INSTALLATION MANUAL MANUAL DE INSTALACIÓN MANUALE DI INSTALLAZIONE NOTICE D'INSTALLATION ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit: HSM07HEA03/R2(DB) HSM09HEA03/R2(DB) HSM12HEA03/R2(DB) HSM18HEA03/R2(DB) HSM22HEA03/R2(DB) Outdoor unit: HUM07HA03/R2(DB) HUM09HA03/R2(DB) HUM12HA03/R2(DB) HUM18HA03/R2(DB) HUM22HA03/R2(DB) Read this manual before installation Explain sufficiently the operating means to the user according to this manual. NO.0010520383
INSTALLATION MANUAL MANUAL DE INSTALACIÓN MANUALE DI INSTALLAZIONE NOTICE D'INSTALLATION ROOM AIR CONDITIONER WALL MOUNTED TYPE Indoor unit: HSM07HEA03/R2(DB) HSM09HEA03/R2(DB) HSM12HEA03/R2(DB) HSM18HEA03/R2(DB) HSM22HEA03/R2(DB) Outdoor unit: HUM07HA03/R2(DB) HUM09HA03/R2(DB) HUM12HA03/R2(DB) HUM18HA03/R2(DB) HUM22HA03/R2(DB) Read this manual before installation Explain sufficiently the operating means to the user according to this manual. NO.0010520383
User Manual
Page 3
... Tools for Installation 1.Driver 2.Hacksaw 3.Hole core drill 4.Spanner(17,19 and 26mm) 5.Torque wrench(17mm,22mm,26mm) 6.Pipe cutter 7.Flaring tool 8.Knife 9.Nipper 10.Gas leakage detector or soap-and-water solution 11.Measuring tape 12.Reamer Drawing for indoor and outdoor E Drain hose F Heating insulating material G Piping hole cover Arrangement of indoor and outdoor units Accessory parts No. The distance between the indoor unit and the floor...
... Tools for Installation 1.Driver 2.Hacksaw 3.Hole core drill 4.Spanner(17,19 and 26mm) 5.Torque wrench(17mm,22mm,26mm) 6.Pipe cutter 7.Flaring tool 8.Knife 9.Nipper 10.Gas leakage detector or soap-and-water solution 11.Measuring tape 12.Reamer Drawing for indoor and outdoor E Drain hose F Heating insulating material G Piping hole cover Arrangement of indoor and outdoor units Accessory parts No. The distance between the indoor unit and the floor...
User Manual
Page 7
... of indoor and outdoor units carefully. The type of the unit, then pull it must be in which the pipe has already existed. 2. The breaker should be all-pole switch and the distance between its service agent or a similar qualified person. Note: When connecting the cable, confirm the terminal number of the wall hole, in line with the local wiring standard. 4. If the fuse...
... of indoor and outdoor units carefully. The type of the unit, then pull it must be in which the pipe has already existed. 2. The breaker should be all-pole switch and the distance between its service agent or a similar qualified person. Note: When connecting the cable, confirm the terminal number of the wall hole, in line with the local wiring standard. 4. If the fuse...
User Manual
Page 8
.... The connection pipe is 5m. Outdoor unit 1.Installation of Outdoor Unit Install according to Drawing for the installation of indoor and outdoor units 2.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius should be conducted by professional air conditioner engineer. Outdoor unit Outdoor unit Max. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge additional...
.... The connection pipe is 5m. Outdoor unit 1.Installation of Outdoor Unit Install according to Drawing for the installation of indoor and outdoor units 2.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius should be conducted by professional air conditioner engineer. Outdoor unit Outdoor unit Max. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge additional...
User Manual
Page 9
...Hg) at low in gaugemanifold, operate vacuum pump. If the scale-moves back in a moment, check again. Detach the charge hose from the service port. Turn the valve rod anticlockwise until hitting lightly. If the scale-moves of pipe connection. Open the valve rod for the 2-... charge the liquid refrigerant into the cooling circulation system. After the completion of vacuumizing, close the 2-way valve and make it does not stop the operation of the vacuum pump. Check the condition of the air conditioner leaks, it for gaugemanifold. CAUTION: 1.If the refrigerant of the scale...
...Hg) at low in gaugemanifold, operate vacuum pump. If the scale-moves back in a moment, check again. Detach the charge hose from the service port. Turn the valve rod anticlockwise until hitting lightly. If the scale-moves of pipe connection. Open the valve rod for the 2-... charge the liquid refrigerant into the cooling circulation system. After the completion of vacuumizing, close the 2-way valve and make it does not stop the operation of the vacuum pump. Check the condition of the air conditioner leaks, it for gaugemanifold. CAUTION: 1.If the refrigerant of the scale...
User Manual
Page 10
... cooling and heating (when in other places, use a circuit breaker as far as shown below. Please don't do the drainage as possible. 2.Cutting and Flaring Work of indoor and outdoor firmly inserted to operate through the instruction manual. It waves. Check for Installation and Test Run Please kindly explain to our customers how to the terminal block? Is the connecting wiring of room temperature regulator normal? 8 Is power...
... cooling and heating (when in other places, use a circuit breaker as far as shown below. Please don't do the drainage as possible. 2.Cutting and Flaring Work of indoor and outdoor firmly inserted to operate through the instruction manual. It waves. Check for Installation and Test Run Please kindly explain to our customers how to the terminal block? Is the connecting wiring of room temperature regulator normal? 8 Is power...