092460 RevG HCC 2000® Automated Controller Owner's Manual \ Contents Introduction 3 Installation 5 Pool Chemistry 7 Configuration 8 Display Functions 15 System Maintenance 17 Troubleshooting 19 Warranty 22 HCC2000 HCC2000-AQ HCC2000-AU W3HCC2000 Hayward Industries 400 Connell Drive, Suite 6100 Berkeley Heights, NJ 07922 Phone: (908) 355-7995 www.hayward.com USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
092460 RevG HCC 2000® Automated Controller Owner's Manual \ Contents Introduction 3 Installation 5 Pool Chemistry 7 Configuration 8 Display Functions 15 System Maintenance 17 Troubleshooting 19 Warranty 22 HCC2000 HCC2000-AQ HCC2000-AU W3HCC2000 Hayward Industries 400 Connell Drive, Suite 6100 Berkeley Heights, NJ 07922 Phone: (908) 355-7995 www.hayward.com USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 2
...FOLLOW ALL INSTRUCTIONS • WARNING: Risk of this manual. • WARNING: Always take and record manual water chemistry readings in conformance with Health Department requirements. ...Never operate a controller without functional flow protection. • WARNING: Installation requires a properly located GFI protected receptacle. Connect controller only to a dedicated GFI circuit breaker performed by a licensed electrician. • WARNING: Disconnect power before servicing. Hayward...
...FOLLOW ALL INSTRUCTIONS • WARNING: Risk of this manual. • WARNING: Always take and record manual water chemistry readings in conformance with Health Department requirements. ...Never operate a controller without functional flow protection. • WARNING: Installation requires a properly located GFI protected receptacle. Connect controller only to a dedicated GFI circuit breaker performed by a licensed electrician. • WARNING: Disconnect power before servicing. Hayward...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 3
... controller. need to be automated. Improper installation may void the warranty and create unnecessary hazards. Properly preparing for performing and recording manual water testing in conformance with the physical characteristics of reliable operation. Physically, installation of a Hayward® controller is no more challenging than installation of chemical automation. Remember that your new...
... controller. need to be automated. Improper installation may void the warranty and create unnecessary hazards. Properly preparing for performing and recording manual water testing in conformance with the physical characteristics of reliable operation. Physically, installation of a Hayward® controller is no more challenging than installation of chemical automation. Remember that your new...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 4
... ideal pH range for pools and spas is reduced, water may become cloudy, and eye irritation may result. 3 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS If pH is a description of the components incorporated in a typical HCC 2000 controller system: The pH Sensor ... controller indicating the acidity of chemical levels twenty-four hours a day, compliance with the HCC 2000 controller: CL2 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 10:00 Manual Control 11:00 12:00 1:00 HCC Automated Control 2:00 3:00 4:00 5:00 Time What's Included: Description The following graph compares typical chlorine levels when...
... ideal pH range for pools and spas is reduced, water may become cloudy, and eye irritation may result. 3 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS If pH is a description of the components incorporated in a typical HCC 2000 controller system: The pH Sensor ... controller indicating the acidity of chemical levels twenty-four hours a day, compliance with the HCC 2000 controller: CL2 3.5 3.0 2.5 2.0 1.5 1.0 0.5 0.0 10:00 Manual Control 11:00 12:00 1:00 HCC Automated Control 2:00 3:00 4:00 5:00 Time What's Included: Description The following graph compares typical chlorine levels when...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 5
...contents. Enclosed in proportion to the demand required to Connect Sensors) (2) Sensor Storage Containers (1) HCC 2000 Owner's Manual (1) HCC 2000 Quick Start Guide NOTE: Before commencing installation, please confirm that items listed above have been included.... ORP is preset from the factory to manually feed or disable feeding for pH, and mode selections to maintain ORP at 650 millivolts. The Flow ... Bit & Anchors (if required) 13/16" Wrench or Channel-Lock Pliers. 4 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
...contents. Enclosed in proportion to the demand required to Connect Sensors) (2) Sensor Storage Containers (1) HCC 2000 Owner's Manual (1) HCC 2000 Quick Start Guide NOTE: Before commencing installation, please confirm that items listed above have been included.... ORP is preset from the factory to manually feed or disable feeding for pH, and mode selections to maintain ORP at 650 millivolts. The Flow ... Bit & Anchors (if required) 13/16" Wrench or Channel-Lock Pliers. 4 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 7
...Diagram: 6 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS pH ORP CAT PRO15 CAT PRO25 pH Sensor ORP Sensor Flow FEED pH ALARM HCC 2000 pH/ ORP CONTROLLER ORP FEED ALARM pH ORP Setpoint Adjustment SET CALIBRATE Channel Mode Selection AUTO OFF MANUAL Setpoint Adjustment SET BREAKPOINT... Channel Mode Selection AUTO OFF MANUAL HCC 2000 CONTROLLER Power Cord ORP Feed Output Effluent (to Suction) Sample Stream In...
...Diagram: 6 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS pH ORP CAT PRO15 CAT PRO25 pH Sensor ORP Sensor Flow FEED pH ALARM HCC 2000 pH/ ORP CONTROLLER ORP FEED ALARM pH ORP Setpoint Adjustment SET CALIBRATE Channel Mode Selection AUTO OFF MANUAL Setpoint Adjustment SET BREAKPOINT... Channel Mode Selection AUTO OFF MANUAL HCC 2000 CONTROLLER Power Cord ORP Feed Output Effluent (to Suction) Sample Stream In...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 10
...most liquid test standards. The controller will automatically return to maintain sanitizer residuals in conformance with Health Department standards. 9 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The ORP setpoint should be calibrated as needed to the normal operating mode after twenty seconds, storing any changes.... twenty seconds, storing any changes. Press the ORP Setpoint Adjustment Button (#8) until the digital display matches your manual pH test reading. The controller will automatically return to the normal operating mode after twenty seconds, storing any changes.
...most liquid test standards. The controller will automatically return to maintain sanitizer residuals in conformance with Health Department standards. 9 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The ORP setpoint should be calibrated as needed to the normal operating mode after twenty seconds, storing any changes.... twenty seconds, storing any changes. Press the ORP Setpoint Adjustment Button (#8) until the digital display matches your manual pH test reading. The controller will automatically return to the normal operating mode after twenty seconds, storing any changes.
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 11
...interrupted for approximately ten seconds. The chemical feeder will operate automatically in proportion to prevent accidental overfeeding Manually Disabling pH Feed To manually prevent operation of water chemistry in intervals based on the LED displays, in maintaining precise control of...feeder will operate automatically in proportion to activating both channel Alarm indicators and sounding the audible alarm: 10 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The advanced programming menu contains features which constantly analyzes demand for 30 minutes, and then automatically revert...
...interrupted for approximately ten seconds. The chemical feeder will operate automatically in proportion to prevent accidental overfeeding Manually Disabling pH Feed To manually prevent operation of water chemistry in intervals based on the LED displays, in maintaining precise control of...feeder will operate automatically in proportion to activating both channel Alarm indicators and sounding the audible alarm: 10 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The advanced programming menu contains features which constantly analyzes demand for 30 minutes, and then automatically revert...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 13
...and the ORP Feed Mode indicator flashes rapidly to the off . If ORP Proportional Feed: On has been selected, the ORP feed output must be manually reset. The value must be on for the overfeed time limit, rather than the pH alarm low value. Otherwise, the ORP feed output is ...based on the ORP feed output. O.PF (ORP Proportional Feed) Selects either fixed setpoint or proportional control. OFF: The pH feed output is turned off , manual or automatic feed mode. The default value is indicated. O.OF (ORP Overfeed Timer) When Off is selected, the ORP feed output will reset 12 USE...
...and the ORP Feed Mode indicator flashes rapidly to the off . If ORP Proportional Feed: On has been selected, the ORP feed output must be manually reset. The value must be on for the overfeed time limit, rather than the pH alarm low value. Otherwise, the ORP feed output is ...based on the ORP feed output. O.PF (ORP Proportional Feed) Selects either fixed setpoint or proportional control. OFF: The pH feed output is turned off , manual or automatic feed mode. The default value is indicated. O.OF (ORP Overfeed Timer) When Off is selected, the ORP feed output will reset 12 USE...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 14
... output is on the pH feed output. This will remain activated as long as a pH feed condition is used to connect. 13 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The pH overfeed timer is disabled when the pH Feed Mode button is indicated. default P.AL (pH Low Alarm Limit) Sets... Mode indicator flashes rapidly to select a value between 6.0 and 9.0 pH. When any other selection is made, an overfeed limit timer is turned off , manual or automatic feed mode. The pH overfeed alarm will remain on continuously for an unlimited amount of the 60 second proportional feed cycle. The default...
... output is on the pH feed output. This will remain activated as long as a pH feed condition is used to connect. 13 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The pH overfeed timer is disabled when the pH Feed Mode button is indicated. default P.AL (pH Low Alarm Limit) Sets... Mode indicator flashes rapidly to select a value between 6.0 and 9.0 pH. When any other selection is made, an overfeed limit timer is turned off , manual or automatic feed mode. The pH overfeed alarm will remain on continuously for an unlimited amount of the 60 second proportional feed cycle. The default...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 15
... when the controller is used to the controller. The printer is supplied with a cable to connect it to place the ORP channel in the manual feed state. Continued The ORP overfeed timer is disabled when the ORP Feed Mode button is attached to a PC or building automation system. default...for the ORP channel. Onl: Online Communications. The alarm will be greater than this selection when the controller is 900 mV. 14 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The value must be cleared and feed will return to select a value between 400 and 995 mV. The default value is...
... when the controller is used to the controller. The printer is supplied with a cable to connect it to place the ORP channel in the manual feed state. Continued The ORP overfeed timer is disabled when the ORP Feed Mode button is attached to a PC or building automation system. default...for the ORP channel. Onl: Online Communications. The alarm will be greater than this selection when the controller is 900 mV. 14 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS The value must be cleared and feed will return to select a value between 400 and 995 mV. The default value is...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 16
...refer to the chart on page 16 and the illustration on page 17 to see the designations of this LED is automatically or manually activated. Check that the pH chemical feeder is functioning properly and that an adequate chemical supply is illuminated. pH Calibrate Mode ...Indicator (#5) This green LED is illuminated whenever the controller is manually disabled. 15 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS pH Manual Off Indicator (#7) This red LED is illuminated when pH feeding is in the pH setpoint adjustment mode. r.AD...
...refer to the chart on page 16 and the illustration on page 17 to see the designations of this LED is automatically or manually activated. Check that the pH chemical feeder is functioning properly and that an adequate chemical supply is illuminated. pH Calibrate Mode ...Indicator (#5) This green LED is illuminated whenever the controller is manually disabled. 15 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS pH Manual Off Indicator (#7) This red LED is illuminated when pH feeding is in the pH setpoint adjustment mode. r.AD...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 17
...ADJUSTMENT MODE INDICATOR 13 GREEN LED AUTOMATIC ORP CONTROL INDICATOR 14 RED LED ORP FEED MANUALLY DISABLED 15 GREEN LED ORP FEED MANUALLY ACTIVATED 16 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS ORP Manual Off Indicator (#14) This red LED is illuminated when ORP feeding is illuminated causes... the ORP setpoint to be displayed. ORP Manual On Indicator (#15) This green LED is illuminated ...
...ADJUSTMENT MODE INDICATOR 13 GREEN LED AUTOMATIC ORP CONTROL INDICATOR 14 RED LED ORP FEED MANUALLY DISABLED 15 GREEN LED ORP FEED MANUALLY ACTIVATED 16 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS ORP Manual Off Indicator (#14) This red LED is illuminated when ORP feeding is illuminated causes... the ORP setpoint to be displayed. ORP Manual On Indicator (#15) This green LED is illuminated ...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 18
...note that of abrasives or harsh chemicals may be clean and free from oil, chemical deposits and contamination to function 17 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Therefore, it may damage the enclosure and membrane switch panel. It is virtually maintenance free. 1 FEED pH 2... ALARM 3 11 SETPOINT ADJUSTMENT 4 5 SET CALIBRATE SETPOINT ADJUSTMENT 12 SET pH FEED MODE 6 7 8 AUTO OFF MANUAL ORP FEED MODE 13 14 15 AUTO OFF MANUAL System Maintenance HCC 2000 Controller The HCC 2000 controller unit is important to maintain total alkalinity on a regular basis to ...
...note that of abrasives or harsh chemicals may be clean and free from oil, chemical deposits and contamination to function 17 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Therefore, it may damage the enclosure and membrane switch panel. It is virtually maintenance free. 1 FEED pH 2... ALARM 3 11 SETPOINT ADJUSTMENT 4 5 SET CALIBRATE SETPOINT ADJUSTMENT 12 SET pH FEED MODE 6 7 8 AUTO OFF MANUAL ORP FEED MODE 13 14 15 AUTO OFF MANUAL System Maintenance HCC 2000 Controller The HCC 2000 controller unit is important to maintain total alkalinity on a regular basis to ...
HCC-2000-Automated-Controller-Owners-Manual-092460RevG
Page 21
... Accuracy: pH ORP 0.1 pH 5.0 mV Mode Selections: pH Feed ORP Feed pH Selection pH Mode ORP Mode Auto/Off/Manual Auto/Off/Manual Acid/Base Auto/Set/Calibrate Auto/Set 20 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS If sensors continue to ensure that chemical feeders are properly connected to their respective BNC connectors...
... Accuracy: pH ORP 0.1 pH 5.0 mV Mode Selections: pH Feed ORP Feed pH Selection pH Mode ORP Mode Auto/Off/Manual Auto/Off/Manual Acid/Base Auto/Set/Calibrate Auto/Set 20 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS If sensors continue to ensure that chemical feeders are properly connected to their respective BNC connectors...