Honeywell T8411R Support Question
Find answers below for this question about Honeywell T8411R.Need a Honeywell T8411R manual? We have 1 online manual for this item!
Question posted by devantesmith80 on January 11th, 2016
Myt8411r1028 Thermostat Will Not Reach The Desired Setpoint What Do I Do?
Current Answers
Answer #1: Posted by waelsaidani1 on January 11th, 2016 2:23 PM
During a programmed recovery (or when the temperature setpoint is changed by the user), the thermostat waits to turn on the backup heat depending on system performance, load conditions and how many degrees the temperature setpoint is changed. Backup heat will be used ONLY when the temperature is not rising quickly enough to reach the setpoint in a reasonable time.
If the backup heat was used in the last 2 hours because the primary heat was not able to maintain the setpoint, the thermostat may turn on the backup heat earlier when the user raises the setpoint. This does NOT apply to heat pumps with fossil fuel backup heat.