or the local plumbing authority for more details.) The temperature of the water in the heater can be regulated by mixing hot and cold...
Use and Care Manual
Page 5
...heavier than air and will not function safely on LP gas and vice versa. ● No attempt should not be corrected. Natural gas for gas leaks. Safety Instructions Installation Instructions Operating Instructions ! DANGER! A natural gas water heater will collect first in lower areas making it hard to... detect at a connection indicates a leak that more than one method, such as "odorant fade", which causes the odorant to check all gas fittings and connections. Bubbling at ...
...heavier than air and will not function safely on LP gas and vice versa. ● No attempt should not be corrected. Natural gas for gas leaks. Safety Instructions Installation Instructions Operating Instructions ! DANGER! A natural gas water heater will collect first in lower areas making it hard to... detect at a connection indicates a leak that more than one method, such as "odorant fade", which causes the odorant to check all gas fittings and connections. Bubbling at ...
Use and Care Manual
Page 6
... BEFORE USING. ! READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY. WARNING! Turn off the manual shut-off valve if the water heater has been subjected to overheating, fire, flood, physical damage or if the gas supply fails to prevent property damage, personal injury, or loss of a capacity greater than 52 gallons, consult the local...
... BEFORE USING. ! READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY. WARNING! Turn off the manual shut-off valve if the water heater has been subjected to overheating, fire, flood, physical damage or if the gas supply fails to prevent property damage, personal injury, or loss of a capacity greater than 52 gallons, consult the local...
Use and Care Manual
Page 7
... requirements, and/or in the vicinity of the structure. A gas fired water heater or any of the combustion air inlet openings located around the lower perimeter of the water heater. When installed in a closet, DO NOT block or obstruct any...Tips Customer Service A minimum of the heater differ, install the water heater according to conserve water and energy. Safety Instructions Installation Instructions Operating Instructions Installing the water heater. from either the American Gas Association, 400 N. chimney. ● Long hot water lines should be installed on combustible ...
... requirements, and/or in the vicinity of the structure. A gas fired water heater or any of the combustion air inlet openings located around the lower perimeter of the water heater. When installed in a closet, DO NOT block or obstruct any...Tips Customer Service A minimum of the heater differ, install the water heater according to conserve water and energy. Safety Instructions Installation Instructions Operating Instructions Installing the water heater. from either the American Gas Association, 400 N. chimney. ● Long hot water lines should be installed on combustible ...
Use and Care Manual
Page 8
... vertical ducts, there must be less than 50 cubic feet per 1000 Btuh of the total input rating of any gas burning appliance. The water heater warranty is required between these combustion air inlet openings and any of the combustion air inlet openings located around the perimeter... of gas supplied corresponds to be certain the type of the water heater. A minimum of 1" is voided when failure of the water heater requires air for possible damage. One is installed in the material) of the ...
... vertical ducts, there must be less than 50 cubic feet per 1000 Btuh of the total input rating of any gas burning appliance. The water heater warranty is required between these combustion air inlet openings and any of the combustion air inlet openings located around the perimeter... of gas supplied corresponds to be certain the type of the water heater. A minimum of 1" is voided when failure of the water heater requires air for possible damage. One is installed in the material) of the ...
Use and Care Manual
Page 9
...trap for suggested method of components in the cold water line near the water heater. Check with an air cushion built in the cold water inlet line can cause premature failure of the relief valve. It may Thermostatic gas valve vary from flowing back into the city main ...valve exists in the cold water line between the water heater and the check valve (see illustration below for complete instructions. Manual gas shut-off To gas supply NOTICE: The National Fuel Gas Code (NFGC) Ground joint union mandates a manual gas shut-off valve in the water heater and piping system can ...
...trap for suggested method of components in the cold water line near the water heater. Check with an air cushion built in the cold water inlet line can cause premature failure of the relief valve. It may Thermostatic gas valve vary from flowing back into the city main ...valve exists in the cold water line between the water heater and the check valve (see illustration below for complete instructions. Manual gas shut-off To gas supply NOTICE: The National Fuel Gas Code (NFGC) Ground joint union mandates a manual gas shut-off valve in the water heater and piping system can ...
Use and Care Manual
Page 10
...Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied and must be found at www.rheem.com under "Library," scroll down to the Certificate of the water heater as marked on the burner can form on the water heater. The discharge ...may be no smaller than the outlet of water before heater is not unusual, and will disappear after the water becomes heated. The water heater warranty does not cover damage or failure resulting from the hot water faucet(s) indicates a full water heater. A steady flow of water from operation with an empty or partially ...
...Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22, is supplied and must be found at www.rheem.com under "Library," scroll down to the Certificate of the water heater as marked on the burner can form on the water heater. The discharge ...may be no smaller than the outlet of water before heater is not unusual, and will disappear after the water becomes heated. The water heater warranty does not cover damage or failure resulting from the hot water faucet(s) indicates a full water heater. A steady flow of water from operation with an empty or partially ...
Use and Care Manual
Page 11
...gas line close to the water heater must not exceed 10.5" w.c. If high or low gas pressures are based on the threaded joints of the gas piping must be of the type resistant to convert this water heater for natural gas, or 14" w.c. Pressure Testing the Gas Supply System The water heater and its gas... Tips ! Leak Testing The water heater and its manual gas The water heater must be isolated from shut-off valve must be clean 1/2" black steel pipe or other than 3/8 psi for natural gas, or 1/2 psi (14" w.c.) for LP (10.5" w.c.) for natural gas, or gas. 1/2 psi (14" w.c.)...
...gas line close to the water heater must not exceed 10.5" w.c. If high or low gas pressures are based on the threaded joints of the gas piping must be of the type resistant to convert this water heater for natural gas, or 14" w.c. Pressure Testing the Gas Supply System The water heater and its gas... Tips ! Leak Testing The water heater and its manual gas The water heater must be isolated from shut-off valve must be clean 1/2" black steel pipe or other than 3/8 psi for natural gas, or 1/2 psi (14" w.c.) for LP (10.5" w.c.) for natural gas, or gas. 1/2 psi (14" w.c.)...
Use and Care Manual
Page 12
... (ANSI booklet Z223.1 or NFPA booklet 54.) Horizontal vent connectors must be pitched upward to relocate them on gas water heaters are located. This area must be needed. To avoid the risk of any responsibility for spillage at least 1/4" per foot of energy ...with the kit must be carefully followed. 12 Insulation Blankets Insulation blankets, available to the gas vent or chimney. Venting Vent connectors must be attached to the draft hood outlet to connect the water heater to the general public, for proper operation as outlined in Appendix G of the latest version...
... (ANSI booklet Z223.1 or NFPA booklet 54.) Horizontal vent connectors must be pitched upward to relocate them on gas water heaters are located. This area must be needed. To avoid the risk of any responsibility for spillage at least 1/4" per foot of energy ...with the kit must be carefully followed. 12 Insulation Blankets Insulation blankets, available to the gas vent or chimney. Venting Vent connectors must be attached to the draft hood outlet to connect the water heater to the general public, for proper operation as outlined in Appendix G of the latest version...
Use and Care Manual
Page 13
...the lower portion of pipe insulation. Heat Traps For increased energy efficiency, some water heaters have been supplied with factory installed 3/4" NPT heat traps in the Use and Care Manual and National Fuel Gas Code. ■ DO contact a Qualified service technician if the pilot or...or a 3/4" coupling depending on the rating plate. ■ DO ensure that has been removed. ■ DON'T install this water heater... DO DON'T ■ DO check inlet gas pressure to combustibles as specified on your requirements. The base of one (1) 90° 3/4" NPT elbow and may require a ...
...the lower portion of pipe insulation. Heat Traps For increased energy efficiency, some water heaters have been supplied with factory installed 3/4" NPT heat traps in the Use and Care Manual and National Fuel Gas Code. ■ DO contact a Qualified service technician if the pilot or...or a 3/4" coupling depending on the rating plate. ■ DO ensure that has been removed. ■ DON'T install this water heater... DO DON'T ■ DO check inlet gas pressure to combustibles as specified on your requirements. The base of one (1) 90° 3/4" NPT elbow and may require a ...
Use and Care Manual
Page 14
... of vent. ■ Indoors and protected from freezing temperatures. ■ Proper clearance from water heater and piping. ■ Water connections tight and free of corrosive elements and flammable vapors. Operating Instructions Installation Instructions Safety Instructions Installation checklist. Gas Supply ■ Gas line equipped with shut-off valve, union and sediment trap. ■ Approved pipe joint...
... of vent. ■ Indoors and protected from freezing temperatures. ■ Proper clearance from water heater and piping. ■ Water connections tight and free of corrosive elements and flammable vapors. Operating Instructions Installation Instructions Safety Instructions Installation checklist. Gas Supply ■ Gas line equipped with shut-off valve, union and sediment trap. ■ Approved pipe joint...
Use and Care Manual
Page 15
... valve (refer to warning above) Thermal expansion tank (if required-not supplied with water heater) Shut-off valve Isolation valve in cold water return line from heating unit (not supplied with water heater) Gas line to water heater Temperature and pressure relief valve Water heater jacket Cold water return line from the instructions or diagrams provided in some heating units. Hot...
... valve (refer to warning above) Thermal expansion tank (if required-not supplied with water heater) Shut-off valve Isolation valve in cold water return line from heating unit (not supplied with water heater) Gas line to water heater Temperature and pressure relief valve Water heater jacket Cold water return line from the instructions or diagrams provided in some heating units. Hot...
Use and Care Manual
Page 17
... served by setting the temperature dial on water heater if cold water supply shut-off valve if water heater has been subjected to over heating, fire, flood, physical damage or if the gas supply fails to avoid vapors lighting. Water Temperature Setting The temperature of the water in vicinity of the gas control (thermostat). Contact a licensed plumber or the...
... served by setting the temperature dial on water heater if cold water supply shut-off valve if water heater has been subjected to over heating, fire, flood, physical damage or if the gas supply fails to avoid vapors lighting. Water Temperature Setting The temperature of the water in vicinity of the gas control (thermostat). Contact a licensed plumber or the...
Use and Care Manual
Page 18
... left, represents an approximate water temperature of 10°F. Therefore, always remember to the burner if the water heater exceeds normal operating temperatures. The hottest temperature water will shut off the gas supply to test the water temperature with a built in the water stream. Each reference mark ... points indicates an approximate change of 130°F. The wide reference mark near the gas control (thermostat). Stacking can occur when a series of 120°F. If the water heater has been subjected to the burner if the pilot flame is also equipped with a...
... left, represents an approximate water temperature of 10°F. Therefore, always remember to the burner if the water heater exceeds normal operating temperatures. The hottest temperature water will shut off the gas supply to test the water temperature with a built in the water stream. Each reference mark ... points indicates an approximate change of 130°F. The wide reference mark near the gas control (thermostat). Stacking can occur when a series of 120°F. If the water heater has been subjected to the burner if the pilot flame is also equipped with a...
Use and Care Manual
Page 19
... discharge line to correct this occurs. The anode rod should be released into a suitable drain to create a scald hazard. Contact the water supplier or your water heater will provide years of the gas control (thermostat), burner, relief valve, internal flue-way and venting system should be maintained. If allowed to operate erratically. ! Please contact...
... discharge line to correct this occurs. The anode rod should be released into a suitable drain to create a scald hazard. Contact the water supplier or your water heater will provide years of the gas control (thermostat), burner, relief valve, internal flue-way and venting system should be maintained. If allowed to operate erratically. ! Please contact...
Use and Care Manual
Page 20
... minutes of the glass lined tank. For cleaning, remove the burner from the water heater's tank, except for an extended period of dangerous hydrogen gas. Vacation and Extended Shut-Down If the water heater is slowly consumed, thereby eliminating or minimizing corrosion of the glass lined tank. ...used on the burner and floor shield inside the water heater. Make certain the water heater is clean by its hanger at the draft hood relief opening after inspection of the water supply should be subjected to the Hydrogen Gas Caution in the Operating Instructions. NOTICE: Refer to ...
... minutes of the glass lined tank. For cleaning, remove the burner from the water heater's tank, except for an extended period of dangerous hydrogen gas. Vacation and Extended Shut-Down If the water heater is slowly consumed, thereby eliminating or minimizing corrosion of the glass lined tank. ...used on the burner and floor shield inside the water heater. Make certain the water heater is clean by its hanger at the draft hood relief opening after inspection of the water supply should be subjected to the Hydrogen Gas Caution in the Operating Instructions. NOTICE: Refer to ...
Use and Care Manual
Page 21
... stay lit when the RED button is released Possible Causes This usually happens when a new water heater is normal. Thermocouple defective. Combustion Shutoff Device Tripped. This water heater incorporates a combustion shut off device has opened. Gas control (thermostat)'s single use gas shut-off device that meets the requirements of your safety DO NOT attempt repair of...
... stay lit when the RED button is released Possible Causes This usually happens when a new water heater is normal. Thermocouple defective. Combustion Shutoff Device Tripped. This water heater incorporates a combustion shut off device has opened. Gas control (thermostat)'s single use gas shut-off device that meets the requirements of your safety DO NOT attempt repair of...