Honeywell T8195B Support Question
Find answers below for this question about Honeywell T8195B.Need a Honeywell T8195B manual? We have 2 online manuals for this item!
Question posted by kjtriantafilo on January 2nd, 2012
Replacement For Honeywell Thermostat T8195b 1009
Current Answers
Answer #1: Posted by BusterDoogen on January 2nd, 2012 3:35 PM
Voltage trouble shooting chart:
Voltage at Timer Terminals
Ac Voltage at
C-R Terminals Possible Cause Check Action
0 Vac 1. System power is Off. 1. Restore power.
2. Short in timer power supply wiring. 2. Replace wiring.
3. Limit switch contacts stuck open. 3. Free or replace limit switch.
4. Transformer supplying power is
burned out.
4. Replace transformer.
Up to 15 Vac. 1. System transformer used to power
the timer is inadequate.
1. Use additional (separate)
transformer.
2. Additional (separate) transformer
used to power the timer has
inadequate voltage.
2. Install transformer with proper
secondary voltage.
15 to 30 Vac. 1. Spring fingers on thermostat not
making proper contact with
subbase terminals.
1. Rebend spring fingers to a
45 degree angle to ensure
proper contact.
2. Timer has failed. 2. Replace thermostat.
Hope this helps!