HP D2220sb Storage Blade Maintenance and Service Guide
Page 3
... and data loss 22 Remove the access panel ...26 Install the access panel ...26 Drive blank...26 Drive...27 FBWC capacitor pack ...29 FBWC module ...30 Front panel ...31 LED panel...32 System board ...33 Drive drawer ...37 Enclosure release latch assembly ...39 Diagnostic tools ...41 HP ROM-Based Setup Utility ...41 Using RBSU ...41 HP Insight Diagnostics ...41 HP Insight Diagnostics survey functionality 42 Active Health System ...42 Integrated Management Log...43 Troubleshooting ...44 Troubleshooting...
... and data loss 22 Remove the access panel ...26 Install the access panel ...26 Drive blank...26 Drive...27 FBWC capacitor pack ...29 FBWC module ...30 Front panel ...31 LED panel...32 System board ...33 Drive drawer ...37 Enclosure release latch assembly ...39 Diagnostic tools ...41 HP ROM-Based Setup Utility ...41 Using RBSU ...41 HP Insight Diagnostics ...41 HP Insight Diagnostics survey functionality 42 Active Health System ...42 Integrated Management Log...43 Troubleshooting ...44 Troubleshooting...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 19
...do not open for some procedures: • T-10 Torx screwdriver • HP Insight Diagnostics software ("HP Insight Diagnostics" on page 41) Safety considerations Before performing service procedures, review all the safety ...Refer all maintenance, upgrades, and servicing to qualified personnel. Removal and replacement procedures 19 This symbol indicates the presence of hazardous energy circuits or electric shock hazards. The area contains no user or field serviceable parts. Do not open this enclosure. WARNING: To reduce the risk of potentially hazardous conditions. WARNING...
...do not open for some procedures: • T-10 Torx screwdriver • HP Insight Diagnostics software ("HP Insight Diagnostics" on page 41) Safety considerations Before performing service procedures, review all the safety ...Refer all maintenance, upgrades, and servicing to qualified personnel. Removal and replacement procedures 19 This symbol indicates the presence of hazardous energy circuits or electric shock hazards. The area contains no user or field serviceable parts. Do not open this enclosure. WARNING: To reduce the risk of potentially hazardous conditions. WARNING...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 20
... 21). 2. CAUTION: Do not operate the D2220sb with the access panel removed. Storage blade preparation Servicing internal storage blade components To service any internal D2220sb component, do not plug telephone or telecommunications connectors into the enclosure. This symbol indicates that the equipment is supplied by multiple sources of shock or injury from electric shock, remove all power cords to handle safely. WARNING: To reduce the risk...
... 21). 2. CAUTION: Do not operate the D2220sb with the access panel removed. Storage blade preparation Servicing internal storage blade components To service any internal D2220sb component, do not plug telephone or telecommunications connectors into the enclosure. This symbol indicates that the equipment is supplied by multiple sources of shock or injury from electric shock, remove all power cords to handle safely. WARNING: To reduce the risk...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 21
... beginning any installation procedure. For information about removing a half-height device, see the half-height device user guide. 4. Remove the D2220sb: Removal and replacement procedures 21 See the server blade documentation. Power down the partner server blade. o Remove the half-height device installed above the D2220sb. To power down the D2220sb, power down the partner server blade (on page 21). 3. Remove the D2220sb WARNING: To reduce the risk of the following: o Remove the blank installed above the D2220sb. Taking this...
... beginning any installation procedure. For information about removing a half-height device, see the half-height device user guide. 4. Remove the D2220sb: Removal and replacement procedures 21 See the server blade documentation. Power down the partner server blade. o Remove the half-height device installed above the D2220sb. To power down the D2220sb, power down the partner server blade (on page 21). 3. Remove the D2220sb WARNING: To reduce the risk of the following: o Remove the blank installed above the D2220sb. Taking this...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 23
...; A fast beep and flash (2 per second)-To avoid drive damage or data loss and storage blade shutdown, close the drive drawer immediately. Power down the partner server blade (on the D2220sb. 2. IMPORTANT: The drive drawer is not fully extended until the rail lock is closed . Removal and replacement procedures 23 The drives are populated with either a component or a blank. Remove the drives Use this procedure to electrical components...
...; A fast beep and flash (2 per second)-To avoid drive damage or data loss and storage blade shutdown, close the drive drawer immediately. Power down the partner server blade (on the D2220sb. 2. IMPORTANT: The drive drawer is not fully extended until the rail lock is closed . Removal and replacement procedures 23 The drives are populated with either a component or a blank. Remove the drives Use this procedure to electrical components...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 24
... beginning any installation procedure. Remove the FBWC module Use this procedure to the bay in a static-free environment. 5. Removal and replacement procedures 24 WARNING: To reduce the risk of personal injury from hot surfaces, allow the drives and the internal system components to indicate the drive bay from which it was removed. 7. To replace a failed or broken module, see "FBWC module (on each drive to remove the FBWC module when servicing other...
... beginning any installation procedure. Remove the FBWC module Use this procedure to the bay in a static-free environment. 5. Removal and replacement procedures 24 WARNING: To reduce the risk of personal injury from hot surfaces, allow the drives and the internal system components to indicate the drive bay from which it was removed. 7. To replace a failed or broken module, see "FBWC module (on each drive to remove the FBWC module when servicing other...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 25
... lead to the FBWC module. 6. Operating the D2220sb in this manner results in a static-free environment. Remove the D2220sb (on the D2220sb. 2. The drive drawer and cable spool are not shown for clarity. 7. Remove the cache module from the system board. CAUTION: Do not operate the D2220sb with the access panel open or removed. Back up all data on page 21). 4. Removal and replacement procedures 25 Open the drive drawer. Extend the...
... lead to the FBWC module. 6. Operating the D2220sb in this manner results in a static-free environment. Remove the D2220sb (on the D2220sb. 2. The drive drawer and cable spool are not shown for clarity. 7. Remove the cache module from the system board. CAUTION: Do not operate the D2220sb with the access panel open or removed. Back up all data on page 21). 4. Removal and replacement procedures 25 Open the drive drawer. Extend the...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 26
... can cause ESD. When the service procedures are complete, install the module by reversing the removal procedure. Power down the partner server blade (on page 21). 3. Press the access panel release button. 4. CAUTION: To prevent damage to thermal damage. Operating the D2220sb in this manner results in ). 2. Allow the panel to electrical components, properly ground the D2220sb before beginning any installation procedure. CAUTION: To prevent damage to...
... can cause ESD. When the service procedures are complete, install the module by reversing the removal procedure. Power down the partner server blade (on page 21). 3. Press the access panel release button. 4. CAUTION: To prevent damage to thermal damage. Operating the D2220sb in this manner results in ). 2. Allow the panel to electrical components, properly ground the D2220sb before beginning any installation procedure. CAUTION: To prevent damage to...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 27
... the removal procedure. Improper grounding can cause ESD. Removal and replacement procedures 27 The drives are populated with either a component or a blank. CAUTION: To prevent improper cooling and thermal damage, do not operate the D2220sb or the enclosure unless all enclosure device bays and the first three storage drive bays are not fully protected by system air flow. • A fast beep and flash (2 per...
... the removal procedure. Improper grounding can cause ESD. Removal and replacement procedures 27 The drives are populated with either a component or a blank. CAUTION: To prevent improper cooling and thermal damage, do not operate the D2220sb or the enclosure unless all enclosure device bays and the first three storage drive bays are not fully protected by system air flow. • A fast beep and flash (2 per...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 28
...) past the initial resistance. The drives are populated with either a component or a blank. To remove the component: 1. The drive drawer open . Removal and replacement procedures 28 CAUTION: To prevent improper cooling and thermal damage, do not operate the D2220sb or the enclosure unless the first drive bay is populated with a drive, and drive bays 2 and 3 and all server data. 3. CAUTION: Thermal regulation is maintained...
...) past the initial resistance. The drives are populated with either a component or a blank. To remove the component: 1. The drive drawer open . Removal and replacement procedures 28 CAUTION: To prevent improper cooling and thermal damage, do not operate the D2220sb or the enclosure unless the first drive bay is populated with a drive, and drive bays 2 and 3 and all server data. 3. CAUTION: Thermal regulation is maintained...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 29
... before beginning any installation procedure. Remove the access panel (on page 21). 3. 4. Power down the partner server blade (on page 26). Remove the drive. CAUTION: Do not operate the D2220sb with the access panel open or removed. To remove the component: 1. Operating the D2220sb in this manner results in improper airflow and improper cooling that can cause ESD. Back up all data on page 21). 4. Removal and replacement procedures 29 Improper...
... before beginning any installation procedure. Remove the access panel (on page 21). 3. 4. Power down the partner server blade (on page 26). Remove the drive. CAUTION: Do not operate the D2220sb with the access panel open or removed. To remove the component: 1. Operating the D2220sb in this manner results in improper airflow and improper cooling that can cause ESD. Back up all data on page 21). 4. Removal and replacement procedures 29 Improper...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 30
... not operate the D2220sb with the access panel open or removed. Back up all data on page 21). 3. CAUTION: Be sure to wind the cable counterclockwise and to electrical components, properly ground the server blade before touching them. Remove the D2220sb (on page 26). To remove the component: 1. Removal and replacement procedures 30 Disconnect the FBWC capacitor pack cable from hot surfaces, allow the drives and...
... not operate the D2220sb with the access panel open or removed. Back up all data on page 21). 3. CAUTION: Be sure to wind the cable counterclockwise and to electrical components, properly ground the server blade before touching them. Remove the D2220sb (on page 26). To remove the component: 1. Removal and replacement procedures 30 Disconnect the FBWC capacitor pack cable from hot surfaces, allow the drives and...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 33
... module ("FBWC module" on page 21). 3. Power down the partner server blade (on page 30). Tilt the LED panel away from hot surfaces, allow the drives and the internal system components to electrical components, properly ground the server blade before touching them. Improper grounding can lead to thermal damage. CAUTION: Do not operate the D2220sb with the access panel open or removed. Remove the access panel...
... module ("FBWC module" on page 21). 3. Power down the partner server blade (on page 30). Tilt the LED panel away from hot surfaces, allow the drives and the internal system components to electrical components, properly ground the server blade before touching them. Improper grounding can lead to thermal damage. CAUTION: Do not operate the D2220sb with the access panel open or removed. Remove the access panel...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 37
.... Remove the access panel (on page 21). 3. 10. Power up all drives ("Remove the drives" on page 21). 4. Back up the partner server blade. Remove the D2220sb (on page 23). 5. Install the storage blade. 11. After you replace the system board, you must re-enter the product identification and serial number in the CLI: SET DEVICE SERIAL_NUMBER BLADE Drive drawer WARNING: To reduce the risk of the Onboard Administrator module or remotely...
.... Remove the access panel (on page 21). 3. 10. Power up all drives ("Remove the drives" on page 21). 4. Back up the partner server blade. Remove the D2220sb (on page 23). 5. Install the storage blade. 11. After you replace the system board, you must re-enter the product identification and serial number in the CLI: SET DEVICE SERIAL_NUMBER BLADE Drive drawer WARNING: To reduce the risk of the Onboard Administrator module or remotely...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 41
... typical server operation, but configuration settings can include the following keys: • To access RBSU, press the F9 key during power-up • After defaults have been restored Default configuration settings are applied to assist IT administrators who verify server blade installations, troubleshoot problems, and perform repair validation. Default configuration settings are sufficient for a highlighted configuration option, press the F1 key. To change a selected setting, you press the Enter key. HP Insight Diagnostics HP Insight Diagnostics is a configuration utility...
... typical server operation, but configuration settings can include the following keys: • To access RBSU, press the F9 key during power-up • After defaults have been restored Default configuration settings are applied to assist IT administrators who verify server blade installations, troubleshoot problems, and perform repair validation. Default configuration settings are sufficient for a highlighted configuration option, press the F1 key. To change a selected setting, you press the Enter key. HP Insight Diagnostics HP Insight Diagnostics is a configuration utility...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 42
...; Server model • Serial number • Processor model and speed • Storage capacity and speed • Memory capacity and speed • Firmware/BIOS HP Active Health System does not collect information about Active Health System users' operations, finances, customers, employees, partners, or data center, such as IP addresses, host names, user names, and Diagnostic tools 42 The Active Health System assists in the server hardware and system configuration. HP Insight Diagnostics Online...
...; Server model • Serial number • Processor model and speed • Storage capacity and speed • Memory capacity and speed • Firmware/BIOS HP Active Health System does not collect information about Active Health System users' operations, finances, customers, employees, partners, or data center, such as IP addresses, host names, user names, and Diagnostic tools 42 The Active Health System assists in the server hardware and system configuration. HP Insight Diagnostics Online...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 43
The IML timestamps each event with the system monitoring provided by the operating system. Integrated Management Log The IML records hundreds of hardware and configuration changes, system status, and service alerts for various server components. The data that you can be downloaded manually from third-party error event log activities, such as content created or passed through by Agentless Management or SNMP Pass-thru, provides continuous monitoring of events and stores them in...
The IML timestamps each event with the system monitoring provided by the operating system. Integrated Management Log The IML records hundreds of hardware and configuration changes, system status, and service alerts for various server components. The data that you can be downloaded manually from third-party error event log activities, such as content created or passed through by Agentless Management or SNMP Pass-thru, provides continuous monitoring of events and stores them in...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 46
... operation Solid amber = Drive failed Flashing amber = Predictive failure Solid green = Drive installed Flashing green = Drive activity established Flashing green (slow) = Drive rebuilding Green = Normal operation Flashing amber = No partner blade, or not yet recognized Solid amber = Degraded condition Flashing red = System critical Red = Drive over-temperature triggered shutdown *The drawer open LED flashes when the drive drawer open alarm (on page 46) is activated. ** The health status LED bar flashes amber when the storage blade establishes a connection with...
... operation Solid amber = Drive failed Flashing amber = Predictive failure Solid green = Drive installed Flashing green = Drive activity established Flashing green (slow) = Drive rebuilding Green = Normal operation Flashing amber = No partner blade, or not yet recognized Solid amber = Degraded condition Flashing red = System critical Red = Drive over-temperature triggered shutdown *The drawer open LED flashes when the drive drawer open alarm (on page 46) is activated. ** The health status LED bar flashes amber when the storage blade establishes a connection with...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 47
... fail. Drive LED definitions Item 1 2 3 4 LED Locate Activity ring Do not remove Drive status Status Solid blue Flashing blue Definition The drive is being identified by a RAID controller. Removing the drive does not cause a logical drive to normal operating temperature. The drive carrier firmware is being updated or requires an update. Removing the drive causes one or more logical drives and predicts the drive will fail. Component identification 47 The drive is not configured and predicts the drive will fail...
... fail. Drive LED definitions Item 1 2 3 4 LED Locate Activity ring Do not remove Drive status Status Solid blue Flashing blue Definition The drive is being identified by a RAID controller. Removing the drive does not cause a logical drive to normal operating temperature. The drive carrier firmware is being updated or requires an update. Removing the drive causes one or more logical drives and predicts the drive will fail. Component identification 47 The drive is not configured and predicts the drive will fail...
HP D2220sb Storage Blade Maintenance and Service Guide
Page 51
... specifications 48 error messages 44 F front panel components 45 front panel LEDs 46 H health LEDs 46 HP Insight Diagnostics 41, 42 I illustrated parts catalog 15 Insight Diagnostics 41, 42 installing the access panel 26 Integrated Management Log (IML) 43 L LED, health 46 LED, internal health 46 LEDs 47 LEDs, drive 47 LEDs, front panel 46, 47 M management tools 41 P part numbers 15 powering down 21 preparation procedures problem diagnosis 44 20, 22 R removal and replacement procedures 19 removing the access panel 26 removing...
... specifications 48 error messages 44 F front panel components 45 front panel LEDs 46 H health LEDs 46 HP Insight Diagnostics 41, 42 I illustrated parts catalog 15 Insight Diagnostics 41, 42 installing the access panel 26 Integrated Management Log (IML) 43 L LED, health 46 LED, internal health 46 LEDs 47 LEDs, drive 47 LEDs, front panel 46, 47 M management tools 41 P part numbers 15 powering down 21 preparation procedures problem diagnosis 44 20, 22 R removal and replacement procedures 19 removing the access panel 26 removing...