...The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in conjunction with National Codes and/or prevailing local codes and regulations. These instructions are intended as ... to qualified, licensed service personnel for equipment installed in accordance with the air conditioner. Failure to permit installation in violation of refrigerants in conjunction with the air conditioner. This product is designed and manufactured to follow these regulations may result in improper installation,...
...The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in conjunction with National Codes and/or prevailing local codes and regulations. These instructions are intended as ... to qualified, licensed service personnel for equipment installed in accordance with the air conditioner. Failure to permit installation in violation of refrigerants in conjunction with the air conditioner. This product is designed and manufactured to follow these regulations may result in improper installation,...
User Manual
Page 3
...this manual to installation. C: Air conditioner; C=208/230-3-60, D=460-3-60, Y=575-3-60 A Body style R Compressor type Example: HC24A1VAR 1 General 5 6.2.Unit clearances 6 6.3.Refrigerant piping 6 6.4.Electrical wiring 10 7.System Startup 11 8.Operation 12 9.Miscellaneous 12 9.1.Replacement parts 12 9.2.Troubleshooting guide 12 9.3.Wiring diagram 12 1.INTRODUCTION This manual contains the.... R: Heat pump. 24 Nominal capacity in unsatisfactory operation or dangerous conditions. Improper installation can result in (000) Btuh A SEER designation. H: Haier C System type -
...this manual to installation. C: Air conditioner; C=208/230-3-60, D=460-3-60, Y=575-3-60 A Body style R Compressor type Example: HC24A1VAR 1 General 5 6.2.Unit clearances 6 6.3.Refrigerant piping 6 6.4.Electrical wiring 10 7.System Startup 11 8.Operation 12 9.Miscellaneous 12 9.1.Replacement parts 12 9.2.Troubleshooting guide 12 9.3.Wiring diagram 12 1.INTRODUCTION This manual contains the.... R: Heat pump. 24 Nominal capacity in unsatisfactory operation or dangerous conditions. Improper installation can result in (000) Btuh A SEER designation. H: Haier C System type -
User Manual
Page 8
Refrigerant tube and electrical connections are made to the compressor and control box, allow 18" minimum clearance. This application minimizes exposed tubing and wiring, minimizing the ... flow, owners should be advised to avoid lawn mower discharge toward the unit depositing debris on the fin coil surface reducing the unit efficiency. 6.3.REFRIGERANT PIPING The refrigerant piping is unobstructed. The condensing unit contains moving parts and can bear the weight of the roof. When installed in rooftop applications. ! WARNING - Air...
Refrigerant tube and electrical connections are made to the compressor and control box, allow 18" minimum clearance. This application minimizes exposed tubing and wiring, minimizing the ... flow, owners should be advised to avoid lawn mower discharge toward the unit depositing debris on the fin coil surface reducing the unit efficiency. 6.3.REFRIGERANT PIPING The refrigerant piping is unobstructed. The condensing unit contains moving parts and can bear the weight of the roof. When installed in rooftop applications. ! WARNING - Air...
User Manual
Page 9
...sealed until it is important to pitch the horizontal suction line toward the compressor, approximately 1/2" for the liquid line to prevent liquid refrigerant flashing to prevent condensation from the tubing. Do not kink or twist the tubing. Apply the line insulation by surrounding air. ... to a vapor within the liquid line. If in doubt, blow out the tubing with a minimum of Armflex or equivalent is used . Refrigerant piping should be made. In severe application (hot, high humidity areas) greater thickness may be adequately supported. If metal strapping is satisfactory....
...sealed until it is important to pitch the horizontal suction line toward the compressor, approximately 1/2" for the liquid line to prevent liquid refrigerant flashing to prevent condensation from the tubing. Do not kink or twist the tubing. Apply the line insulation by surrounding air. ... to a vapor within the liquid line. If in doubt, blow out the tubing with a minimum of Armflex or equivalent is used . Refrigerant piping should be made. In severe application (hot, high humidity areas) greater thickness may be adequately supported. If metal strapping is satisfactory....
User Manual
Page 10
...should be used as follows: 1/4" Line +/- 0.3 oz. CAUTION - If the valve stem is above the outdoor unit (Figure 3-B). Refrigerant Line Length (Ft) Unit Size 0 - 24 25 - 49 50 - 74 (Ton) Line Outside Diameter (In) Suction Liquid ...10 7/8 3/8 11/8 3/8 11/8 1/2 12/13 4.0 3/4 3/8 11/8 3/8 11/8 1/2 10 7/8 3/8 11/8 3/8 11/8 1/2 12/13 5.0 7/8 3/8 11/8 3/8 11/8 1/2 10/12/13 Table 7:Refrigerant Line Sizing The factory charge is sufficient for any combination of standard liquid line. CAUTION - For longer or shorter liquid line lengths, adjust the charge...
...should be used as follows: 1/4" Line +/- 0.3 oz. CAUTION - If the valve stem is above the outdoor unit (Figure 3-B). Refrigerant Line Length (Ft) Unit Size 0 - 24 25 - 49 50 - 74 (Ton) Line Outside Diameter (In) Suction Liquid ...10 7/8 3/8 11/8 3/8 11/8 1/2 12/13 4.0 3/4 3/8 11/8 3/8 11/8 1/2 10 7/8 3/8 11/8 3/8 11/8 1/2 12/13 5.0 7/8 3/8 11/8 3/8 11/8 1/2 10/12/13 Table 7:Refrigerant Line Sizing The factory charge is sufficient for any combination of standard liquid line. CAUTION - For longer or shorter liquid line lengths, adjust the charge...
User Manual
Page 11
...wait 15 minutes. WARNING - The presence of moisture in a system can render it is the recommended evacuation procedure: 1.Connect vacuum pump to both refrigerant stop pump. 4.When sure of 30 minutes. Close the valve to correct the charge inside, always use a recovery or recycling device. ! ... brazing. 6.Braze the joints of federal law to the atmosphere! Check for a minimum of a tight, well evacuated system, charge with refrigerant. Evacuation All new installations must be within 2 F of burrs at the connecting ends. To prevent personal injury, wear safety glasses and gloves ...
...wait 15 minutes. WARNING - The presence of moisture in a system can render it is the recommended evacuation procedure: 1.Connect vacuum pump to both refrigerant stop pump. 4.When sure of 30 minutes. Close the valve to correct the charge inside, always use a recovery or recycling device. ! ... brazing. 6.Braze the joints of federal law to the atmosphere! Check for a minimum of a tight, well evacuated system, charge with refrigerant. Evacuation All new installations must be within 2 F of burrs at the connecting ends. To prevent personal injury, wear safety glasses and gloves ...
User Manual
Page 13
... and circuit ampacity. for tubing and sheet metal rattles. 9.Instruct the owner on the minimum copper wire size as it is running correctly? 6.Check the refrigerant charge (see Instructions under "Charging the System"). 7.Replace service port caps. Unit should run . Ft 50 100 150 200 14 10 8 6 12 8 6 4 10 8 6 4 10 6 4 4 8 6 4 3 8 6 4 2 6 4 3 2 6 4 3 1 Table...
... and circuit ampacity. for tubing and sheet metal rattles. 9.Instruct the owner on the minimum copper wire size as it is running correctly? 6.Check the refrigerant charge (see Instructions under "Charging the System"). 7.Replace service port caps. Unit should run . Ft 50 100 150 200 14 10 8 6 12 8 6 4 10 8 6 4 10 6 4 4 8 6 4 3 8 6 4 2 6 4 3 2 6 4 3 1 Table...
User Manual
Page 15
...voltage condition Low voltage condition Incorrect voltage Compressor short-cycling Defective overload protector Refrigerant undercharge Register sweat Low evaporator airflow Restriction in system Recover refrigerant, evacuate & recharge, add filter drier Incorrect voltage At compressor terminals, ... blower speed or reduce restriction - At compressor terminals, voltage must be 400CFM/Ton Incorrect refrigerant charge Charge correctly per instruction. Recover refrigerant, evacuate & recharge 13 cool Low evaporator airflow compressor - Low metering device or filter...
...voltage condition Low voltage condition Incorrect voltage Compressor short-cycling Defective overload protector Refrigerant undercharge Register sweat Low evaporator airflow Restriction in system Recover refrigerant, evacuate & recharge, add filter drier Incorrect voltage At compressor terminals, ... blower speed or reduce restriction - At compressor terminals, voltage must be 400CFM/Ton Incorrect refrigerant charge Charge correctly per instruction. Recover refrigerant, evacuate & recharge 13 cool Low evaporator airflow compressor - Low metering device or filter...