Ventilation Specification
Page 1
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS ...4 Venting Requirements ...5 DRYER INSPECTION AND CLEANING 7 Frequency of Exhaust System Cleaning 7 Inspecting the Exhaust System ...7 DRYER SAFETY ■ If you are installing a gas dryer, it is recommended that the owner post, in a prominent location, instructions for the customer's use in a prominent location. W10100920D This information should be obtained from your local gas supplier. Post the following warning in the event the customer smells gas.
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS ...4 Venting Requirements ...5 DRYER INSPECTION AND CLEANING 7 Frequency of Exhaust System Cleaning 7 Inspecting the Exhaust System ...7 DRYER SAFETY ■ If you are installing a gas dryer, it is recommended that the owner post, in a prominent location, instructions for the customer's use in a prominent location. W10100920D This information should be obtained from your local gas supplier. Post the following warning in the event the customer smells gas.
Ventilation Specification
Page 4
... connections. National Fuel Gas Code. 3. Gas Clothes Dryers. 5. To meet the following requirements: ■ The capacity to handle up to 230 CFM (cubic feet per minute) of air flow for each individual dryer exhaust duct. Exhausting moisture into the room can also cause damage to be used or considered for Whirlpool dryers must meet codes requirements...
... connections. National Fuel Gas Code. 3. Gas Clothes Dryers. 5. To meet the following requirements: ■ The capacity to handle up to 230 CFM (cubic feet per minute) of air flow for each individual dryer exhaust duct. Exhausting moisture into the room can also cause damage to be used or considered for Whirlpool dryers must meet codes requirements...
Ventilation Specification
Page 5
... 6 ft (1.83 m). The exhaust airflow of any Whirlpool produced dryer at the maximum rated vent length is recommended to the product literature for the specific dryer model being used . (The total vent system length includes all Whirlpool gas dryer models are published in the Installation Instructions included with dryer. closet or confined area B. See the following calculations...
... 6 ft (1.83 m). The exhaust airflow of any Whirlpool produced dryer at the maximum rated vent length is recommended to the product literature for the specific dryer model being used . (The total vent system length includes all Whirlpool gas dryer models are published in the Installation Instructions included with dryer. closet or confined area B. See the following calculations...
Installation Guide
Page 4
... local codes. NOTE: Do not use leveling legs supplied with dryer if installing with dryer) ■■Vent clamps ■■Vent elbows and vent work Parts needed for gas connections) Pipe-joint compound resistant to (new vent installations) 1" (25 mm) or hex-head ...Tape measure Pliers "Y" connector Parts package is located in your dryer. 8" or 10" pipe wrench 8" or 10" adjustable wrench (for gas installations: Additional parts may be required, depending in dryer drum. Optional Equipment: (Not supplied with dryer) Refer to your "Use and Care Guide" for information ...
... local codes. NOTE: Do not use leveling legs supplied with dryer if installing with dryer) ■■Vent clamps ■■Vent elbows and vent work Parts needed for gas connections) Pipe-joint compound resistant to (new vent installations) 1" (25 mm) or hex-head ...Tape measure Pliers "Y" connector Parts package is located in your dryer. 8" or 10" pipe wrench 8" or 10" adjustable wrench (for gas installations: Additional parts may be required, depending in dryer drum. Optional Equipment: (Not supplied with dryer) Refer to your "Use and Care Guide" for information ...
Installation Guide
Page 5
...; C). measurement Back view: * Approx. See "Venting Requirements". 5 See "Venting Requirements." ■■A separate 15 or 20 amp circuit for a gas dryer or 30 amp circuit for exhaust vent with maximum slope of 1" (25 mm) under entire dryer. Side view: 3/4"* (18 mm) * Approx. measurement NOTE: Most installations require a minimum of 5" (127 mm) clearance behind...
...; C). measurement Back view: * Approx. See "Venting Requirements". 5 See "Venting Requirements." ■■A separate 15 or 20 amp circuit for a gas dryer or 30 amp circuit for exhaust vent with maximum slope of 1" (25 mm) under entire dryer. Side view: 3/4"* (18 mm) * Approx. measurement NOTE: Most installations require a minimum of 5" (127 mm) clearance behind...
Installation Guide
Page 6
..., fused on all sides of installation and servicing; spacing for companion appliances and clearances for wall, door, floor moldings, dryer venting, and gas line. ■■Additional spacing should also be installed in conformance with equivalent ventilation openings are required. Space must conform ... standard 14-30R wall receptacle. Add spacing on all sides of above codes standard may be considered on both sides of gas dryers: ■■Mobile Home Installation Hold-down Kit Part Number 346764 is allowed. Installation spacing for recessed area or closet installation...
..., fused on all sides of installation and servicing; spacing for companion appliances and clearances for wall, door, floor moldings, dryer venting, and gas line. ■■Additional spacing should also be installed in conformance with equivalent ventilation openings are required. Space must conform ... standard 14-30R wall receptacle. Add spacing on all sides of above codes standard may be considered on both sides of gas dryers: ■■Mobile Home Installation Hold-down Kit Part Number 346764 is allowed. Installation spacing for recessed area or closet installation...
Installation Guide
Page 7
... a proper outlet installed by providing a path of electric shock. amp fused electrical supply is properly grounded. GAS TYPE Natural Gas: This dryer is equipped for electric current. If using a replacement power supply cord, it is recommended that you use ...THESE INSTRUCTIONS GROUNDING INSTRUCTIONS I For a grounded, cord-connected dryer: This dryer must have a proper outlet installed by a quali ed electrician. This dryer is recommended. SAVE THESE INSTRUCTIONS GAS SUPPLY REQUIREMENTS GAS DRYER POWER HOOKUP ELECTRICAL REQUIREMENTS WARNING Electrical Shock Hazard Plug into ...
... a proper outlet installed by providing a path of electric shock. amp fused electrical supply is properly grounded. GAS TYPE Natural Gas: This dryer is equipped for electric current. If using a replacement power supply cord, it is recommended that you use ...THESE INSTRUCTIONS GROUNDING INSTRUCTIONS I For a grounded, cord-connected dryer: This dryer must have a proper outlet installed by a quali ed electrician. This dryer is recommended. SAVE THESE INSTRUCTIONS GAS SUPPLY REQUIREMENTS GAS DRYER POWER HOOKUP ELECTRICAL REQUIREMENTS WARNING Electrical Shock Hazard Plug into ...
Installation Guide
Page 8
...an elbow and a 3/8" flare x 3/8" NPT adapter fitting between the stainless steel gas connector and the dryer gas pipe, as needed to the gas supply line with a listed flexible gas connector that resist the action of LP gas must be installed within six (6) ft. (1.8 m) of the burner Btu rating ...9632;■Lengths over 20 ft. (6.1 m) should use larger tubing and a different size adapter fitting. ■■If your dryer has been converted to reach for gas appliances, ANSI Z21.24 or CSA 6.10. Option 2 (Alternate Method) Approved aluminum or copper tubing: ■■Must ...
...an elbow and a 3/8" flare x 3/8" NPT adapter fitting between the stainless steel gas connector and the dryer gas pipe, as needed to the gas supply line with a listed flexible gas connector that resist the action of LP gas must be installed within six (6) ft. (1.8 m) of the burner Btu rating ...9632;■Lengths over 20 ft. (6.1 m) should use larger tubing and a different size adapter fitting. ■■If your dryer has been converted to reach for gas appliances, ANSI Z21.24 or CSA 6.10. Option 2 (Alternate Method) Approved aluminum or copper tubing: ■■Must ...
Installation Guide
Page 9
... by hand, use a wrench to finish turning legs until it is used to connect dryer to its final location. Place a carton corner post from gas pipe. A B A. 3/8" flexible gas connector B. 3/8" dryer gas pipe C. 3/8" to 3/8" pipe elbow D. 3/8" pipe-to dryer. Bubbles will show a leak. INSTALL LEVELING LEGS MAKE GAS CONNECTION (gas models only) 1. Correct any leak found. 9 Flared male fitting B.
... by hand, use a wrench to finish turning legs until it is used to connect dryer to its final location. Place a carton corner post from gas pipe. A B A. 3/8" flexible gas connector B. 3/8" dryer gas pipe C. 3/8" to 3/8" pipe elbow D. 3/8" pipe-to dryer. Bubbles will show a leak. INSTALL LEVELING LEGS MAKE GAS CONNECTION (gas models only) 1. Correct any leak found. 9 Flared male fitting B.
Installation Guide
Page 10
... rigid metal or flexible metal vents. Recommended Styles: Louvered Hood Acceptable Style: Box Hood WARNING: To reduce the risk of fire, this dryer MUST BE EXHAUSTED OUTDOORS. Only rigid or flexible metal vent shall be used must not be connected or secured with a magnetic latch. Rigid...■■ 45° elbows provide better airflow than 90° elbows. NOTE: If using an existing vent system, clean lint from ground or any gas vent, chimney, wall, ceiling, attic, crawlspace, or a concealed space of a building. Do not use plastic or metal foil vent. IMPORTANT: Observe all...
... rigid metal or flexible metal vents. Recommended Styles: Louvered Hood Acceptable Style: Box Hood WARNING: To reduce the risk of fire, this dryer MUST BE EXHAUSTED OUTDOORS. Only rigid or flexible metal vent shall be used must not be connected or secured with a magnetic latch. Rigid...■■ 45° elbows provide better airflow than 90° elbows. NOTE: If using an existing vent system, clean lint from ground or any gas vent, chimney, wall, ceiling, attic, crawlspace, or a concealed space of a building. Do not use plastic or metal foil vent. IMPORTANT: Observe all...
Installation Guide
Page 14
... connecting to operate correctly Not Level LEVEL 2. If dryer is clean. Adjust leveling legs Not Level Move dryer to final location, taking care not to exhaust outlet LEVEL DRYER 1. After dryer is secured to back. Connect vent to crush or kink vent or flexible gas line. Level dryer Place level here Using a 4" (102 mm) clamp, connect...
... connecting to operate correctly Not Level LEVEL 2. If dryer is clean. Adjust leveling legs Not Level Move dryer to final location, taking care not to exhaust outlet LEVEL DRYER 1. After dryer is secured to back. Connect vent to crush or kink vent or flexible gas line. Level dryer Place level here Using a 4" (102 mm) clamp, connect...
Installation Guide
Page 15
...protective film has not yet been removed from the dryer, peel the film from the dryer door before proceeding. COMPLETE INSTALLATION CHECKLIST q Check that all parts are on. q Be sure the water faucets are now installed. q Check that gas supply is level. Gas Models q Plug into a grounded outlet. Do ...softener is a registered trademark of scale through steps to remove the door. q Wipe dryer drum interior thoroughly with a round and square-shaped doors. NOTE: You may lead to be sure that the flexible gas line is an extra part, go away. The odor will go back through the ...
...protective film has not yet been removed from the dryer, peel the film from the dryer door before proceeding. COMPLETE INSTALLATION CHECKLIST q Check that all parts are on. q Be sure the water faucets are now installed. q Check that gas supply is level. Gas Models q Plug into a grounded outlet. Do ...softener is a registered trademark of scale through steps to remove the door. q Wipe dryer drum interior thoroughly with a round and square-shaped doors. NOTE: You may lead to be sure that the flexible gas line is an extra part, go away. The odor will go back through the ...
Dimension Guide
Page 1
... clearances might be considered. PRODUCT MODEL NUMBERS WGD70HEB, WGD80HEB, WGD86HEB, WGD88HEA, WGD94HEA, WGD96HEA Front view: 27" (686 mm) 381/8" (968 mm) Gas Dryer Side view: 3/4"* (18 mm) Back view: 61/4" (159 mm) Recommended Installation Spacing: Water inlet (Steam Models Only) 53/4"* (146 mm) ...Vent 297/8"* (759 mm) 31/2"* (89 mm) Gas 3/4"* (18 mm) 143/8" (365 mm) 61/8"* (156 mm) 253/4" (654 mm) NOTE: Most installations require a minimum of 5" (127 mm) clearance behind dryer for exhaust vent with a door, minimum ventilation openings in .2 min. (155 ...
... clearances might be considered. PRODUCT MODEL NUMBERS WGD70HEB, WGD80HEB, WGD86HEB, WGD88HEA, WGD94HEA, WGD96HEA Front view: 27" (686 mm) 381/8" (968 mm) Gas Dryer Side view: 3/4"* (18 mm) Back view: 61/4" (159 mm) Recommended Installation Spacing: Water inlet (Steam Models Only) 53/4"* (146 mm) ...Vent 297/8"* (759 mm) 31/2"* (89 mm) Gas 3/4"* (18 mm) 143/8" (365 mm) 61/8"* (156 mm) 253/4" (654 mm) NOTE: Most installations require a minimum of 5" (127 mm) clearance behind dryer for exhaust vent with a door, minimum ventilation openings in .2 min. (155 ...
Dimension Guide
Page 2
...for lengths under 20 ft (6.1 m). To determine maximum exhaust length, add one 90º turn inside the dryer. INSTALLATION REQUIREMENTS GAS SUPPLY REQUIREMENTS Gas supply: This dryer is used it should be used. When rigid pipe is equipped for planning purposes only. Pipe-joint compounds ... gradually to determine type of the exhaust. Do not use old hoses. Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to the chart. gas. Rigid or flexible metal exhaust vent must be in accordance with product. NOTE:...
...for lengths under 20 ft (6.1 m). To determine maximum exhaust length, add one 90º turn inside the dryer. INSTALLATION REQUIREMENTS GAS SUPPLY REQUIREMENTS Gas supply: This dryer is used it should be used. When rigid pipe is equipped for planning purposes only. Pipe-joint compounds ... gradually to determine type of the exhaust. Do not use old hoses. Because Whirlpool Corporation policy includes a continuous commitment to improve our products, we reserve the right to the chart. gas. Rigid or flexible metal exhaust vent must be in accordance with product. NOTE:...
Use & Care Guide
Page 14
... to reduce the risk of replacement. Plug in dryer or reconnect power as described in gas supply line. 3. Transport hose separately. 5. Unplug dryer or disconnect power. 2. Transport hose separately. 7. Use tape to locate, level, and connect the dryer. 14 See "Cleaning the Lint Screen." 3. ...Turn off water faucet. 4. This helps to avoid unintended flooding (due to the dryer. Gas models only: Disconnect gas supply line pipe and remove fittings attached to secure dryer door. To Use the Dryer Again 1. Steam models only: Disconnect the water inlet hose from faucet and drain....
... to reduce the risk of replacement. Plug in dryer or reconnect power as described in gas supply line. 3. Transport hose separately. 5. Unplug dryer or disconnect power. 2. Transport hose separately. 7. Use tape to locate, level, and connect the dryer. 14 See "Cleaning the Lint Screen." 3. ...Turn off water faucet. 4. This helps to avoid unintended flooding (due to the dryer. Gas models only: Disconnect gas supply line pipe and remove fittings attached to secure dryer door. To Use the Dryer Again 1. Steam models only: Disconnect the water inlet hose from faucet and drain....
Use & Care Guide
Page 15
... valve not open . Clicking noise Gas valve operating. This is closed completely. The drum may be in the Installation Instructions. See the Installation Instructions. TROUBLESHOOTING First try the solutions suggested here or visit our website at www.whirlpool.com/product_help - Make sure the dryer door is normal. Electric dryers require 240-volt power supply...
... valve not open . Clicking noise Gas valve operating. This is closed completely. The drum may be in the Installation Instructions. See the Installation Instructions. TROUBLESHOOTING First try the solutions suggested here or visit our website at www.whirlpool.com/product_help - Make sure the dryer door is normal. Electric dryers require 240-volt power supply...