Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 4
... mode, where this button is used to select setup options. 5 OFF BUTTON: Press this button until you hear a beep to turn the UPS system's inverter OFF. 6 O/P (OUTPUT) LED: This green light will illuminate to indicate your UPS, familiarize yourself with the location and function of the features of ... battery pack(s). 10 BATTERY LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or inverter. Momentarily pressing it ; and pop the panel back into these slots and gently lever the panel out. Pop the panel out; Pressing ...
... mode, where this button is used to select setup options. 5 OFF BUTTON: Press this button until you hear a beep to turn the UPS system's inverter OFF. 6 O/P (OUTPUT) LED: This green light will illuminate to indicate your UPS, familiarize yourself with the location and function of the features of ... battery pack(s). 10 BATTERY LED: This green light will illuminate when the UPS is providing filtered mains power without engaging its converter or inverter. Momentarily pressing it ; and pop the panel back into these slots and gently lever the panel out. Pop the panel out; Pressing ...
Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 8
... and shut down equipment during a blackout. The UPS system is now turned off the Output Circuit Breakers M located on your computer the Tripp Lite PowerAlert Software appropriate to a workstation or server. See "Startup Self-Test" in the ON position. It is used to connect your computer...then release the button. It will disable the RS-232 port. 1b 8 201102160 93-2897.indb 8 3/30/2011 9:30:45 AM The UPS system's inverter will perform a brief self-test and show the results on PDU module M . 3. Connection (continued) 5 Plug Your Equipment into the PDU's Outlets Your...
... and shut down equipment during a blackout. The UPS system is now turned off the Output Circuit Breakers M located on your computer the Tripp Lite PowerAlert Software appropriate to a workstation or server. See "Startup Self-Test" in the ON position. It is used to connect your computer...then release the button. It will disable the RS-232 port. 1b 8 201102160 93-2897.indb 8 3/30/2011 9:30:45 AM The UPS system's inverter will perform a brief self-test and show the results on PDU module M . 3. Connection (continued) 5 Plug Your Equipment into the PDU's Outlets Your...
Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 9
...potential contact with high voltage. Failure to follow the bypass procedure completely will not receive battery power in the event of the UPS's inverter and inhibits transfer to internal bypass. When the UPS is connected to the circuit diagram (see 2a) to a user-supplied normally... are extremely heavy. Visit www.tripplite.com/support for mounting instructions.) WARNING! Using the cable provided, connect the EPO port of death or injury from Tripp Lite. EPO PIN ASSIGNMENT 12V 1 X 2 3 4 1K 5 X 6 UPS Unit State when asserting EPO with AC line present: 2b LEDs ...
...potential contact with high voltage. Failure to follow the bypass procedure completely will not receive battery power in the event of the UPS's inverter and inhibits transfer to internal bypass. When the UPS is connected to the circuit diagram (see 2a) to a user-supplied normally... are extremely heavy. Visit www.tripplite.com/support for mounting instructions.) WARNING! Using the cable provided, connect the EPO port of death or injury from Tripp Lite. EPO PIN ASSIGNMENT 12V 1 X 2 3 4 1K 5 X 6 UPS Unit State when asserting EPO with AC line present: 2b LEDs ...
Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 13
...RECTIFIER OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00KW / 000% DIAGNOSTIC MODE FREQ OUT = 50Hz DIAGNOSTIC MODE INPUT 000V / 00Hz ... OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00V / 000% Failed Self-Test If a problem is cold started, its LCD, call Tripp Lite Technical Support at (773) 869-1234 for service. CALL FOR SERVICE...
...RECTIFIER OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00KW / 000% DIAGNOSTIC MODE FREQ OUT = 50Hz DIAGNOSTIC MODE INPUT 000V / 00Hz ... OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00V / 000% Failed Self-Test If a problem is cold started, its LCD, call Tripp Lite Technical Support at (773) 869-1234 for service. CALL FOR SERVICE...
Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 20
... MENU, scroll DOWNi until you reach the UPS ALARM LOG screen. See the Fail Event List below: Fail Event List DC BUS FAIL SHORT CIRCUIT INVERTER FAIL OVER TEMPERATURE OUTPUT SCR FAIL OVERLOAD FAN FAIL CHARGER BATTERY FAIL BYPASS SCR SHORT FAIL INPUT SCR SHORT FAIL DERATE SHUTDOWN ENERGY SAVING OUTPUT...
... MENU, scroll DOWNi until you reach the UPS ALARM LOG screen. See the Fail Event List below: Fail Event List DC BUS FAIL SHORT CIRCUIT INVERTER FAIL OVER TEMPERATURE OUTPUT SCR FAIL OVERLOAD FAN FAIL CHARGER BATTERY FAIL BYPASS SCR SHORT FAIL INPUT SCR SHORT FAIL DERATE SHUTDOWN ENERGY SAVING OUTPUT...
Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 21
... OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00KW / 000% When starting on battery power, you will see the following sequence display: DIAGNOSTIC MODE...000V / 00Hz DIAGNOSTIC MODE RECTIFIER OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00V / 000% 21 201102160 93-2897.indb 21 3/30/2011 9:30:52 AM
... OK DIAGNOSTIC MODE CHARGER OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00KW / 000% When starting on battery power, you will see the following sequence display: DIAGNOSTIC MODE...000V / 00Hz DIAGNOSTIC MODE RECTIFIER OK DIAGNOSTIC MODE BATTERY OK DIAGNOSTIC MODE DC BUS OK DIAGNOSTIC MODE INVERTER TEST DIAGNOSTIC MODE INVERTER OK LOAD LEVEL 00.00V / 000% 21 201102160 93-2897.indb 21 3/30/2011 9:30:52 AM
Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 23
Operation (continued) Display Information-Bypass Mode When operating in Bypass Mode, you will see the following sequence display: LOAD LEVEL 00.00KW / 000% LOAD LEVEL 00.00KVA / 000% INPUT VOLTAGE 000V / 00.0Hz BYPASS VOLTAGE 000V / 00.0Hz OUTPUT VOLTAGE 000V / 00.0Hz BATTERY CAPACITY 000V / 000% REMAINING TIME 0000 MINUTES ON-LINE 10KVA V00 CV01 UPS Fault Shutdown Messages CONDITION +BUS >450V Load 100%: +BUS 450V Load
Operation (continued) Display Information-Bypass Mode When operating in Bypass Mode, you will see the following sequence display: LOAD LEVEL 00.00KW / 000% LOAD LEVEL 00.00KVA / 000% INPUT VOLTAGE 000V / 00.0Hz BYPASS VOLTAGE 000V / 00.0Hz OUTPUT VOLTAGE 000V / 00.0Hz BATTERY CAPACITY 000V / 000% REMAINING TIME 0000 MINUTES ON-LINE 10KVA V00 CV01 UPS Fault Shutdown Messages CONDITION +BUS >450V Load 100%: +BUS 450V Load
Owner's Manual for SmartOnline 8kVA-10kVA UPS 932897
Page 24
... UPS monitors its LCD reports that output voltage was too high or too low at more than nominal), the UPS displays the condition on its inverter. To silence the On Battery Alarm, press the "ON/MUTE" button. If the UPS is using battery power to support connected equipment. If power levels...
... UPS monitors its LCD reports that output voltage was too high or too low at more than nominal), the UPS displays the condition on its inverter. To silence the On Battery Alarm, press the "ON/MUTE" button. If the UPS is using battery power to support connected equipment. If power levels...