Installation Instructions
Page 2
... M22268 MOUNTING SCREWS (2) Fig. 3. Refer to prevent drafts from Thermostat 1. Pull the wires through the wire hole on the wall: 1. Terminal identifications for appearance only. 62-0273-05 C W1 G G2 Y G3 O/B S1 RC S2 R M27415 Fig. 4. SCREW TERMINALS THERMOSTAT M22267 Fig. 2. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT CAUTION Electrical Shock or Equipment Damage Hazard. Can shock...
... M22268 MOUNTING SCREWS (2) Fig. 3. Refer to prevent drafts from Thermostat 1. Pull the wires through the wire hole on the wall: 1. Terminal identifications for appearance only. 62-0273-05 C W1 G G2 Y G3 O/B S1 RC S2 R M27415 Fig. 4. SCREW TERMINALS THERMOSTAT M22267 Fig. 2. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT CAUTION Electrical Shock or Equipment Damage Hazard. Can shock...
Installation Instructions
Page 3
... Coil (with batteries. G2 Fan relay. R (see Note 2) Common wire from the thermostat control cable. Y Compressor output. Common wire is optional when thermostat is configured for a heat pump in place between RC and R. WIRE TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT WALLPLATE WALL OPENING SHADED AREA M22266 Fig. 5. Restrict wires to secondary side of cooling system transformer. High fan...
... Coil (with batteries. G2 Fan relay. R (see Note 2) Common wire from the thermostat control cable. Y Compressor output. Common wire is optional when thermostat is configured for a heat pump in place between RC and R. WIRE TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT WALLPLATE WALL OPENING SHADED AREA M22266 Fig. 5. Restrict wires to secondary side of cooling system transformer. High fan...
Installation Instructions
Page 4
...REQUIRED. 2 FACTORY INSTALLED JUMPER. 3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. Typical hookup of single transformer 1H/1C system. Typical wiring of heat-only system with fan. 1 L1 (HOT) 3 C W1 G G2 Y G3 24 VAC O/B S1 L2 RC S2 R2 ...THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY. M27419 Fig. 9. Typical hookup of cool-only system. 62-0273-05 4 TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Conventional System Wiring L1 1 (HOT) C 3 W1 G G2 Y G3 24 VAC O/B S1 L2 RC S2 R2 COMPRESSOR CONTACTOR FAN RELAY...
...REQUIRED. 2 FACTORY INSTALLED JUMPER. 3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. Typical hookup of single transformer 1H/1C system. Typical wiring of heat-only system with fan. 1 L1 (HOT) 3 C W1 G G2 Y G3 24 VAC O/B S1 L2 RC S2 R2 ...THE COMMON MUST CONNECT TO THE COOLING TRANSFORMER SECONDARY. M27419 Fig. 9. Typical hookup of cool-only system. 62-0273-05 4 TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Conventional System Wiring L1 1 (HOT) C 3 W1 G G2 Y G3 24 VAC O/B S1 L2 RC S2 R2 COMPRESSOR CONTACTOR FAN RELAY...
Installation Instructions
Page 5
... IS OPTIONAL. 4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. 5 OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Heat Pump System Wiring Fan Coil System Wiring L1 (HOT) 3 24 VAC C W1 L2 G G2 1 Y G3 4 O/B S1 RC S2 R2 CHANGEOVER VALVE COMPRESSOR CONTACTOR FAN RELAY INDOOR TEMPERATURE...
... IS OPTIONAL. 4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. 5 OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Heat Pump System Wiring Fan Coil System Wiring L1 (HOT) 3 24 VAC C W1 L2 G G2 1 Y G3 4 O/B S1 RC S2 R2 CHANGEOVER VALVE COMPRESSOR CONTACTOR FAN RELAY INDOOR TEMPERATURE...
Installation Instructions
Page 6
... and LO fan speeds (2H/1C). 1 TR21-A 1 TR21-A 1 THE TR21-A IS A 10K OHM SENSOR. Wiring two TR21 (20K ohm) Sensors and one TR21-A (10K ohm) Sensor to provide a temperature averaging network. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT PTAC System Wiring Sensor Wiring for Temperature Averaging L1 (HOT) 3 24 VAC C W1 L2 G G2 1 Y G3 4 O/B S1 RC...
... and LO fan speeds (2H/1C). 1 TR21-A 1 TR21-A 1 THE TR21-A IS A 10K OHM SENSOR. Wiring two TR21 (20K ohm) Sensors and one TR21-A (10K ohm) Sensor to provide a temperature averaging network. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT PTAC System Wiring Sensor Wiring for Temperature Averaging L1 (HOT) 3 24 VAC C W1 L2 G G2 1 Y G3 4 O/B S1 RC...
Installation Instructions
Page 7
.... 21. REMOVE DURING INSTALLATION POWER THE THERMOSTAT You can choose from thermostat back. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SUBBASE S1 S2 1 C7189 C7189 2. Push the thermostat straight onto the wallplate until it snaps into place. Mount thermostat to set the real-time clock. C7189 C7189 REMOVE TAB REMOVE DURING INSTALLATION 1 WIRES MUST HAVE A CABLE SEPARATE FROM...
.... 21. REMOVE DURING INSTALLATION POWER THE THERMOSTAT You can choose from thermostat back. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SUBBASE S1 S2 1 C7189 C7189 2. Push the thermostat straight onto the wallplate until it snaps into place. Mount thermostat to set the real-time clock. C7189 C7189 REMOVE TAB REMOVE DURING INSTALLATION 1 WIRES MUST HAVE A CABLE SEPARATE FROM...
Installation Instructions
Page 14
... operation, depending on the secondary side of equipment in the display and the compressor and fan turn on . If the thermostat is system powered (common wire), the Minimum-Off Timer is not Heat (Heat on) or Cool operating. (Cool on . When the Minimum Off ...0170 and make sure correct system type is chosen. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT System Settings Heat-Thermostat controls the heating system. Fan Settings Auto -Fan runs only when heating/cooling system is not present, check wire connection (loose or broken) between power and common. ...
... operation, depending on the secondary side of equipment in the display and the compressor and fan turn on . If the thermostat is system powered (common wire), the Minimum-Off Timer is not Heat (Heat on) or Cool operating. (Cool on . When the Minimum Off ...0170 and make sure correct system type is chosen. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT System Settings Heat-Thermostat controls the heating system. Fan Settings Auto -Fan runs only when heating/cooling system is not present, check wire connection (loose or broken) between power and common. ...
Installation Instructions
Page 15
... is not set to Heat and/ Set the system setting to Heat and set the or temperature setting is active. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 6. Troubleshooting. (Continued) Symptom Possible Cause Action Heat pump puts out cool Changeover Valve (Installer Setup air in ...0190) is set temperature setting above room temperature. Both the heating and cooling equipment are shorted Separate the shorted heating and cooling wires. The heating equipment is not a heat pump but the System Type (Installer Setup Number 0170) is not configured to match ...
... is not set to Heat and/ Set the system setting to Heat and set the or temperature setting is active. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 6. Troubleshooting. (Continued) Symptom Possible Cause Action Heat pump puts out cool Changeover Valve (Installer Setup air in ...0190) is set temperature setting above room temperature. Both the heating and cooling equipment are shorted Separate the shorted heating and cooling wires. The heating equipment is not a heat pump but the System Type (Installer Setup Number 0170) is not configured to match ...