Installation Instructions
Page 1
TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat APPLICATION INSTALLATION INSTRUCTIONS The TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat provides electronic control of properly. TB7100A Thermostat Description. Read these instructions. 62-0273-05 Description • Battery only • 24 Vac only • 24 Vac with battery backup • Conventional (1 Heat, 1 Cool ...
TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat APPLICATION INSTALLATION INSTRUCTIONS The TB7100A1000 MultiPRO™ Multispeed and Multipurpose Thermostat provides electronic control of properly. TB7100A Thermostat Description. Read these instructions. 62-0273-05 Description • Battery only • 24 Vac only • 24 Vac with battery backup • Conventional (1 Heat, 1 Cool ...
Installation Instructions
Page 2
... and tighten. See Fig. 5. 5. Concealed pipes and chimneys. - Terminal identifications for the application. 3. Separate the wallplate from the thermostat control cable. Position the wallplate on the wallplate. 2. Disconnect power supply before installation. M22258 Fig. 1. NOTES: - - - Pull... or short equipment circuitry. All wiring must have a cable separate from the thermostat. Select thermostat location. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT CAUTION Electrical Shock or Equipment Damage Hazard. Shielded cable is not required.
... and tighten. See Fig. 5. 5. Concealed pipes and chimneys. - Terminal identifications for the application. 3. Separate the wallplate from the thermostat control cable. Position the wallplate on the wallplate. 2. Disconnect power supply before installation. M22258 Fig. 1. NOTES: - - - Pull... or short equipment circuitry. All wiring must have a cable separate from the thermostat. Select thermostat location. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT CAUTION Electrical Shock or Equipment Damage Hazard. Shielded cable is not required.
Installation Instructions
Page 3
WIRE TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT WALLPLATE WALL OPENING SHADED AREA M22266 Fig. 5. W1 Heat relay. Common wire is optional when thermostat is configured for cooling-connect to shaded area of cooling system transformer. Sensor wires must come from the thermostat control cable....have a cable separate from the cooling transformer. C (see Note 1) Power for a heat pump in place between RC and R. If thermostat is used with Auxiliary Heat) 14 2 Pipe Fan Coil (no Auxiliary Heat) 15 PTAC 1H/1C (High speed, Low speed 16...
WIRE TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT WALLPLATE WALL OPENING SHADED AREA M22266 Fig. 5. W1 Heat relay. Common wire is optional when thermostat is configured for cooling-connect to shaded area of cooling system transformer. Sensor wires must come from the thermostat control cable....have a cable separate from the cooling transformer. C (see Note 1) Power for a heat pump in place between RC and R. If thermostat is used with Auxiliary Heat) 14 2 Pipe Fan Coil (no Auxiliary Heat) 15 PTAC 1H/1C (High speed, Low speed 16...
Installation Instructions
Page 4
... SECONDARY. M27418 Fig. 8. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FACTORY INSTALLED JUMPER. 3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Conventional System Wiring L1 1 (HOT) C 3 W1 G G2 Y G3 24 VAC O/B S1 L2 RC S2 R2 COMPRESSOR CONTACTOR FAN RELAY INDOOR TEMPERATURE SENSOR/REMOTE...
... SECONDARY. M27418 Fig. 8. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FACTORY INSTALLED JUMPER. 3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Conventional System Wiring L1 1 (HOT) C 3 W1 G G2 Y G3 24 VAC O/B S1 L2 RC S2 R2 COMPRESSOR CONTACTOR FAN RELAY INDOOR TEMPERATURE SENSOR/REMOTE...
Installation Instructions
Page 5
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FACTORY INSTALLED JUMPER. 3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. PROVIDE... 5 AUXILIARY HEAT RELAY 1 POWER SUPPLY. M27422 Fig. 12. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE. Typical wiring of single-stage heat pump with no auxiliary heat (1H/1C). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Heat Pump System Wiring Fan Coil System Wiring L1 (HOT) 3 24 VAC C W1 L2 G G2 1...
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 FACTORY INSTALLED JUMPER. 3 WHEN USING BATTERIES, THE 24V COMMON CONNECTION IS OPTIONAL. PROVIDE... 5 AUXILIARY HEAT RELAY 1 POWER SUPPLY. M27422 Fig. 12. WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE. Typical wiring of single-stage heat pump with no auxiliary heat (1H/1C). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Heat Pump System Wiring Fan Coil System Wiring L1 (HOT) 3 24 VAC C W1 L2 G G2 1...
Installation Instructions
Page 6
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE. Wiring four TR21 (20K ohm) Sensors. Wiring two TR21-A (10K ohm) Sensors to provide a temperature averaging network 62-0273-05 6 M27426 Fig. 16. ...IS OPTIONAL. 4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. 5 OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. M27427 Fig. 17. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT PTAC System Wiring Sensor Wiring for Temperature Averaging L1 (HOT) 3 24 VAC C W1 L2 G G2 1 Y G3 4 O/B S1 RC S2 R2 CHANGEOVER VALVE ...
WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE. Wiring four TR21 (20K ohm) Sensors. Wiring two TR21-A (10K ohm) Sensors to provide a temperature averaging network 62-0273-05 6 M27426 Fig. 16. ...IS OPTIONAL. 4 "O/B" TERMINAL SET TO CONTROL AS EITHER "O" OR "B" IN THE INSTALLER SETUP. 5 OPTIONAL INDOOR REMOTE SENSOR OR REMOTE SETBACK. M27427 Fig. 17. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT PTAC System Wiring Sensor Wiring for Temperature Averaging L1 (HOT) 3 24 VAC C W1 L2 G G2 1 Y G3 4 O/B S1 RC S2 R2 CHANGEOVER VALVE ...
Installation Instructions
Page 7
... 1. Wiring 24 Vac Common • Single-Transformer System-Connect the common side of the thermostat. 2. Remove tab labeled REMOVE from three methods to provide a temperature averaging network. Mount thermostat to set the real-time clock. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SUBBASE S1 S2 1 C7189 C7189 2. Locate and remove the tab labeled Remove. See...
... 1. Wiring 24 Vac Common • Single-Transformer System-Connect the common side of the thermostat. 2. Remove tab labeled REMOVE from three methods to provide a temperature averaging network. Mount thermostat to set the real-time clock. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SUBBASE S1 S2 1 C7189 C7189 2. Locate and remove the tab labeled Remove. See...
Installation Instructions
Page 8
...ways to set the calendar and time for this thermostat: SETTING DATE/TIME WHEN THERMOSTAT IS FIRST POWERED When the thermostat is first powered, the display is ready to set year, month and day. SETTING DATE/TIME AFTER THERMOSTAT IS ALREADY FUNCTIONING Use the installer setup to ten ... and Tests section. These settings can be adjusted to match the HVAC system. M23023A 62-0273-05 8 TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SETTING CALENDAR AND TIME This thermostat is designed to, under normal use, automatically keep current time and day in memory for up to set ...
...ways to set the calendar and time for this thermostat: SETTING DATE/TIME WHEN THERMOSTAT IS FIRST POWERED When the thermostat is first powered, the display is ready to set year, month and day. SETTING DATE/TIME AFTER THERMOSTAT IS ALREADY FUNCTIONING Use the installer setup to ten ... and Tests section. These settings can be adjusted to match the HVAC system. M23023A 62-0273-05 8 TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SETTING CALENDAR AND TIME This thermostat is designed to, under normal use, automatically keep current time and day in memory for up to set ...
Installation Instructions
Page 9
... Date (Day) 15 1-31 (Month Dependent) 0160 Schedule Options 4 0-Non-Programmable 4-Programmable 0170 System Selection 1 1-1H/1C Conv Relay Y is selected (ISU 0170). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4) Configure Installer Setup 1. Shown for heat pump, fan coil, PTAC, and conventional cooling stages. 0240 CPH...
... Date (Day) 15 1-31 (Month Dependent) 0160 Schedule Options 4 0-Non-Programmable 4-Programmable 0170 System Selection 1 1-1H/1C Conv Relay Y is selected (ISU 0170). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT INSTALLER SETUP NUMBERS, SETTINGS, AND TESTS (TABLE 4) Configure Installer Setup 1. Shown for heat pump, fan coil, PTAC, and conventional cooling stages. 0240 CPH...
Installation Instructions
Page 10
... Number Installer Setup Name Default Setting All Settings Notes 0300 Changeover 1 0-Manual 1-Auto Only shown if system has both heat and cool stages (ISU 0170). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 4.
... Number Installer Setup Name Default Setting All Settings Notes 0300 Changeover 1 0-Manual 1-Auto Only shown if system has both heat and cool stages (ISU 0170). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 4.
Installation Instructions
Page 11
... setting affects control operation in CNV, Heat Pump, PTAC (ISU 0170). Fan will be set after the user selects the constant fan speed. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 4. If 2 is calculated after initial call for fan coil or PTAC applications. 0 means no limit. Only shown if system has cool stages...
... setting affects control operation in CNV, Heat Pump, PTAC (ISU 0170). Fan will be set after the user selects the constant fan speed. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 4. If 2 is calculated after initial call for fan coil or PTAC applications. 0 means no limit. Only shown if system has cool stages...
Installation Instructions
Page 12
...: Press the Done key to default energy savings (see Table 5). Only shown if system has fan. Systems with more heating than cooling stages). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Installer Setup Number Installer Setup Name 0700 Temperature Display Offset 0710 0720 Restore Factory Defaults Screen Display INSTALLER TESTS Test 1 Installer Test Cool...
...: Press the Done key to default energy savings (see Table 5). Only shown if system has fan. Systems with more heating than cooling stages). TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Installer Setup Number Installer Setup Name 0700 Temperature Display Offset 0710 0720 Restore Factory Defaults Screen Display INSTALLER TESTS Test 1 Installer Test Cool...
Installation Instructions
Page 13
... (ISU 343) and unoccupied cooling (ISU 346) setpoints are available to auto mode after the time period expires. OPERATION TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Fan Sequence Operations (ISU 347, 348, 349) If heat pump or conventional application modes are enabled in ISU 170, ... fan ramping algorithm enabled (ISU 347). Occupancy sensors, manual time clock inputs, and DDC night setback can provide restrictions on the thermostat for PI control. Lockout configuration via ISU 670 can be G, located on the auxiliary heat. Preoccupancy purge (ISU 185) This ...
... (ISU 343) and unoccupied cooling (ISU 346) setpoints are available to auto mode after the time period expires. OPERATION TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Fan Sequence Operations (ISU 347, 348, 349) If heat pump or conventional application modes are enabled in ISU 170, ... fan ramping algorithm enabled (ISU 347). Occupancy sensors, manual time clock inputs, and DDC night setback can provide restrictions on the thermostat for PI control. Lockout configuration via ISU 670 can be G, located on the auxiliary heat. Preoccupancy purge (ISU 185) This ...
Installation Instructions
Page 14
...heat terminal (W) and transformer common. See the Sensor instructions for cooling or heating during the Minimum-Off Time, the thermostat displays "Wait." - on indoor temperature. Temperature settings do The upper or lower temperature limits Check temperature setpoints. The ... Guide for a minimum of equipment in the display). Cool-Thermostat controls the cooling system. Wait up to find the cause of the problem. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT System Settings Heat-Thermostat controls the heating system. Fan is incorrect. Verify operation of ...
...heat terminal (W) and transformer common. See the Sensor instructions for cooling or heating during the Minimum-Off Time, the thermostat displays "Wait." - on indoor temperature. Temperature settings do The upper or lower temperature limits Check temperature setpoints. The ... Guide for a minimum of equipment in the display). Cool-Thermostat controls the cooling system. Wait up to find the cause of the problem. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT System Settings Heat-Thermostat controls the heating system. Fan is incorrect. Verify operation of ...
Installation Instructions
Page 15
...cooling wires are running in the display. Check for 24 Vac at the same time. Check for 24 Vac between the thermostat and the cooling equipment. Loose or broken wire connection between the cool terminal (Y) and transformer common. Heating equipment Heating equipment...and/ Set the system setting to Cool and set temperature setting above room temperature. below the room temperature. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 6. Troubleshooting. (Continued) Symptom Possible Cause Action Heat pump puts out cool Changeover Valve (Installer Setup air ...
...cooling wires are running in the display. Check for 24 Vac at the same time. Check for 24 Vac between the thermostat and the cooling equipment. Loose or broken wire connection between the cool terminal (Y) and transformer common. Heating equipment Heating equipment...and/ Set the system setting to Cool and set temperature setting above room temperature. below the room temperature. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 6. Troubleshooting. (Continued) Symptom Possible Cause Action Heat pump puts out cool Changeover Valve (Installer Setup air ...
Installation Instructions
Page 16
...handling may contain Perchlorate material. Registered Trademark © 2011 Honeywell International Inc. 62-0273-05 M.S. Perchlorate Material This thermostat contains a Lithium battery which may apply. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden...Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. C7772 Flush-Mount Remote Indoor Sensor: 20K ohm NTC. Rev. 03-11 Printed in . (35 mm) deep. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SPECIFICATIONS Electrical Ratings: Terminal W (Heating) Y (...
...handling may contain Perchlorate material. Registered Trademark © 2011 Honeywell International Inc. 62-0273-05 M.S. Perchlorate Material This thermostat contains a Lithium battery which may apply. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden...Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. C7772 Flush-Mount Remote Indoor Sensor: 20K ohm NTC. Rev. 03-11 Printed in . (35 mm) deep. TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT SPECIFICATIONS Electrical Ratings: Terminal W (Heating) Y (...