HP UPS Best Practices
Page 18
...when configuring a redundant system When configuring a UPS in the event that exceeds their normal operating current. Battery Testing The battery test function in HP Power Manager does not initiate a battery test on the UPS model, you may need to provide an advanced warning of each rest mode, the ... time it is loaded to configure a UPS in #4 above). The rackmount UPS automatically performs a battery test each UPS. 6. Page 18 of powering on the HP R3000 UPS, the Test/Reset button must consider the run a ERM configuration utility that can be correctly reported. When Performing ...
...when configuring a redundant system When configuring a UPS in the event that exceeds their normal operating current. Battery Testing The battery test function in HP Power Manager does not initiate a battery test on the UPS model, you may need to provide an advanced warning of each rest mode, the ... time it is loaded to configure a UPS in #4 above). The rackmount UPS automatically performs a battery test each UPS. 6. Page 18 of powering on the HP R3000 UPS, the Test/Reset button must consider the run a ERM configuration utility that can be correctly reported. When Performing ...
HP UPS R3000 User Guide
Page 41
... Auto-Bypass mode ("General alarm condition" on page 42) Yes Bypass is out of range (on page 43) Yes Battery test failure ("Battery condition" on page 43) No Low battery (no utility power) ("UPS is on battery" on page 43) Yes Batteries are disconnected ("Battery condition" on page 43) Yes On battery-No utility power ("UPS is on...
... Auto-Bypass mode ("General alarm condition" on page 42) Yes Bypass is out of range (on page 43) Yes Battery test failure ("Battery condition" on page 43) No Low battery (no utility power) ("UPS is on battery" on page 43) Yes Batteries are disconnected ("Battery condition" on page 43) Yes On battery-No utility power ("UPS is on...
HP UPS R3000 User Guide
Page 63
...batteries, care and storage 36 batteries, charging 24, 26 batteries, connecting 19 batteries, obtaining 36 batteries, replacing 35, 36 batteries, runtime 48 batteries, specifications 48 batteries, testing 38 battery bracket 36 battery cables, connecting 19 battery condition 43 Battery Fault LED, location 8 Battery Fault LED, troubleshooting 41 battery replacement notice 59 battery... button, location 7 Configure mode 28 Configure Mode On LED, location 8 connecting batteries 19 connecting devices to UPS 23 contacting HP 52 cord retention clip locations 9, 10, 11 cord retention clips, connecting 23...
...batteries, care and storage 36 batteries, charging 24, 26 batteries, connecting 19 batteries, obtaining 36 batteries, replacing 35, 36 batteries, runtime 48 batteries, specifications 48 batteries, testing 38 battery bracket 36 battery cables, connecting 19 battery condition 43 Battery Fault LED, location 8 Battery Fault LED, troubleshooting 41 battery replacement notice 59 battery... button, location 7 Configure mode 28 Configure Mode On LED, location 8 connecting batteries 19 connecting devices to UPS 23 contacting HP 52 cord retention clip locations 9, 10, 11 cord retention clips, connecting 23...
HP 3 Phase UPS User Guide
Page 4
... the UPS ...67 Changing the language...67 Changing display functions...67 Changing user settings ...68 Setting the Battery Low alarm level...70 Running automatic battery tests ...71 Testing the front panel display...71 Silencing an audible alarm ...71 Verifying the REPO port connection ...71 Powering ... inputs...77 Parallel communication ...77 Mode transfers ...78 Redundant signal wiring ...78 Auto-identification...78 Metering ...79 Power management ...80 HP UPS Power Protection Agent overview 80 Features ...80 Maintenance ...81 Removing the UPS front bezel ...81 Removing the ERM front bezel......
... the UPS ...67 Changing the language...67 Changing display functions...67 Changing user settings ...68 Setting the Battery Low alarm level...70 Running automatic battery tests ...71 Testing the front panel display...71 Silencing an audible alarm ...71 Verifying the REPO port connection ...71 Powering ... inputs...77 Parallel communication ...77 Mode transfers ...78 Redundant signal wiring ...78 Auto-identification...78 Metering ...79 Power management ...80 HP UPS Power Protection Agent overview 80 Features ...80 Maintenance ...81 Removing the UPS front bezel ...81 Removing the ERM front bezel......
HP 3 Phase UPS User Guide
Page 5
... Verifying the HP UPS Management Module firmware version 91 Configuring a USB to serial converter 91 Reassigning the USB COM ports ...92 Troubleshooting ...94 LED and audible alarm troubleshooting ...94 Silencing an audible alarm ...95 Abnormal output voltage at startup ...95 Battery breaker ...95 Battery connection condition ...96 Battery low condition ...96 Battery test condition...96 Bypass...
... Verifying the HP UPS Management Module firmware version 91 Configuring a USB to serial converter 91 Reassigning the USB COM ports ...92 Troubleshooting ...94 LED and audible alarm troubleshooting ...94 Silencing an audible alarm ...95 Abnormal output voltage at startup ...95 Battery breaker ...95 Battery connection condition ...96 Battery low condition ...96 Battery test condition...96 Bypass...
HP 3 Phase UPS User Guide
Page 68
... Status Event Log Measurements Control Settings Identification Turn UPS On/Off Submenu Parallel system Output Battery Input Load Receptacle Go to Bypass mode Start Battery Test Display Test User Settings Service Settings On and Off Option Display information or menu function System Normal ...| High Efficiency Power: % / Battery Resting | Battery Floating UPS in Parallel mode / Parallel Unit Number x / Units on Bus Bar / Units on page 68)." The battery test might not start immediately. Four different selectable tests for the front panel functions: • The LEDs...
... Status Event Log Measurements Control Settings Identification Turn UPS On/Off Submenu Parallel system Output Battery Input Load Receptacle Go to Bypass mode Start Battery Test Display Test User Settings Service Settings On and Off Option Display information or menu function System Normal ...| High Efficiency Power: % / Battery Resting | Battery Floating UPS in Parallel mode / Parallel Unit Number x / Units on Bus Bar / Units on page 68)." The battery test might not start immediately. Four different selectable tests for the front panel functions: • The LEDs...
HP 3 Phase UPS User Guide
Page 69
...volts per cell] 1.880 V/cell Automatic Battery Tests: Enabled [Enabled][Disabled] Enabled automatically runs the battery test once a month. Power Strategy [High Efficiency][Standard] High Efficiency For more information, see "Normal mode (on page 64) HP logo User Password [Enabled][Disabled] If ...parallel configuration) Mode][Capacity Mode] This setting is USER. Battery Setup Number of ERMs: [0 through 4] 0 For more information, see "Configuring the (internal batteries only) UPS (on page 77)." Start Screen HP logo Mimic screen (on page 65)." Select Sub Unit...
...volts per cell] 1.880 V/cell Automatic Battery Tests: Enabled [Enabled][Disabled] Enabled automatically runs the battery test once a month. Power Strategy [High Efficiency][Standard] High Efficiency For more information, see "Normal mode (on page 64) HP logo User Password [Enabled][Disabled] If ...parallel configuration) Mode][Capacity Mode] This setting is USER. Battery Setup Number of ERMs: [0 through 4] 0 For more information, see "Configuring the (internal batteries only) UPS (on page 77)." Start Screen HP logo Mimic screen (on page 65)." Select Sub Unit...
HP 3 Phase UPS User Guide
Page 70
Select SETTINGS > USER SETTINGS > BATTERY SETUP > Automatic Battery Tests. 3. For a list of battery warning for a UPS. Warning time Number of ERMs (in a parallel system can provide a longer warning time. Press and hold the ESC ...Custom Event Settings REPO Configuration Available settings [Enabled][Disabled] 0 through 32 [Enabled][Disabled] Default setting Enabled Total: 0/32 Enabled Setting the Battery Low alarm level The default Battery Low alarm level setting provides approximately 2.5 minutes of settings, see the table below. 4. Additional ERMs installed in minutes) installed...
Select SETTINGS > USER SETTINGS > BATTERY SETUP > Automatic Battery Tests. 3. For a list of battery warning for a UPS. Warning time Number of ERMs (in a parallel system can provide a longer warning time. Press and hold the ESC ...Custom Event Settings REPO Configuration Available settings [Enabled][Disabled] 0 through 32 [Enabled][Disabled] Default setting Enabled Total: 0/32 Enabled Setting the Battery Low alarm level The default Battery Low alarm level setting provides approximately 2.5 minutes of settings, see the table below. 4. Additional ERMs installed in minutes) installed...
HP 3 Phase UPS User Guide
Page 71
...using the utility as a load. NOTE: For automatic and manual battery tests, the UPS determines when it is in a safe test mode so the effects do not disrupt critical operations. Select SETTINGS > USER SETTINGS > BATTERY SETUP > Battery Low Alarm. 3. Confirm the selection by closing the REPO contact... audible alarm conditions, see "LED and audible alarm troubleshooting (on page 21): 1. UPS operations 71 Some sites might trip off). Battery tests run the test. IMPORTANT: • Although the audible alarm silences, the condition that caused the alarm to sound may still exist. • If...
...using the utility as a load. NOTE: For automatic and manual battery tests, the UPS determines when it is in a safe test mode so the effects do not disrupt critical operations. Select SETTINGS > USER SETTINGS > BATTERY SETUP > Battery Low Alarm. 3. Confirm the selection by closing the REPO contact... audible alarm conditions, see "LED and audible alarm troubleshooting (on page 21): 1. UPS operations 71 Some sites might trip off). Battery tests run the test. IMPORTANT: • Although the audible alarm silences, the condition that caused the alarm to sound may still exist. • If...
HP 3 Phase UPS User Guide
Page 77
...card. If active, the High Efficiency setting is disabled (BladeUPS 12i model only) and battery tests are disabled.1 If active, the UPS knows that the external batteries are local only to activate the specific input. Programmable signal inputs The UPS incorporates two ...air conditioner sensor to power down regardless of the mode of operation. HP recommends using non-polar (relay) control input. Signal Description empty Not in a parallel system. Auxiliary power, communication, and rectifier/battery charger remain functional. Communication 77 In a utility power outage, the ...
...card. If active, the High Efficiency setting is disabled (BladeUPS 12i model only) and battery tests are disabled.1 If active, the UPS knows that the external batteries are local only to activate the specific input. Programmable signal inputs The UPS incorporates two ...air conditioner sensor to power down regardless of the mode of operation. HP recommends using non-polar (relay) control input. Signal Description empty Not in a parallel system. Auxiliary power, communication, and rectifier/battery charger remain functional. Communication 77 In a utility power outage, the ...
HP 3 Phase UPS User Guide
Page 89
Remove the UPS battery modules. IMPORTANT: Charge the batteries for 48 hours to perform the battery test. NOTE: For an accurate battery test, test the UPS with at least 48 hours before supplying backup power to the UPS. Select CONTROL and then START BATTERY TEST. During the battery test, the front panel displays "Battery Test Pending." Maintenance 89 A failed battery test initiates a Battery Test Failed alarm. Plug the...
Remove the UPS battery modules. IMPORTANT: Charge the batteries for 48 hours to perform the battery test. NOTE: For an accurate battery test, test the UPS with at least 48 hours before supplying backup power to the UPS. Select CONTROL and then START BATTERY TEST. During the battery test, the front panel displays "Battery Test Pending." Maintenance 89 A failed battery test initiates a Battery Test Failed alarm. Plug the...
HP 3 Phase UPS User Guide
Page 96
... the load, and charges the battery. See "Testing the new battery module (on page 104)." Battery test failed: If the condition persists, contact an HP authorized service representative. When utility power is in the On position. 2. Battery test did not run or was aborted: 1. Allow the UPS batteries to the connected equipment. Battery test condition Action: Battery test pending: 1. The UPS continues to...
... the load, and charges the battery. See "Testing the new battery module (on page 104)." Battery test failed: If the condition persists, contact an HP authorized service representative. When utility power is in the On position. 2. Battery test did not run or was aborted: 1. Allow the UPS batteries to the connected equipment. Battery test condition Action: Battery test pending: 1. The UPS continues to...
HP 3 Phase UPS User Guide
Page 113
..., insufficient 100 batteries, care and storage 87 batteries, charging 25, 63 batteries, replacing 87, 88 batteries, specifications 104 battery bracket 19, 20 battery circuit breaker 24 battery circuit breaker, troubleshooting 95 Battery Low Alarm level, setting 70 Battery mode 66 battery tests 71 battery warranty 109 battery, installing 19 ...configuring, Parallel UPS Card 41 connecting devices to UPS 24 connecting, bus bar 35 connectors 7, 10, 12 contacting HP 107 continuous double-conversion mode 65 control terminals, installing 74 control terminals, overview 76 D Declaration of Conformity 108...
..., insufficient 100 batteries, care and storage 87 batteries, charging 25, 63 batteries, replacing 87, 88 batteries, specifications 104 battery bracket 19, 20 battery circuit breaker 24 battery circuit breaker, troubleshooting 95 Battery Low Alarm level, setting 70 Battery mode 66 battery tests 71 battery warranty 109 battery, installing 19 ...configuring, Parallel UPS Card 41 connecting devices to UPS 24 connecting, bus bar 35 connectors 7, 10, 12 contacting HP 107 continuous double-conversion mode 65 control terminals, installing 74 control terminals, overview 76 D Declaration of Conformity 108...
HP 3 Phase UPS User Guide
Page 115
..., normally-closed 22, 33 REPO, normally-open 21, 30 required tools 13 running battery tests 71 S safety considerations 13, 87 selecting a site 14 selective trip 99 serial port 75 setting Battery Low alarm level 70 shipping the UPS 14 site requirements 14 site wiring condition 99 spare... down 72 standalone UPS, powering up 25 Standby mode 64 static electricity 110 storing batteries 87 support 107 supported hardware 106 T technical support 107 telephone numbers 107 temperature ranges (environmental) 103 testing LEDs 71 tools 13 top entry wiring 28 troubleshooting 94 U unpacking the components 14...
..., normally-closed 22, 33 REPO, normally-open 21, 30 required tools 13 running battery tests 71 S safety considerations 13, 87 selecting a site 14 selective trip 99 serial port 75 setting Battery Low alarm level 70 shipping the UPS 14 site requirements 14 site wiring condition 99 spare... down 72 standalone UPS, powering up 25 Standby mode 64 static electricity 110 storing batteries 87 support 107 supported hardware 106 T technical support 107 telephone numbers 107 temperature ranges (environmental) 103 testing LEDs 71 tools 13 top entry wiring 28 troubleshooting 94 U unpacking the components 14...
UPS R3000 XR Models User Guide
Page 40
... suggested actions. The UPS power cord is disconnected. Contact a qualified electrician. Allow the UPS to charge the batteries for 24 hours. Initiate a self-test. Allow the UPS to charge the batteries for a long period of time. HP Uninterruptible Power System R3000 XR Models User Guide 5-1 Problems During Startup If problems occur when starting the...
... suggested actions. The UPS power cord is disconnected. Contact a qualified electrician. Allow the UPS to charge the batteries for 24 hours. Initiate a self-test. Allow the UPS to charge the batteries for a long period of time. HP Uninterruptible Power System R3000 XR Models User Guide 5-1 Problems During Startup If problems occur when starting the...
HP UPS R7000 User Guide
Page 33
...Resets the UPS back to factory settings Change language Changes language settings. The default is USER. Automatic battery test Enables or disables battery test. UPS Type / Part Number / Serial Number / NMC Firmware / Comm Firmware / UPS Firmware Verifying the REPO port ...changed. Event Log Measurements - - - - Default: Disable. Control - - - - Output Output Output Input Battery Go to Bypass mode Battery Test Display information or menu function Battery Charging/Floating/Resting, Charge Level, ERM Number, and Runtime Displays events and alarms Output watts and VA Output amps...
...Resets the UPS back to factory settings Change language Changes language settings. The default is USER. Automatic battery test Enables or disables battery test. UPS Type / Part Number / Serial Number / NMC Firmware / Comm Firmware / UPS Firmware Verifying the REPO port ...changed. Event Log Measurements - - - - Default: Disable. Control - - - - Output Output Output Input Battery Go to Bypass mode Battery Test Display information or menu function Battery Charging/Floating/Resting, Charge Level, ERM Number, and Runtime Displays events and alarms Output watts and VA Output amps...
HP UPS R7000 User Guide
Page 45
... charger has been disabled until commanded out of ABM charge mode is detected during the battery Notice test. Alarm The UPS is powered up all output relays and shed the load. The UPS is operating from bypass. Notice The UPS is Alarm less ... UPS On Bypass 170 UPS Off 172 UPS On Command 173 UPS Off Command 174 Battery Shutdown 181 UPS Control Power ON 191 Battery Test Failed 194 Site Wiring Problem 199 Battery Disconnected 237 1600 1601 1602 1603 1999 UPS System Normal ABM State Charging ABM State Floating ABM State Resting ABM State OFF...
... charger has been disabled until commanded out of ABM charge mode is detected during the battery Notice test. Alarm The UPS is powered up all output relays and shed the load. The UPS is operating from bypass. Notice The UPS is Alarm less ... UPS On Bypass 170 UPS Off 172 UPS On Command 173 UPS Off Command 174 Battery Shutdown 181 UPS Control Power ON 191 Battery Test Failed 194 Site Wiring Problem 199 Battery Disconnected 237 1600 1601 1602 1603 1999 UPS System Normal ABM State Charging ABM State Floating ABM State Resting ABM State OFF...
HP R/T3000 G2 UPS User Guide
Page 55
Troubleshooting LED troubleshooting Utility LED On On Self Test Battery Site Over Battery Bypass LED Fault LED Wiring Temp LED LED Fault LED LED Overload Condition LED On-Lo Off Off On-Loa On-Loa On-Loa On-... Auto-Bypass mode On Off Flashing * * * * * Bypass is out of range (on page 58) * Off * Off Flashing * * * Off Flashing Off Off Off Off Off Off Battery condition (on page 58)-Batteries are disconnected or battery test failure Low battery (no utility power) ("UPS is on battery" on page 58) Troubleshooting 55
Troubleshooting LED troubleshooting Utility LED On On Self Test Battery Site Over Battery Bypass LED Fault LED Wiring Temp LED LED Fault LED LED Overload Condition LED On-Lo Off Off On-Loa On-Loa On-Loa On-... Auto-Bypass mode On Off Flashing * * * * * Bypass is out of range (on page 58) * Off * Off Flashing * * * Off Flashing Off Off Off Off Off Off Battery condition (on page 58)-Batteries are disconnected or battery test failure Low battery (no utility power) ("UPS is on battery" on page 58) Troubleshooting 55
HP R/T3000 G2 UPS User Guide
Page 78
...batteries, care and storage 46 batteries, charging 25, 30 batteries, connecting 18, 27 batteries, obtaining 47 batteries, replacing 45, 46, 47 batteries, runtime 63 batteries, specifications 62 batteries, testing 48 battery bracket 47 battery condition 58 Battery Fault LED, location 8 Battery Fault LED, troubleshooting 55 Battery mode 41 battery replacement notice 73 battery... B equipment 69 components, identification 7, 8 configuration of system 42 Configure mode 41 connecting batteries 18, 27 contacting HP 66 Converter Off mode 57 converter, serial to USB 50 D Declaration of Conformity 70 ...
...batteries, care and storage 46 batteries, charging 25, 30 batteries, connecting 18, 27 batteries, obtaining 47 batteries, replacing 45, 46, 47 batteries, runtime 63 batteries, specifications 62 batteries, testing 48 battery bracket 47 battery condition 58 Battery Fault LED, location 8 Battery Fault LED, troubleshooting 55 Battery mode 41 battery replacement notice 73 battery... B equipment 69 components, identification 7, 8 configuration of system 42 Configure mode 41 connecting batteries 18, 27 contacting HP 66 Converter Off mode 57 converter, serial to USB 50 D Declaration of Conformity 70 ...
HP UPS R1500 G2 User Guide
Page 33
...LED and audible alarm troubleshooting Condition Power On LED (green) On Battery LED (yellow) UPS operating from utility Buck mode (high input voltage) Boost mode (low input voltage) Over temperature condition Battery test failure Fan failure Output short circuit Power up failure from a ...DC start- Low battery (no utility power) Low battery (no utility power) Online-UPS power capacity exceeded Overload timeout On battery-Input voltage is out of range On battery-No utility power On battery-Battery voltage...
...LED and audible alarm troubleshooting Condition Power On LED (green) On Battery LED (yellow) UPS operating from utility Buck mode (high input voltage) Boost mode (low input voltage) Over temperature condition Battery test failure Fan failure Output short circuit Power up failure from a ...DC start- Low battery (no utility power) Low battery (no utility power) Online-UPS power capacity exceeded Overload timeout On battery-Input voltage is out of range On battery-No utility power On battery-Battery voltage...