Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 5
...temperature ranges for measuring equipment with a mains supply and/or measuring equipment deriving its output voltage directly from the distribution system. 5 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers and 4-pole with dc voltage respectively across the terminals E (ES) and S. and 4-pole with/without ...Hz, 162/3 Hz or with dc 4 digit (2999 Digit) - 7 segment liquid crystal display, digit size 18 mm (0.71 in the 1625 Users Manual. the instrument can be 3 V; • resistance of the auxiliary earth electrode and of the probes: 0 to satisfy European Standards requirements;
...temperature ranges for measuring equipment with a mains supply and/or measuring equipment deriving its output voltage directly from the distribution system. 5 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers and 4-pole with dc voltage respectively across the terminals E (ES) and S. and 4-pole with/without ...Hz, 162/3 Hz or with dc 4 digit (2999 Digit) - 7 segment liquid crystal display, digit size 18 mm (0.71 in the 1625 Users Manual. the instrument can be 3 V; • resistance of the auxiliary earth electrode and of the probes: 0 to satisfy European Standards requirements;
FE 1625 Users Manual
Page 1
® 1625 Earth/Ground Tester Users Manual January 2006 © 2006 Fluke Corporation, All rights reserved. Printed in USA All product names are trademarks of their respective companies.
® 1625 Earth/Ground Tester Users Manual January 2006 © 2006 Fluke Corporation, All rights reserved. Printed in USA All product names are trademarks of their respective companies.
FE 1625 Users Manual
Page 4
1625 Users Manual Measurement of Displays 72 ii Voltages and Frequencies 31 Measurement of Earthing Resistances 32 3-pole/4-pole Measurement of Earthing Resistance 33 Measurement of Single Earth ...
1625 Users Manual Measurement of Displays 72 ii Voltages and Frequencies 31 Measurement of Earthing Resistances 32 3-pole/4-pole Measurement of Earthing Resistance 33 Measurement of Single Earth ...
FE 1625 Users Manual
Page 10
1625 Users Manual Notes • The terms earth and earthing also refer to Appendix A for a complete set of operating information including specifications. • Selective measurements are described in the main section of this manual. • For stakeless earth resistance measurements, the EI-1625 must be purchased. (The EI-1625 comes standard with the 1625... Kit). Figure 1 displays the Fluke 1625 Earth/Ground Tester: START TEST 1625 EARTH / ...
1625 Users Manual Notes • The terms earth and earthing also refer to Appendix A for a complete set of operating information including specifications. • Selective measurements are described in the main section of this manual. • For stakeless earth resistance measurements, the EI-1625 must be purchased. (The EI-1625 comes standard with the 1625... Kit). Figure 1 displays the Fluke 1625 Earth/Ground Tester: START TEST 1625 EARTH / ...
FE 1625 Users Manual
Page 11
...) Spilt Core Transformer 2-3 Wire Adapter Cable for 1625 for EI162AC Current Transformer Earth Stake Cable Reel w/25m Wire Cable Reel w/50m Wire 1625 Users Manual Item/Part Number Fluke-1625 Fluke-1625 Kit Fluke-162x-7001 ES-162P3 ES-162P4 EI-1625 EI-162X 2539195 EI-162AC EI-162BN 2577171 2539121... 2539100 2539117 2560348 3 Basic (Includes manual, 2 leads and 2 clips) Earth Ground Tester -...
...) Spilt Core Transformer 2-3 Wire Adapter Cable for 1625 for EI162AC Current Transformer Earth Stake Cable Reel w/25m Wire Cable Reel w/50m Wire 1625 Users Manual Item/Part Number Fluke-1625 Fluke-1625 Kit Fluke-162x-7001 ES-162P3 ES-162P4 EI-1625 EI-162X 2539195 EI-162AC EI-162BN 2577171 2539121... 2539100 2539117 2560348 3 Basic (Includes manual, 2 leads and 2 clips) Earth Ground Tester -...
FE 1625 Users Manual
Page 12
... operation is only to be switched off immediately and protected against accidental restarting. Fault-free and reliable operation of such equipment to carry dangerous voltage. 1625 Users Manual Safety Instructions W Warning This measuring equipment is no longer possible if and when the instrument • shows visible damage, • fails to work in spite...
... operation is only to be switched off immediately and protected against accidental restarting. Fault-free and reliable operation of such equipment to carry dangerous voltage. 1625 Users Manual Safety Instructions W Warning This measuring equipment is no longer possible if and when the instrument • shows visible damage, • fails to work in spite...
FE 1625 Users Manual
Page 14
... Hz) switched on current transformer for use as a simple meter as well as a high end fully automated measuring device. 1625 Users Manual General Microprocessor controlled universal earth resistance meter with fully automated measuring frequency selection process as well as automatic testing of earthing resistance ...and customer defined special functions, e.g. and auxiliary earth electrode resistances and possible interference voltages as an option and enables the user to measure on high voltage pylons without seperating the overhead earth wires or earth strips at the bottom of the pylons...
... Hz) switched on current transformer for use as a simple meter as well as a high end fully automated measuring device. 1625 Users Manual General Microprocessor controlled universal earth resistance meter with fully automated measuring frequency selection process as well as automatic testing of earthing resistance ...and customer defined special functions, e.g. and auxiliary earth electrode resistances and possible interference voltages as an option and enables the user to measure on high voltage pylons without seperating the overhead earth wires or earth strips at the bottom of the pylons...
FE 1625 Users Manual
Page 16
... will be started. values). Description of Functions edw003.eps Measurement of Interference Frequency (FST) For interference voltage >1 V its frequency is derived from the period time. 8 1625 Users Manual EXT H S ES E Switching Voltage measurement Current measurement Source Undervoltage detection Supply voltage ADC Comp Processor LCD driver Display Relais driver Rotary selector switch buttons Figure 2.
... will be started. values). Description of Functions edw003.eps Measurement of Interference Frequency (FST) For interference voltage >1 V its frequency is derived from the period time. 8 1625 Users Manual EXT H S ES E Switching Voltage measurement Current measurement Source Undervoltage detection Supply voltage ADC Comp Processor LCD driver Display Relais driver Rotary selector switch buttons Figure 2.
FE 1625 Users Manual
Page 18
Specifications General: Microprocessor controlled, fully automated earth measuring instrument with supplementary signs and active illumination. Display edw004.eps 10 1625 Users Manual LO-BAT Supervision of its specified value is done with a comparator circuit. and 4-pole with / without clip-on the display with AC, 2- and 4-pole with ...
Specifications General: Microprocessor controlled, fully automated earth measuring instrument with supplementary signs and active illumination. Display edw004.eps 10 1625 Users Manual LO-BAT Supervision of its specified value is done with a comparator circuit. and 4-pole with / without clip-on the display with AC, 2- and 4-pole with ...
FE 1625 Users Manual
Page 20
accessories and batteries in any combination, max. 1625 Users Manual Max voltage: EMC (Emission Immunity): Quality standard: External field influence: Auxiliary power: Battery life span: Dimensions: Weight: Case material: Wsocket A to socket EFGH Urms = 0 V Sockets " E ...
accessories and batteries in any combination, max. 1625 Users Manual Max voltage: EMC (Emission Immunity): Quality standard: External field influence: Auxiliary power: Battery life span: Dimensions: Weight: Case material: Wsocket A to socket EFGH Urms = 0 V Sockets " E ...
FE 1625 Users Manual
Page 22
A tions Part 5, 6.1 R Position Reference posi- E1 tion ± 90° Part 1, 4.2 R Supply volt- 1625 Users Manual Table 2. age Part 5, 4.3 T Operating Part 5, 4.3 R error B = ±( A + 1,15 E12 E22 E32 E 2 4 E52 E62 E72 E82 14 See 4.2 and 4.3 E4 ference voltage Part 5, 4.2, T 4.3 Resistance 0 to 110 % ...
A tions Part 5, 6.1 R Position Reference posi- E1 tion ± 90° Part 1, 4.2 R Supply volt- 1625 Users Manual Table 2. age Part 5, 4.3 T Operating Part 5, 4.3 R error B = ±( A + 1,15 E12 E22 E32 E 2 4 E52 E62 E72 E82 14 See 4.2 and 4.3 E4 ference voltage Part 5, 4.2, T 4.3 Resistance 0 to 110 % ...
FE 1625 Users Manual
Page 24
F 1000% 100% 10% 1 % 3000 1000 RH/RE= 300 100 30 10 3 1 0,3 0 ,1% 1 0 100 1 k 10k 100k 1M RS edw005.eps Automatic switchover of measuring resolution in dependence to auxiliary earth electrode resistance RH: RH with Umeas = 48 V < 300 Ω < 6 kΩ < 60 kΩ < 600 kΩ RH with Umeas = 20 V < 250 Ω < 2,5 kΩ < 25 kΩ < 250 kΩ Resolution 1 mΩ 10 mΩ 100 mΩ 1 Ω 16 1625 Users Manual fluencing conditions (see diagramm), the display shows a warning symbol W and a notice that RS or RH are too high.
F 1000% 100% 10% 1 % 3000 1000 RH/RE= 300 100 30 10 3 1 0,3 0 ,1% 1 0 100 1 k 10k 100k 1M RS edw005.eps Automatic switchover of measuring resolution in dependence to auxiliary earth electrode resistance RH: RH with Umeas = 48 V < 300 Ω < 6 kΩ < 60 kΩ < 600 kΩ RH with Umeas = 20 V < 250 Ω < 2,5 kΩ < 25 kΩ < 250 kΩ Resolution 1 mΩ 10 mΩ 100 mΩ 1 Ω 16 1625 Users Manual fluencing conditions (see diagramm), the display shows a warning symbol W and a notice that RS or RH are too high.
FE 1625 Users Manual
Page 26
... A through transformer: with transformer (1000:1) with transformer (200:1) with higher voltages measurement will not be measured: 0.1 mA Max. 1625 Users Manual Minimal current in single 0.5 mA branch to be started Urms max. = 250 V 18 of m.v. interference voltage: Max overload: typ...and voltage measurement Measuring voltage: 20 V AC, square pulse Short circuit current: > 250 mA AC Measuring frequency: 94, 105, 111, 128 Hz selected manually or automatically (AFC) Measuring Range 0.020 Ω... 300 kΩ Display Range Resolution 0.001 Ω ... 2.999 Ω 3.0 Ω ... ...
... A through transformer: with transformer (1000:1) with transformer (200:1) with higher voltages measurement will not be measured: 0.1 mA Max. 1625 Users Manual Minimal current in single 0.5 mA branch to be started Urms max. = 250 V 18 of m.v. interference voltage: Max overload: typ...and voltage measurement Measuring voltage: 20 V AC, square pulse Short circuit current: > 250 mA AC Measuring frequency: 94, 105, 111, 128 Hz selected manually or automatically (AFC) Measuring Range 0.020 Ω... 300 kΩ Display Range Resolution 0.001 Ω ... 2.999 Ω 3.0 Ω ... ...
FE 1625 Users Manual
Page 28
1625 Users Manual Compensation of Lead Resistance (RK) Compensation of lead resistance (RK) can be switched on in functions RE 3pole, RE 4pole A, R~ , and R F 2pole Formation of measuring adjustment. 20 Rcompensated* * Value of setpoint entry RK = 0.000Ω, variable from 0.000...29.99 Ω by means of measured value: Rdisplay = Rmeasured -
1625 Users Manual Compensation of Lead Resistance (RK) Compensation of lead resistance (RK) can be switched on in functions RE 3pole, RE 4pole A, R~ , and R F 2pole Formation of measuring adjustment. 20 Rcompensated* * Value of setpoint entry RK = 0.000Ω, variable from 0.000...29.99 Ω by means of measured value: Rdisplay = Rmeasured -
FE 1625 Users Manual
Page 30
1625 Users Manual D "CHANGE ITEM" button to be changed. E "SELECT" button to select the digit to change the set point entry values. M Screws to sockets EFGH. I Connecting socket ...
1625 Users Manual D "CHANGE ITEM" button to be changed. E "SELECT" button to select the digit to change the set point entry values. M Screws to sockets EFGH. I Connecting socket ...
FE 1625 Users Manual
Page 32
.... Procedure of the device observe the following points: 24 For optimum performance and utilization of Measurements W Warning Use the instrument on voltage free systems only. 1. 1625 Users Manual R ~ R* AFC TEST LIMIT > LIMIT EFGH B } LO-BAT REMOTE C AC-
.... Procedure of the device observe the following points: 24 For optimum performance and utilization of Measurements W Warning Use the instrument on voltage free systems only. 1. 1625 Users Manual R ~ R* AFC TEST LIMIT > LIMIT EFGH B } LO-BAT REMOTE C AC-
FE 1625 Users Manual
Page 34
Operation The measuring functions have two initial operational modes: the Control loop and the Measuring loop (see Figure 6). 26 The instrument is switched on again by " and, together with the instrument, is switched off with ON/OFF on sequence the display illumination is activated. Illumination fades away automatically if the instrument is switched to"Stand by pressing any button. 1625 Users Manual e) Activation of display illumination By keeping the "CHANGE ITEM" button pressed during the switch on the central rotary switch exclusively.
Operation The measuring functions have two initial operational modes: the Control loop and the Measuring loop (see Figure 6). 26 The instrument is switched on again by " and, together with the instrument, is switched off with ON/OFF on sequence the display illumination is activated. Illumination fades away automatically if the instrument is switched to"Stand by pressing any button. 1625 Users Manual e) Activation of display illumination By keeping the "CHANGE ITEM" button pressed during the switch on the central rotary switch exclusively.
FE 1625 Users Manual
Page 36
... and changed . Pushing the "CHANGE ITEM" button the instrument either switches between the different set values or increases the decimal point selected with "SELECT" by 1. 1625 Users Manual Control Loop After turning the function rotary switch, the voltage display mode is activated with CODE only if activated with CODE display only display only...
... and changed . Pushing the "CHANGE ITEM" button the instrument either switches between the different set values or increases the decimal point selected with "SELECT" by 1. 1625 Users Manual Control Loop After turning the function rotary switch, the voltage display mode is activated with CODE only if activated with CODE display only display only...