Installation Instructions
Page 5
...long. 4-wire receptacle (14-50R) The minimum conductor sized for the copper 4-wire power cord are: 40-amp circuit 2 No.-8 conductors 1 No.-10 white neutral 1 No.-8 green grounding If connecting to a 3-wire system: Local codes may permit the use of the "Location Requirements" section. ■ This...directly to the circuit breaker box (or fused disconnect) through the neutral conductor is manufactured with the ground connected to the neutral by a white cover. If connecting to a 4-wire system: This range is prohibited for new branch-circuit installations (1996 NEC); When a 4-wire ...
...long. 4-wire receptacle (14-50R) The minimum conductor sized for the copper 4-wire power cord are: 40-amp circuit 2 No.-8 conductors 1 No.-10 white neutral 1 No.-8 green grounding If connecting to a 3-wire system: Local codes may permit the use of the "Location Requirements" section. ■ This...directly to the circuit breaker box (or fused disconnect) through the neutral conductor is manufactured with the ground connected to the neutral by a white cover. If connecting to a 4-wire system: This range is prohibited for new branch-circuit installations (1996 NEC); When a 4-wire ...
Installation Instructions
Page 9
Allow enough slack to easily attach the wiring to the terminal block. A B C D A. Terminal block B. Use ³⁄₈" nut driver to connect the neutral (white) wire to the outer terminal block posts with 10-32 hex nuts. 4. C D A. Terminal block B. Power supply cord wires - Ground-link screw C. Connect line 2 (red) and ... enough slack to easily attach the wiring to the terminal block. UL listed strain relief D. Use ³⁄₈" nut driver to connect the neutral (white) wire to neutral wire of range. Neutral...
Allow enough slack to easily attach the wiring to the terminal block. A B C D A. Terminal block B. Use ³⁄₈" nut driver to connect the neutral (white) wire to the outer terminal block posts with 10-32 hex nuts. 4. C D A. Terminal block B. Power supply cord wires - Ground-link screw C. Connect line 2 (red) and ... enough slack to easily attach the wiring to the terminal block. UL listed strain relief D. Use ³⁄₈" nut driver to connect the neutral (white) wire to neutral wire of range. Neutral...
Installation Instructions
Page 10
... ³⁄₈" (1.0 cm) from the back of the range. Complete electrical connection according to line 1 (black), neutral (white), and line 2 (red) wires. Attach terminal lugs to your electrical supply, make the required 3-wire or 4-wire connection. 1....block - 20 lbs-in. (2.3 N-m) Wire Awg Torque 8 gauge copper 6 gauge aluminum 25 lbs-in. (2.8 N-m) 35 lbs-in the following Bare Wire Torque Specifications chart. Neutral (white) wire G. A A B B C A. Discard C. A B 3" (7.6 cm) 2. C G D EF A. C D E A. Setscrew C. Use a Phillips screwdriver to the...
... ³⁄₈" (1.0 cm) from the back of the range. Complete electrical connection according to line 1 (black), neutral (white), and line 2 (red) wires. Attach terminal lugs to your electrical supply, make the required 3-wire or 4-wire connection. 1....block - 20 lbs-in. (2.3 N-m) Wire Awg Torque 8 gauge copper 6 gauge aluminum 25 lbs-in. (2.8 N-m) 35 lbs-in the following Bare Wire Torque Specifications chart. Neutral (white) wire G. A A B B C A. Discard C. A B 3" (7.6 cm) 2. C G D EF A. C D E A. Setscrew C. Use a Phillips screwdriver to the...
Installation Instructions
Page 11
... one of the 10-32 hex nuts. Bare (green) ground wire E. Use ³⁄₈" nut driver to connect the neutral (white) wire to torque as shown in . (4.0 N-m) 3. Neutral (white) wire F. Securely tighten hex nuts. 9. Securely tighten setscrew to the center terminal block post with one of the 10-32 hex nuts...
... one of the 10-32 hex nuts. Bare (green) ground wire E. Use ³⁄₈" nut driver to connect the neutral (white) wire to torque as shown in . (4.0 N-m) 3. Neutral (white) wire F. Securely tighten hex nuts. 9. Securely tighten setscrew to the center terminal block post with one of the 10-32 hex nuts...