Owner's Manual
Page 3
Table of Contents Important Information 5 Tools 6 Uninstalling the Existing Unit 9 Installing the Thermostat 13 installing the wall plate 15 connecting the wires 17 attaching the thermostat 19 Operation 23 Indicators & Adjustments 25 Troubleshooting 28 Wiring Diagrams 30
Table of Contents Important Information 5 Tools 6 Uninstalling the Existing Unit 9 Installing the Thermostat 13 installing the wall plate 15 connecting the wires 17 attaching the thermostat 19 Operation 23 Indicators & Adjustments 25 Troubleshooting 28 Wiring Diagrams 30
Owner's Manual
Page 7
The wires must be labeled prior to removal to ensure proper reconnection. NOTICE! Do not disconnect the wires from the existing thermostat before reading these instructions.
The wires must be labeled prior to removal to ensure proper reconnection. NOTICE! Do not disconnect the wires from the existing thermostat before reading these instructions.
Owner's Manual
Page 9
Turn the power to the back of the wall plate. Locate, but do not disconnect the wires. (If wires are not visible, they may have doors that must be connected to the HVAC system OFF at the main power panel or at the furnace. 2. uninstalling the existing unit 1. Remove the existing thermostat cover to expose the wires and mounting screws.) Some models may have multiple covers, screws or other locking devices that open to access the wires from the existing thermostat. Turn the system power OFF from the wall. (Some thermostats may be removed or disengaged.) 3.
Turn the power to the back of the wall plate. Locate, but do not disconnect the wires. (If wires are not visible, they may have doors that must be connected to the HVAC system OFF at the main power panel or at the furnace. 2. uninstalling the existing unit 1. Remove the existing thermostat cover to expose the wires and mounting screws.) Some models may have multiple covers, screws or other locking devices that open to access the wires from the existing thermostat. Turn the system power OFF from the wall. (Some thermostats may be removed or disengaged.) 3.
Owner's Manual
Page 10
if your existing thermostat is marked... label the wire with this sticker: B O G W Y RC RH RH / R / VR / 4 24 Volt RH RC / VC 24 Volt cool RC Y / C* / M air conditioning compressor Y W / H heating W G / F fan G O reversing valve cool O B reversing valve heat B 10
if your existing thermostat is marked... label the wire with this sticker: B O G W Y RC RH RH / R / VR / 4 24 Volt RH RC / VC 24 Volt cool RC Y / C* / M air conditioning compressor Y W / H heating W G / F fan G O reversing valve cool O B reversing valve heat B 10
Owner's Manual
Page 11
... 4. If you have a wire marked C, do not always comply with standards, so wire color should not be ignored. This wire is used . Do not let the wires slip back into the wall during disconnection. After all wires are labeled, disconnect each wire according to the existing terminal ...designation for non-battery powered thermostats. 5. You may be a Common wire and should be used only for proper identification. *If wires marked Y & C are not labeled, contact a qualified HVAC technician.) W RC Y G W Note: Wire colors do not connect it to the wall as you disconnect them. ...
... 4. If you have a wire marked C, do not always comply with standards, so wire color should not be ignored. This wire is used . Do not let the wires slip back into the wall during disconnection. After all wires are labeled, disconnect each wire according to the existing terminal ...designation for non-battery powered thermostats. 5. You may be a Common wire and should be used only for proper identification. *If wires marked Y & C are not labeled, contact a qualified HVAC technician.) W RC Y G W Note: Wire colors do not connect it to the wall as you disconnect them. ...
Owner's Manual
Page 15
Reposition the thermostat on the Hunter wall plate, or if there are flush with the wall. 6. installing the thermostat, cont. If the existing holes do not match those on the wall, pulling the wires through the opening . 3. Verify that the thermostat is visually level and securely tighten both screws. ... . Tap the plastic anchors into the anchors. INSTALLING THE WALL PLATE 2. Position the new thermostat on the wall and pull the labeled wires through the mounting holes and into the holes until they are no existing holes, level the thermostat and mark the wall for two holes. 4....
Reposition the thermostat on the Hunter wall plate, or if there are flush with the wall. 6. installing the thermostat, cont. If the existing holes do not match those on the wall, pulling the wires through the opening . 3. Verify that the thermostat is visually level and securely tighten both screws. ... . Tap the plastic anchors into the anchors. INSTALLING THE WALL PLATE 2. Position the new thermostat on the wall and pull the labeled wires through the mounting holes and into the holes until they are no existing holes, level the thermostat and mark the wall for two holes. 4....
Owner's Manual
Page 17
...but do not provide both an RH and RC wire. If you have both an RH and RC wire, remove this jumper. Push any extra wires should be wrapped in place. 2. Match and connect the wires from the wall to prevent interference. 17 Note: A jumper wire has been provided, connecting the RC and RH ...terminals for systems that do not remove, the terminal screws. CONNECTING THE WIRES 1. Wires should be inserted behind the black terminal shields. If you do not have both an RH and RC wire, leave the jumper in electrical tape and carefully pushed back into the wall to the ...
...but do not provide both an RH and RC wire. If you have both an RH and RC wire, remove this jumper. Push any extra wires should be wrapped in place. 2. Match and connect the wires from the wall to prevent interference. 17 Note: A jumper wire has been provided, connecting the RC and RH ...terminals for systems that do not remove, the terminal screws. CONNECTING THE WIRES 1. Wires should be inserted behind the black terminal shields. If you do not have both an RH and RC wire, leave the jumper in electrical tape and carefully pushed back into the wall to the ...
Owner's Manual
Page 28
... continues to operate when the thermostat is closed properly. 1 f. My heating or cooling will not turn on or off . 1 a. If your system has 4 wires, ensure the jumper wire is enough power to protect the compressor. 1 c. Wait. Check the circuit breakers and switches to the correct position. 1 b. Check the HE/HG switch to...
... continues to operate when the thermostat is closed properly. 1 f. My heating or cooling will not turn on or off . 1 a. If your system has 4 wires, ensure the jumper wire is enough power to protect the compressor. 1 c. Wait. Check the circuit breakers and switches to the correct position. 1 b. Check the HE/HG switch to...
Owner's Manual
Page 30
4-wire Heat/Cool System Jumper G Fan Relay Rc Rh Y W X Heat/Cool Cool Heat Relay 24V Supply Contactor or Valve 5-wire Heat/Cool System G Rc Rh Y W Fan Relay Cool Heat Cool Heat Relay 24V Supply 24V Supply Contactor or Valve 30
4-wire Heat/Cool System Jumper G Fan Relay Rc Rh Y W X Heat/Cool Cool Heat Relay 24V Supply Contactor or Valve 5-wire Heat/Cool System G Rc Rh Y W Fan Relay Cool Heat Cool Heat Relay 24V Supply 24V Supply Contactor or Valve 30
Owner's Manual
Page 31
wiring diagrams Single-stage Heat Pump System Jumper G Fan Relay Rc Rh O B W Y X Heat/Cool 24V Supply Cool Mode OR Heat X Mode Reversing Valve Compressor Contactor 2-wire Heat Only System Jumper Rc Rh W X Heat 24V or Millivolt Supply Heat Relay or Valve 31
wiring diagrams Single-stage Heat Pump System Jumper G Fan Relay Rc Rh O B W Y X Heat/Cool 24V Supply Cool Mode OR Heat X Mode Reversing Valve Compressor Contactor 2-wire Heat Only System Jumper Rc Rh W X Heat 24V or Millivolt Supply Heat Relay or Valve 31
Owner's Manual
Page 32
wiring diagrams, cont. 3-wire Heat Only System Jumper G Rc Rh W Fan Relay X Heat 24V Supply Heat Relay or Valve 3-wire Cool Only System Jumper G Rc Rh Y Fan Relay X Cool 24V Supply Cool Contacter 32
wiring diagrams, cont. 3-wire Heat Only System Jumper G Rc Rh W Fan Relay X Heat 24V Supply Heat Relay or Valve 3-wire Cool Only System Jumper G Rc Rh Y Fan Relay X Cool 24V Supply Cool Contacter 32
Owner's Manual
Page 10
label the wire with this sticker: B O G W Y RC RH RH / R / VR / 4 24 Volt RH RC / VC 24 Volt cool RC Y / C* / M air conditioning compressor Y W / H heating W G / F fan G O reversing valve cool O B reversing valve heat B 10 if your existing thermostat is marked...
label the wire with this sticker: B O G W Y RC RH RH / R / VR / 4 24 Volt RH RC / VC 24 Volt cool RC Y / C* / M air conditioning compressor Y W / H heating W G / F fan G O reversing valve cool O B reversing valve heat B 10 if your existing thermostat is marked...
Owner's Manual
Page 30
4-wire Heat/Cool System Jumper G Fan Relay Rc Rh Y W X Heat/Cool Cool Heat Relay 24V Supply Contactor or Valve 5-wire Heat/Cool System G Rc Rh Y W Fan Relay Cool Heat Cool Heat Relay 24V Supply 24V Supply Contactor or Valve 30
4-wire Heat/Cool System Jumper G Fan Relay Rc Rh Y W X Heat/Cool Cool Heat Relay 24V Supply Contactor or Valve 5-wire Heat/Cool System G Rc Rh Y W Fan Relay Cool Heat Cool Heat Relay 24V Supply 24V Supply Contactor or Valve 30
Owner's Manual
Page 31
diagramAs DE CABLEADO Single-stage Heat Pump System Jumper G Fan Relay Rc Rh O B W H X Heat/Cool 24V Supply Cool Mode OR Heat X Mode Reversing Valve Compressor Contactor 2-wire Heat Only System Jumper Rc Rh W X Heat 24V or Millivolt Supply Heat Relay or Valve 31
diagramAs DE CABLEADO Single-stage Heat Pump System Jumper G Fan Relay Rc Rh O B W H X Heat/Cool 24V Supply Cool Mode OR Heat X Mode Reversing Valve Compressor Contactor 2-wire Heat Only System Jumper Rc Rh W X Heat 24V or Millivolt Supply Heat Relay or Valve 31
Owner's Manual
Page 32
diagramas de cableado, cont. 3-wire Heat Only System Jumper G Rc Rh W Fan Relay X Heat 24V Supply Heat Relay or Valve 3-wire Cool Only System Jumper G Rc Rh Y X Fan Relay Cool 24V Supply Cool Contacter 32
diagramas de cableado, cont. 3-wire Heat Only System Jumper G Rc Rh W Fan Relay X Heat 24V Supply Heat Relay or Valve 3-wire Cool Only System Jumper G Rc Rh Y X Fan Relay Cool 24V Supply Cool Contacter 32
Owner's Manual
Page 10
label the wire with this sticker: B O G W Y RC RH RH / R / VR / 4 24 Volt RH RC / VC 24 Volt cool RC Y / C* / M air conditioning compressor Y W / H heating W G / F fan G O reversing valve cool O B reversing valve heat B 10 if your existing thermostat is marked...
label the wire with this sticker: B O G W Y RC RH RH / R / VR / 4 24 Volt RH RC / VC 24 Volt cool RC Y / C* / M air conditioning compressor Y W / H heating W G / F fan G O reversing valve cool O B reversing valve heat B 10 if your existing thermostat is marked...
Owner's Manual
Page 30
4-wire Heat/Cool System G Fan Relay Jumper Rc Rh Y W X Heat/Cool Cool Heat Relay 24V Supply Contactor or Valve 5-wire Heat/Cool System G Rc Rh Y W Fan Relay Cool Heat Cool Heat Relay 24V Supply 24V Supply Contactor or Valve 30
4-wire Heat/Cool System G Fan Relay Jumper Rc Rh Y W X Heat/Cool Cool Heat Relay 24V Supply Contactor or Valve 5-wire Heat/Cool System G Rc Rh Y W Fan Relay Cool Heat Cool Heat Relay 24V Supply 24V Supply Contactor or Valve 30
Owner's Manual
Page 31
Diagrammes de câblage Single-stage Heat Pump System Jumper G Fan Relay Rc Rh O B W Y X Heat/Cool 24V Supply Cool Mode OR Heat X Mode Reversing Valve Compressor Contactor 2-wire Heat Only System Jumper Rc Rh W X Heat 24V or Millivolt Supply Heat Relay or Valve 31
Diagrammes de câblage Single-stage Heat Pump System Jumper G Fan Relay Rc Rh O B W Y X Heat/Cool 24V Supply Cool Mode OR Heat X Mode Reversing Valve Compressor Contactor 2-wire Heat Only System Jumper Rc Rh W X Heat 24V or Millivolt Supply Heat Relay or Valve 31