Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 1
... ™ Rack/Tower Mount On-Line UPS Systems Not suitable for mobile applications. All rights reserved. SmartOnline™ is a trademark of Tripp Lite. Important Safety Instructions 2 Installation 3 Basic Operation 8 Troubleshooting 12 Battery Replacement 13 Storage and Service 14 Warranty Registration 15 Español 16 Français 31 1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite...
... ™ Rack/Tower Mount On-Line UPS Systems Not suitable for mobile applications. All rights reserved. SmartOnline™ is a trademark of Tripp Lite. Important Safety Instructions 2 Installation 3 Basic Operation 8 Troubleshooting 12 Battery Replacement 13 Storage and Service 14 Warranty Registration 15 Español 16 Français 31 1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 2
...support applications where failure of this equipment in the presence of your UPS to an outlet. • If the UPS receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade output. Battery Warnings • Batteries can reasonably be voided if anything other than Tripp Lite surge suppressors are no user-serviceable parts... space around all Tripp Lite UPS Systems. Failure to locate the specific replacement battery for proper ventilation. • Do not mount unit with any angle). UPS Location Warnings • Install your UPS. 2...
...support applications where failure of this equipment in the presence of your UPS to an outlet. • If the UPS receives power from a motor-powered AC generator, the generator must provide clean, filtered, computer-grade output. Battery Warnings • Batteries can reasonably be voided if anything other than Tripp Lite surge suppressors are no user-serviceable parts... space around all Tripp Lite UPS Systems. Failure to locate the specific replacement battery for proper ventilation. • Do not mount unit with any angle). UPS Location Warnings • Install your UPS. 2...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 3
... . Note that the support ledges should E face forward. 4 Using an assistant if necessary, lift your UPS model does not include an adjustable... rackmount shelf kit, skip steps 1 and 2. 1 Connect the two segments of each shelf to fit your rack, then mount them in the lowest available space of your rack with the screws, nuts and washers provided C . The user... models include hardware required to mount in the next step. If your equipment and slide it onto the mounting shelves. Installation ...manual are not suitable for 2-post mounting).
... . Note that the support ledges should E face forward. 4 Using an assistant if necessary, lift your UPS model does not include an adjustable... rackmount shelf kit, skip steps 1 and 2. 1 Connect the two segments of each shelf to fit your rack, then mount them in the lowest available space of your rack with the screws, nuts and washers provided C . The user... models include hardware required to mount in the next step. If your equipment and slide it onto the mounting shelves. Installation ...manual are not suitable for 2-post mounting).
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 4
...! The "LINE" and "LOAD ACTIVE METER" LEDs will illuminate and the UPS will overload your UPS if you mount 2U UPS models in , the fan and all Indicator Lights will turn ON. Use caution when lifting and mounting. Note...power is not supplied to your UPS's AC outlets until the UPS is designed to support computer equipment only. All UPS systems are extremely heavy. User must be connected to indicate normal operation. See Installation Kit owner's manual for installation procedure for 2U UPS models. Refer to the "OP Rating/Plug Rating" chart printed on either side of a Tripp Lite...
...! The "LINE" and "LOAD ACTIVE METER" LEDs will illuminate and the UPS will overload your UPS if you mount 2U UPS models in , the fan and all Indicator Lights will turn ON. Use caution when lifting and mounting. Note...power is not supplied to your UPS's AC outlets until the UPS is designed to support computer equipment only. All UPS systems are extremely heavy. User must be connected to indicate normal operation. See Installation Kit owner's manual for installation procedure for 2U UPS models. Refer to the "OP Rating/Plug Rating" chart printed on either side of a Tripp Lite...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 5
... your UPS. Installation 3 Turn your UPS ON: • Press the "ON/TEST" Button • Hold it for several seconds until you connect to the UPS's jacks is also protected against surges on your computer the Tripp Lite PowerAlert Software appropriate to the communication port of your computer to your computer's operating system. Select models feature jacks which...
... your UPS. Installation 3 Turn your UPS ON: • Press the "ON/TEST" Button • Hold it for several seconds until you connect to the UPS's jacks is also protected against surges on your computer the Tripp Lite PowerAlert Software appropriate to the communication port of your computer to your computer's operating system. Select models feature jacks which...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 6
...1 second. Remove AC line power to a latching EPO switch. UPS Unit State when asserting EPO without AC line power: LEDs Output Fans Serial SNMP USB OFF OFF OFF OFF OFF OFF...diagram (see 3a ) to a user-supplied 3a Your model may differ. This does not apply to the UPS unit. 3. UPS Unit State when asserting EPO with AC line present: LEDs Output Fans Serial SNMP USB...operation mode. Option 2: 1. Now the UPS will turn back on. Installation 3 EPO Port Connection This optional feature is only for a minimum of the UPS's inverter and inhibits transfer to internal bypass....
...1 second. Remove AC line power to a latching EPO switch. UPS Unit State when asserting EPO without AC line power: LEDs Output Fans Serial SNMP USB OFF OFF OFF OFF OFF OFF...diagram (see 3a ) to a user-supplied 3a Your model may differ. This does not apply to the UPS unit. 3. UPS Unit State when asserting EPO with AC line present: LEDs Output Fans Serial SNMP USB...operation mode. Option 2: 1. Now the UPS will turn back on. Installation 3 EPO Port Connection This optional feature is only for a minimum of the UPS's inverter and inhibits transfer to internal bypass....
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 7
... increase recharge time as well as runtime. select models feature connectors that accept optional external battery packs (sold separately from Tripp Lite) to ensure that the external batteries you are fully inserted into their connectors. this is running on your UPS's battery connector. See the battery pack owner's manual for complete installation instructions. Small sparks may differ. 7 201102199 93-2471.indb...
... increase recharge time as well as runtime. select models feature connectors that accept optional external battery packs (sold separately from Tripp Lite) to ensure that the external batteries you are fully inserted into their connectors. this is running on your UPS's battery connector. See the battery pack owner's manual for complete installation instructions. Small sparks may differ. 7 201102199 93-2471.indb...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 8
...release it . "OFF" Button: This button turns power OFF at an extremely high voltage, and the UPS will flash if the line voltage is nominal. The UPS will shift to battery power (all LEDs will illuminate. Alarm Silence To silence the UPS "on-battery" alarm, press this button, hold it until you ... required on the "LOAD ACTIVE METER" LEDs. No action is performing normal on -line operation, press this light is off . the UPS continuously and automatically filters AC line power to provide pure sine wave output). UPS Self-Test During normal on -line operation (filtering ...
...release it . "OFF" Button: This button turns power OFF at an extremely high voltage, and the UPS will flash if the line voltage is nominal. The UPS will shift to battery power (all LEDs will illuminate. Alarm Silence To silence the UPS "on-battery" alarm, press this button, hold it until you ... required on the "LOAD ACTIVE METER" LEDs. No action is performing normal on -line operation, press this light is off . the UPS continuously and automatically filters AC line power to provide pure sine wave output). UPS Self-Test During normal on -line operation (filtering ...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 9
... UPS is operating from on how to access the Economy Mode, please refer to the PowerAlert software User's Manual) "FAULT" LED (select models only): This red light will flash when your UPS detects an internal fault (overheating, overvoltages, etc.) or when it configures an online UPS to check the AC line. During normal operation this case, contact Tripp Lite for service.
... UPS is operating from on how to access the Economy Mode, please refer to the PowerAlert software User's Manual) "FAULT" LED (select models only): This red light will flash when your UPS detects an internal fault (overheating, overvoltages, etc.) or when it configures an online UPS to check the AC line. During normal operation this case, contact Tripp Lite for service.
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 10
... the appropriate Tripp Lite battery pack to reset. Ground Screw: Use this breaker trips, make sure your UPS is connected to instructions available with the Battery Pack for service. Refer to AC power of the load on when line power is less than fully charged. Basic Operation Rear Panel "REPLACE BATT" LED: This red light will illuminate constantly and the UPS alarm will...
... the appropriate Tripp Lite battery pack to reset. Ground Screw: Use this breaker trips, make sure your UPS is connected to instructions available with the Battery Pack for service. Refer to AC power of the load on when line power is less than fully charged. Basic Operation Rear Panel "REPLACE BATT" LED: This red light will illuminate constantly and the UPS alarm will...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 11
... two may be individually turned off and on the unit. If the UPS battery is optional. Connecting your PowerAlert Software manual or contact Tripp Lite Customer Support for installation instructions. The DB9 port's pin assignments are simple, but some knowledge of AC line power and UPS operating conditions. Basic Operation NEMA 5-15R AC Receptacles (Varied by Model): These 15-, 20- EPO...
... two may be individually turned off and on the unit. If the UPS battery is optional. Connecting your PowerAlert Software manual or contact Tripp Lite Customer Support for installation instructions. The DB9 port's pin assignments are simple, but some knowledge of AC line power and UPS operating conditions. Basic Operation NEMA 5-15R AC Receptacles (Varied by Model): These 15-, 20- EPO...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 12
... turn on , contact Tripp Lite for repairs. If the problem persists, contact Tripp Lite for repairs. Troubleshooting The UPS's control panel lights will deliver no output. On: BYPASS, LINE, LOAD, OVERLOAD Reduce the load the UPS supports. On: FAULT, 100% Condition: Battery Voltage too High Restart the UPS. If the problem persists, contact Tripp Lite for at least 12 hours and perform a self test using the "ON/Test...
... turn on , contact Tripp Lite for repairs. If the problem persists, contact Tripp Lite for repairs. Troubleshooting The UPS's control panel lights will deliver no output. On: BYPASS, LINE, LOAD, OVERLOAD Reduce the load the UPS supports. On: FAULT, 100% Condition: Battery Voltage too High Restart the UPS. If the problem persists, contact Tripp Lite for at least 12 hours and perform a self test using the "ON/Test...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 13
If the problem persists, contact Tripp Lite for air to be performed only by qualified service personnel. Check the UPS to circulate near the vents and that the fan is working properly. Should your UPS require battery replacement, visit Tripp Lite on the Web at 1 6 www.tripplite.com/support/battery/index.cfm to "Battery Warnings" in your UPS. Troubleshooting Lights (On/Flashing) and Condition...
If the problem persists, contact Tripp Lite for air to be performed only by qualified service personnel. Check the UPS to circulate near the vents and that the fan is working properly. Should your UPS require battery replacement, visit Tripp Lite on the Web at 1 6 www.tripplite.com/support/battery/index.cfm to "Battery Warnings" in your UPS. Troubleshooting Lights (On/Flashing) and Condition...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 14
... address given to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. For more information on storing your unit's model and serial numbers, along with other general purchaser information. If the problem requires service, visit www.tripplite.com/support and click the Product Returns link. The RMA number, along with shipping instructions will ask for...
... address given to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. For more information on storing your unit's model and serial numbers, along with other general purchaser information. If the problem requires service, visit www.tripplite.com/support and click the Product Returns link. The RMA number, along with shipping instructions will ask for...
Owner's Manual for SmartOnline Rack/Tower UPS 932471
Page 15
... continuous improvement. See website for repair/warranty information. When requesting compliance information for information.) The policy of Tripp Lite is one of the product. The series number should not be automatically entered into a drawing for Models with FCC Class A Approval: This device complies with the instruction manual, may cause undesired operation. FCC Specifications for a chance to the...
... continuous improvement. See website for repair/warranty information. When requesting compliance information for information.) The policy of Tripp Lite is one of the product. The series number should not be automatically entered into a drawing for Models with FCC Class A Approval: This device complies with the instruction manual, may cause undesired operation. FCC Specifications for a chance to the...
Runtime Chart for UPS Model SU2200RTXL2Ua
Page 1
SU2200RTXL2UA Estimated Runtime UPS SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua Battery Pack Included Batteries BP48V24-2U BP48V24-2U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP Qty. 0 1 2 1 2 3 4 5 6 7 8 9 10 300W 44 168 301 331 648 960 1267 ...
SU2200RTXL2UA Estimated Runtime UPS SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua SU2200RTXL2Ua Battery Pack Included Batteries BP48V24-2U BP48V24-2U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP48V60RT3U BP Qty. 0 1 2 1 2 3 4 5 6 7 8 9 10 300W 44 168 301 331 648 960 1267 ...