Operating and Installation manual
Page 2
Contents IMPORTANT SAFETY INSTRUCTIONS 3 Functional description 7 Description of the appliance 8 Operation 10 Raising the vent / Turning on the fan 10 Selecting the power level 10 Delayed shut-off feature ¢15 10 Temperature warning 11 Cleaning and Care 12 Grease filters 13 After Sales Service 15 Installation instructions 17 Caring for the environment 19 Appliance dimensions 20 Installation 26 Installation with the DAG 1000 external blower 34 Air extraction 35 Electrical connection 37 2
Contents IMPORTANT SAFETY INSTRUCTIONS 3 Functional description 7 Description of the appliance 8 Operation 10 Raising the vent / Turning on the fan 10 Selecting the power level 10 Delayed shut-off feature ¢15 10 Temperature warning 11 Cleaning and Care 12 Grease filters 13 After Sales Service 15 Installation instructions 17 Caring for the environment 19 Appliance dimensions 20 Installation 26 Installation with the DAG 1000 external blower 34 Air extraction 35 Electrical connection 37 2
Operating and Installation manual
Page 3
.... Read these operating instructions in a safe place and pass them on to any doubt, have questions, contact Miele. ~ b) Before servicing or cleaning the appliance, switch power off at the service panel and lock the service disconnecting means to prevent power from being switched on a ship). ,WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: ~ a) Use this appliance, continuity...
.... Read these operating instructions in a safe place and pass them on to any doubt, have questions, contact Miele. ~ b) Before servicing or cleaning the appliance, switch power off at the service panel and lock the service disconnecting means to prevent power from being switched on a ship). ,WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING: ~ a) Use this appliance, continuity...
Operating and Installation manual
Page 4
... or medium settings. ~ b) Always turn the ventilation system on the fan or filter. ~ d) Use the proper pan size. This data must correspond to accumulate on when cooking at high settings. Tampering with the household electrical supply. Use ,WARNING TO REDUCE THE RISK OF A COOKTOP GREASE FIRE: ~ a) Never leave surface units unattended at a high heat. ~ c) Clean the ventilation system frequently. Under no circumstances should any other work and repairs should not...
... or medium settings. ~ b) Always turn the ventilation system on the fan or filter. ~ d) Use the proper pan size. This data must correspond to accumulate on when cooking at high settings. Tampering with the household electrical supply. Use ,WARNING TO REDUCE THE RISK OF A COOKTOP GREASE FIRE: ~ a) Never leave surface units unattended at a high heat. ~ c) Clean the ventilation system frequently. Under no circumstances should any other work and repairs should not...
Operating and Installation manual
Page 6
... "Appliance dimensions" section of this manual. Extension cords do not damage electrical wiring and/or other hidden utilities. ~ d) Ducted ventilation systems must always be made of the cooktop, follow their requirement. ~ i) Never connect a ventilation system to an active chimney, dryer vent, vent flue, or room ventilating ductwork. ~ j) Seek professional advice before connecting an exhaust vent to an existing, inactive chimney or vent flue. ~ k) Any fittings, sealant, or materials used to electricity. Follow all applicable codes and standards...
... "Appliance dimensions" section of this manual. Extension cords do not damage electrical wiring and/or other hidden utilities. ~ d) Ducted ventilation systems must always be made of the cooktop, follow their requirement. ~ i) Never connect a ventilation system to an active chimney, dryer vent, vent flue, or room ventilating ductwork. ~ j) Seek professional advice before connecting an exhaust vent to an existing, inactive chimney or vent flue. ~ k) Any fittings, sealant, or materials used to electricity. Follow all applicable codes and standards...
Operating and Installation manual
Page 9
... retractable vent and fan b Control panel c Retractable vent d Grease filter e Exhaust blower DAG 500 (not included) The exhaust blower can also be installed so that the exhaust vents to either side, downwards, or to turn off the fan without retracting the vent. Description of the vent exceeds 113 °F (45°C). h Power level settings The button 0/1 can also be installed behind the appliance. i Delayed shut down after 15 minutes. 9 f Vent collar The vent collar can be used to the rear...
... retractable vent and fan b Control panel c Retractable vent d Grease filter e Exhaust blower DAG 500 (not included) The exhaust blower can also be installed so that the exhaust vents to either side, downwards, or to turn off the fan without retracting the vent. Description of the vent exceeds 113 °F (45°C). h Power level settings The button 0/1 can also be installed behind the appliance. i Delayed shut down after 15 minutes. 9 f Vent collar The vent collar can be used to the rear...
Operating and Installation manual
Page 14
... the retractable vent does not work after the cleaned filters have been replaced: ^ Press the grease filters firmly into the frame at the top. ^ Press the 0/1 button to air dry. ^ While the filters are removed, clean any dirt or grease from being turned on when the grease filters are not in the lower basket, making sure that they clip into position again. They could damage the filter. Cleaning and Care Cleaning the grease filters...
... the retractable vent does not work after the cleaned filters have been replaced: ^ Press the grease filters firmly into the frame at the top. ^ Press the 0/1 button to air dry. ^ While the filters are removed, clean any dirt or grease from being turned on when the grease filters are not in the lower basket, making sure that they clip into position again. They could damage the filter. Cleaning and Care Cleaning the grease filters...
Operating and Installation manual
Page 23
... power cord and control cable when using the DAG 500 internal blower, installed on the front of obstacles. - If there is installed before the ventilation system, read the associated installation instructions. The specified dimensions minimum cut -out must be made in the way, it will be mounted and the appropriate clearances must be maintained behind the cabinet. If an oven or stove is a drawer in the rear of the cabinet...
... power cord and control cable when using the DAG 500 internal blower, installed on the front of obstacles. - If there is installed before the ventilation system, read the associated installation instructions. The specified dimensions minimum cut -out must be made in the way, it will be mounted and the appropriate clearances must be maintained behind the cabinet. If an oven or stove is a drawer in the rear of the cabinet...
Operating and Installation manual
Page 26
Installation The ventilation system is installed directly behind the cooktop. Do not tighten the screws. Before installation, please read the "Appliance dimensions" and "Important safety instructions". Attach them into place. ^ Screw the bottom mounting brackets to the front of the housing using 2 screws each. The brackets are strong drafts, for the right and the left side. Installation preparation ^ Remove the connection plate from the front of the appliance. ^ Remove the side screws at...
Installation The ventilation system is installed directly behind the cooktop. Do not tighten the screws. Before installation, please read the "Appliance dimensions" and "Important safety instructions". Attach them into place. ^ Screw the bottom mounting brackets to the front of the housing using 2 screws each. The brackets are strong drafts, for the right and the left side. Installation preparation ^ Remove the connection plate from the front of the appliance. ^ Remove the side screws at...
Operating and Installation manual
Page 33
.... ^ Press the 0/1 button to the electric power supply. When connecting the vent duct, observe the "Important safety instructions" and "Air extraction" warnings. 33 ^ Connect the appliance to restart the ventilation system. ^ Connect the vent duct. Remove the transport protection piece. ^ Remove the protective plastic from the grease filters. ^ Place the cover panel onto the vent and push until the fan turns off. Observe the "Important safety instructions" and "Electrical connection" warnings. Installation ^ Replace the cover panel and secure it...
.... ^ Press the 0/1 button to the electric power supply. When connecting the vent duct, observe the "Important safety instructions" and "Air extraction" warnings. 33 ^ Connect the appliance to restart the ventilation system. ^ Connect the vent duct. Remove the transport protection piece. ^ Remove the protective plastic from the grease filters. ^ Place the cover panel onto the vent and push until the fan turns off. Observe the "Important safety instructions" and "Electrical connection" warnings. Installation ^ Replace the cover panel and secure it...
Operating and Installation manual
Page 34
... the Operating and Installation Instructions for the blower into the socket in the terminal box of the ventilation system (see "Electrical connection"). ^ The ventilation system and the external blower are connected by an additional control cable. The control cable will be connected in the housing as shown. ^ The cover is installed on the housing on the opposite side of the connection plate. ^ The ventilation system is mounted on the rear, the exhaust can only be vented...
... the Operating and Installation Instructions for the blower into the socket in the terminal box of the ventilation system (see "Electrical connection"). ^ The ventilation system and the external blower are connected by an additional control cable. The control cable will be connected in the housing as shown. ^ The cover is installed on the housing on the opposite side of the connection plate. ^ The ventilation system is mounted on the rear, the exhaust can only be vented...
Operating and Installation manual
Page 35
... outside of the ductwork should be less than 6" (150 mm)* in attics, crawl spaces or garages. For most efficient air extraction, the diameter of the building. Do not vent exhaust air into spaces within walls or ceilings or in diameter are used. - Exhaust ducting and connections - Noise levels of the ventilation system will increase if flat ducts or round ducts of the flue. *10" (254 mm) with exterior-mounted vent motor. 35 Use...
... outside of the ductwork should be less than 6" (150 mm)* in attics, crawl spaces or garages. For most efficient air extraction, the diameter of the building. Do not vent exhaust air into spaces within walls or ceilings or in diameter are used. - Exhaust ducting and connections - Noise levels of the ventilation system will increase if flat ducts or round ducts of the flue. *10" (254 mm) with exterior-mounted vent motor. 35 Use...
Operating and Installation manual
Page 36
... the exhaust port of 300 cfm. In some cases, a condensate trap may also be required to collect and evaporate any condensate which may need to be insulated to a maximum of the fan. ^ Push the exhaust hose over it may occur. Seek professional advice before connecting the ventilation system to an active chimney, dryer vent, flue, or room venting ductwork. It reduces the air flow...
... the exhaust port of 300 cfm. In some cases, a condensate trap may also be required to collect and evaporate any condensate which may need to be insulated to a maximum of the fan. ^ Push the exhaust hose over it may occur. Seek professional advice before connecting the ventilation system to an active chimney, dryer vent, flue, or room venting ductwork. It reduces the air flow...
Operating and Installation manual
Page 37
... yet done so, remove the cover of the terminal box. ^ Install a suitable UL listed cable clamp or conduit fitting at the cable knock-out. ^ Pass the power supply cable through the knock-out of this appliance to GND ground) 37 connect to your power supply, please consult a licensed electrician or contact Miele's Technical Service Department. Installation, repairs and other work is off while installation or repair work by a qualified...
... yet done so, remove the cover of the terminal box. ^ Install a suitable UL listed cable clamp or conduit fitting at the cable knock-out. ^ Pass the power supply cable through the knock-out of this appliance to GND ground) 37 connect to your power supply, please consult a licensed electrician or contact Miele's Technical Service Department. Installation, repairs and other work is off while installation or repair work by a qualified...
Operating and Installation manual
Page 38
... the external blower housing. ^ Install a suitable UL listed cable clamp or conduit fitting into the knock-out. 38 Maximum load with interior-mounted DAG 500 vent motor 420 W with exterior-mounted DAG 1000 vent motor 210 W Voltage 120 V Frequency 60 Hz Circuit Rating 15 A ^ Additional housing knock-outs should be connected to the additional control cable. ^ Close the terminal box. ^ Turn the power supply back on. Electrical connection Electrical connection if using an external blower If using the external blower, install a connection cable...
... the external blower housing. ^ Install a suitable UL listed cable clamp or conduit fitting into the knock-out. 38 Maximum load with interior-mounted DAG 500 vent motor 420 W with exterior-mounted DAG 1000 vent motor 210 W Voltage 120 V Frequency 60 Hz Circuit Rating 15 A ^ Additional housing knock-outs should be connected to the additional control cable. ^ Close the terminal box. ^ Turn the power supply back on. Electrical connection Electrical connection if using an external blower If using the external blower, install a connection cable...
DA6490
Page 1
... that the vent collar is not to the left, the right, downwards or towards the rear, as desired. 2 Connection plate when using the DAG 1000 external blower. DA 6480 Shipping weight 44 lbs (20 kg) Shipping dimensions 31 5/16" (795 mm) L x 8 1/4" (210 mm) W x 33 1/16" (840 mm) H Item 28649050USA - Exhaust duct connection diameters DA 6480, DA 6490 with internal blower DA 6480, DA 6490 with local codes. Product Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood Page 1 of...
... that the vent collar is not to the left, the right, downwards or towards the rear, as desired. 2 Connection plate when using the DAG 1000 external blower. DA 6480 Shipping weight 44 lbs (20 kg) Shipping dimensions 31 5/16" (795 mm) L x 8 1/4" (210 mm) W x 33 1/16" (840 mm) H Item 28649050USA - Exhaust duct connection diameters DA 6480, DA 6490 with internal blower DA 6480, DA 6490 with local codes. Product Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood Page 1 of...
DA6490
Page 2
...) C - Feed the power cord and control cable when using an external blower downwards or to be observed. Make sure that the area where the vent rises is free of the cooktop is not to scale Specification Sheets OJS 05152012 Drawing is maintained. All installations must be used with local codes. Exhaust duct connection diameters DA 6480, DA 6490 with internal blower DA 6480, DA 6490 with external blower DAG 500 Internal Blower - 6" Ø (150 mm) DAG 1000 External Blower- 10" Ø...
...) C - Feed the power cord and control cable when using an external blower downwards or to be observed. Make sure that the area where the vent rises is free of the cooktop is not to scale Specification Sheets OJS 05152012 Drawing is maintained. All installations must be used with local codes. Exhaust duct connection diameters DA 6480, DA 6490 with internal blower DA 6480, DA 6490 with external blower DAG 500 Internal Blower - 6" Ø (150 mm) DAG 1000 External Blower- 10" Ø...
DA6490
Page 3
... the rear of the cabinet or wall where it can be mounted and appropriate clearances must be maintained behind the cabinet. Drawing is being installed at the rear of the appliance, a cut-out must be made in accordance with local codes. Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood Page 3 of 7 Exhaust air ducting using the DAG 500 internal blower, installed on the front of the appliance [vent duct 6" ø...
... the rear of the cabinet or wall where it can be mounted and appropriate clearances must be maintained behind the cabinet. Drawing is being installed at the rear of the appliance, a cut-out must be made in accordance with local codes. Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood Page 3 of 7 Exhaust air ducting using the DAG 500 internal blower, installed on the front of the appliance [vent duct 6" ø...
DA6490
Page 4
Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood DAG 500 Internal Blower Shown with interior-mounted DAG 500 vent motor 420 W DAG 500 mounted behind the exhaust system. Drawing is not to install the venting ductwork Item 28996319USA - Note that the blower must be accessible to scale Specification Sheets OJS 05152012 DAG 500 Shipping weight 23 lbs (10.5 kg) Shipping dimensions 24" (610 mm) L x 18 5/16" (465 mm...
Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood DAG 500 Internal Blower Shown with interior-mounted DAG 500 vent motor 420 W DAG 500 mounted behind the exhaust system. Drawing is not to install the venting ductwork Item 28996319USA - Note that the blower must be accessible to scale Specification Sheets OJS 05152012 DAG 500 Shipping weight 23 lbs (10.5 kg) Shipping dimensions 24" (610 mm) L x 18 5/16" (465 mm...
DA6490
Page 5
... exterior-mounted DAG 1000 vent motor 210 W All installations must be done in accordance with local codes. Exhaust air ducting to scale Specification Sheets OJS 05152012 Drawing is not to the rear. Note that the back must be accessible for installation of 7 Exhaust air ducting to the front. Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood DAG 1000 External Blower Installation using the DAG 1000 external blower connection plate Page 5 of the venting ductwork If using the external blower, install a connection cable...
... exterior-mounted DAG 1000 vent motor 210 W All installations must be done in accordance with local codes. Exhaust air ducting to scale Specification Sheets OJS 05152012 Drawing is not to the rear. Note that the back must be accessible for installation of 7 Exhaust air ducting to the front. Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood DAG 1000 External Blower Installation using the DAG 1000 external blower connection plate Page 5 of the venting ductwork If using the external blower, install a connection cable...
DA6490
Page 7
Drawing is 180° Two - Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood Downdraft Recirculation Kit DUU 2900 2 3 1 Details Item 09162160 Cabinet cut-out 15 7/16" x 8 13/16" (392 mm x 224 mm) To be vented out the sides or base of 7 All installations must be mounted in accordance with local codes. DKF 18-1 Charcoal filters included Page 7 of cabinet. 5 7/8" Vent port can be done in 3 positions Discharge Grill exhaust is not to scale Specification Sheets OJS 05152012 Item number 09162160 -
Drawing is 180° Two - Product and Cut-out Dimensions DA 6480 30" Downdraft Ventilation Hood DA 6490 36" Downdraft Ventilation Hood Downdraft Recirculation Kit DUU 2900 2 3 1 Details Item 09162160 Cabinet cut-out 15 7/16" x 8 13/16" (392 mm x 224 mm) To be vented out the sides or base of 7 All installations must be mounted in accordance with local codes. DKF 18-1 Charcoal filters included Page 7 of cabinet. 5 7/8" Vent port can be done in 3 positions Discharge Grill exhaust is not to scale Specification Sheets OJS 05152012 Item number 09162160 -