Owner's Manual
Page 1
...current sensing relay with the eight remaining screws. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24V WIRING. Registered Trademark Copyright © 1997 Honeywell Inc. • All Rights Reserved TEMPLATE 69-1107 INSTALLATION WARNING Personal Injury or Equipment Damage Can Occur.... control to prevent electrical shock or equipment damage. W.C. RETURN RETURN HORIZONTAL RETURN RETURN DFOLWON HIGHBOY LOWBOY M12687 Fig. 1. HE360 Humidifier location in the guide slots of the cover to the housing and secure with applicable local codes, ordinances and regulations...
...current sensing relay with the eight remaining screws. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. 2 24V WIRING. Registered Trademark Copyright © 1997 Honeywell Inc. • All Rights Reserved TEMPLATE 69-1107 INSTALLATION WARNING Personal Injury or Equipment Damage Can Occur.... control to prevent electrical shock or equipment damage. W.C. RETURN RETURN HORIZONTAL RETURN RETURN DFOLWON HIGHBOY LOWBOY M12687 Fig. 1. HE360 Humidifier location in the guide slots of the cover to the housing and secure with applicable local codes, ordinances and regulations...
Owner's Manual
Page 2
... run to regulate water flow. Open saddle valve. 2. Check for the humidifier to drain correctly. 4. Box 524 Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 69-11057 J.H. 10-97 Printed in . PLUMBING SADDLE VALVE The humidifier...tap into the solenoid valve fitting and support the valve while tightening the compression nut. Home and Building Control Honeywell Inc. a. b. HUMIDISTAT 2 HUMIDIFIER 120 VAC 1 SAIL SWITCH YELLOW WIRES 1 POWER SUPPLY. NOTE: Lightly clean the copper tubing ends with a humidifier.
... run to regulate water flow. Open saddle valve. 2. Check for the humidifier to drain correctly. 4. Box 524 Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 69-11057 J.H. 10-97 Printed in . PLUMBING SADDLE VALVE The humidifier...tap into the solenoid valve fitting and support the valve while tightening the compression nut. Home and Building Control Honeywell Inc. a. b. HUMIDISTAT 2 HUMIDIFIER 120 VAC 1 SAIL SWITCH YELLOW WIRES 1 POWER SUPPLY. NOTE: Lightly clean the copper tubing ends with a humidifier.
Installation Guide
Page 1
...have also taken the first step in reducing the zapping you create when you use your Honeywell humidifier, notice that your skin is not as dry, and that your new Honeywell HE360 Humidifier, H8908 Humidistat and all the accessories required for the Installation Be sure to identify ...To the comfortable world of your pet. You have just made a great investment in (12.7 mm) ID drain tubing 1 bag Connecting and mounting hardware: Wire nuts (4) No. 8 sheet metal screws (18) Drain tube clamp Feed tube mounting clamps (6) Brass inserts (2) Plastic compression rings (2) 1 H8908 Humidistat 1 ...
...have also taken the first step in reducing the zapping you create when you use your Honeywell humidifier, notice that your skin is not as dry, and that your new Honeywell HE360 Humidifier, H8908 Humidistat and all the accessories required for the Installation Be sure to identify ...To the comfortable world of your pet. You have just made a great investment in (12.7 mm) ID drain tubing 1 bag Connecting and mounting hardware: Wire nuts (4) No. 8 sheet metal screws (18) Drain tube clamp Feed tube mounting clamps (6) Brass inserts (2) Plastic compression rings (2) 1 H8908 Humidistat 1 ...
Installation Guide
Page 2
...we recommend that you can easily remove the cover to allow adequate space for the control wiring circuit. Selecting Location for Humidistat • Select a location for the humidifier on the .... • Level. • 3/4-in . (78 mm) above the humidifier so you install the Honeywell Whole House Drum or Disk Humidifier. Be sure supply plenum static pressure is no greater than 0.4 in...tubing provided is between 32°F (0°C) and 160°F (71°C). HE360 HUMIDIFIER AND INSTALLATION KIT Table 1. sheet metal Terminal Adaptor - RETURN RETURN HORIZONTAL RETURN ...
...we recommend that you can easily remove the cover to allow adequate space for the control wiring circuit. Selecting Location for Humidistat • Select a location for the humidifier on the .... • Level. • 3/4-in . (78 mm) above the humidifier so you install the Honeywell Whole House Drum or Disk Humidifier. Be sure supply plenum static pressure is no greater than 0.4 in...tubing provided is between 32°F (0°C) and 160°F (71°C). HE360 HUMIDIFIER AND INSTALLATION KIT Table 1. sheet metal Terminal Adaptor - RETURN RETURN HORIZONTAL RETURN ...
Installation Guide
Page 3
... off power to the outlet. • Make sure that the 20 ft (6.2m) of thermostat wire is level, then position it in the opening . Position securing clips. 8. Push in . (381 mm) MINIMUM RETURN AIR DUCT M12831A HE360 HUMIDIFIER AND INSTALLATION KIT 4. See Fig. 3. Draw a level line on the top of the opening...
... off power to the outlet. • Make sure that the 20 ft (6.2m) of thermostat wire is level, then position it in the opening . Position securing clips. 8. Push in . (381 mm) MINIMUM RETURN AIR DUCT M12831A HE360 HUMIDIFIER AND INSTALLATION KIT 4. See Fig. 3. Draw a level line on the top of the opening...
Installation Guide
Page 5
... with humidistat. 7. Secure the base to the duct using the four 1 in Fig. 8). 4. Connect the low-voltage wires to drill the control assembly opening and mounting holes for the humidistat. See Fig. 12. HE360 HUMIDIFIER AND INSTALLATION KIT IMPORTANT Calibration accuracy requires that the switch be mounted to the supply duct. Insert...
... with humidistat. 7. Secure the base to the duct using the four 1 in Fig. 8). 4. Connect the low-voltage wires to drill the control assembly opening and mounting holes for the humidistat. See Fig. 12. HE360 HUMIDIFIER AND INSTALLATION KIT IMPORTANT Calibration accuracy requires that the switch be mounted to the supply duct. Insert...
Installation Guide
Page 6
...161;C HUMIDITY SETTING 15% 20% 25% 30% 35% 40% HUMIDIFIER SOLENOID VALVE BLACK AIR PRESSURE SWITCH WHITE M28969 Fig. 12. Wiring the controls. At the humidistat, connect both ends for automatic operation. 69-2517EF-01 6 NOTE: Humidistat and pressure switch can be ... the water supply 2. Check for leaks. 5. HE360 HUMIDIFIER AND INSTALLATION KIT HUMIDISTAT BASE REAR OF HUMIDISTAT WIRE SLOT HUMIDISTAT WIRES M20179 Fig. 11. TESTING HUMIDIFIER OPERATION Checklist Humidifier is level. Control wiring was reviewed using circuit diagram. Humidifier...
...161;C HUMIDITY SETTING 15% 20% 25% 30% 35% 40% HUMIDIFIER SOLENOID VALVE BLACK AIR PRESSURE SWITCH WHITE M28969 Fig. 12. Wiring the controls. At the humidistat, connect both ends for automatic operation. 69-2517EF-01 6 NOTE: Humidistat and pressure switch can be ... the water supply 2. Check for leaks. 5. HE360 HUMIDIFIER AND INSTALLATION KIT HUMIDISTAT BASE REAR OF HUMIDISTAT WIRE SLOT HUMIDISTAT WIRES M20179 Fig. 11. TESTING HUMIDIFIER OPERATION Checklist Humidifier is level. Control wiring was reviewed using circuit diagram. Humidifier...
Installation Guide
Page 9
...etc. Rapid air changes. Verify that needle pierces water line and then backs out needle to drain. Troubleshooting Humidifier. Check all external wiring connections. • Check the humidity control setting. • Call a professional heating contractor. • Keep doors and windows closed....Turn humidistat up and down low enough to click. Condensation on . • Check all connections. TROUBLESHOOTING YOUR HUMIDIFIER HE360 HUMIDIFIER AND INSTALLATION KIT Problem Water leakage No water to open valve. Electrical Humidistat Humidifier power Solenoid Plumbing What to...
...etc. Rapid air changes. Verify that needle pierces water line and then backs out needle to drain. Troubleshooting Humidifier. Check all external wiring connections. • Check the humidity control setting. • Call a professional heating contractor. • Keep doors and windows closed....Turn humidistat up and down low enough to click. Condensation on . • Check all connections. TROUBLESHOOTING YOUR HUMIDIFIER HE360 HUMIDIFIER AND INSTALLATION KIT Problem Water leakage No water to open valve. Electrical Humidistat Humidifier power Solenoid Plumbing What to...
Owners Guide
Page 6
... minimum. • Seal around doors and windows. • Turn humidistat and water off until condensation is on. • Check all external wiring connections. • Check the humidistat setting. • Call a professional heating contractor. • Keep doors and windows closed. • Close... or servicing, use . • Keep exhaust fan running to be a temporary condition caused by following steps to eliminate condensation. HE360 POWERED FLOW-THROUGH HUMIDIFIER 14. Replace the humidifier cover. 16. Verify the humidifier operation by moisture from bathing, mopping, cooking, etc...
... minimum. • Seal around doors and windows. • Turn humidistat and water off until condensation is on. • Check all external wiring connections. • Check the humidistat setting. • Call a professional heating contractor. • Keep doors and windows closed. • Close... or servicing, use . • Keep exhaust fan running to be a temporary condition caused by following steps to eliminate condensation. HE360 POWERED FLOW-THROUGH HUMIDIFIER 14. Replace the humidifier cover. 16. Verify the humidifier operation by moisture from bathing, mopping, cooking, etc...