HP Ground Bonding Rack Option Kit Installation Guide
Page 9
...information. Reference 1 2 3 4 5 Item 48.26-cm (19-in ) grounding strap over the grounding lug on the bottom side panel and tighten. Connect a 36.83-cm (14.5-in) and a 15.24-cm (6-in ) grounding strap, and secure it to ... supervisor for this kit) M8 x 20 bolt Installing the ground bonding rack option kit on the bottom side panel. 4. Installing the HP Ground Bonding Rack Option Kit 9 Insert a T-25 Torx screw through the end of the 15.24-cm ... washer and an M8 hex nut over the grounding lug on HP 10000 G2 Series Rack side panels From the middle system chassis rail to the bottom side...
...information. Reference 1 2 3 4 5 Item 48.26-cm (19-in ) grounding strap over the grounding lug on the bottom side panel and tighten. Connect a 36.83-cm (14.5-in) and a 15.24-cm (6-in ) grounding strap, and secure it to ... supervisor for this kit) M8 x 20 bolt Installing the ground bonding rack option kit on the bottom side panel. 4. Installing the HP Ground Bonding Rack Option Kit 9 Insert a T-25 Torx screw through the end of the 15.24-cm ... washer and an M8 hex nut over the grounding lug on HP 10000 G2 Series Rack side panels From the middle system chassis rail to the bottom side...
HP Ground Bonding Rack Option Kit Installation Guide
Page 11
.... 3. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the perforated panel and tighten. Installing the ground bonding rack option kit on HP 10000 G2 Series Rack fan kits From the grounding lug on the rack top to the grounding lug on the fan kit...: 1. Place the other top side panel. Place one end of a 15.24-cm (6-in ) grounding strap over the grounding lug on...
.... 3. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the perforated panel and tighten. Installing the ground bonding rack option kit on HP 10000 G2 Series Rack fan kits From the grounding lug on the rack top to the grounding lug on the fan kit...: 1. Place the other top side panel. Place one end of a 15.24-cm (6-in ) grounding strap over the grounding lug on...
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 1
... resources ...7 Rack documentation CD...8 Rack deployment considerations ...8 Levels of rack security ...8 HP 10000 G2 Series rack front doors 8 HP 10000 G2 Series rack rear doors 8 HP Side Panel Option Kit...8 Stabilization requirements ...8 Leveling feet...8 HP 10000 Baying Kit ...9 HP 10000 Stabilizer Kit ...9 HP 10000 Ballast Option Kit ...10 Stabilization for seismic activity ...10 HP 10000 Series Plinth Option Kit 11
... resources ...7 Rack documentation CD...8 Rack deployment considerations ...8 Levels of rack security ...8 HP 10000 G2 Series rack front doors 8 HP 10000 G2 Series rack rear doors 8 HP Side Panel Option Kit...8 Stabilization requirements ...8 Leveling feet...8 HP 10000 Baying Kit ...9 HP 10000 Stabilizer Kit ...9 HP 10000 Ballast Option Kit ...10 Stabilization for seismic activity ...10 HP 10000 Series Plinth Option Kit 11
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 4
...is available for air flow of 65 percent. HP racks and rack accessories ease the centralization, protection, organization, and access to hardware for greater ease-of-use. The 10000 G2 Series rack design is the look; Side panels The side panel design has been updated in favor of high ...value and high volume customers. Table 1 lists the key features of installation. Grounding kit New universal grounding kit supports the 9000, 10000, and 10000 G2 Series racks. HP racks are designed be populated...
...is available for air flow of 65 percent. HP racks and rack accessories ease the centralization, protection, organization, and access to hardware for greater ease-of-use. The 10000 G2 Series rack design is the look; Side panels The side panel design has been updated in favor of high ...value and high volume customers. Table 1 lists the key features of installation. Grounding kit New universal grounding kit supports the 9000, 10000, and 10000 G2 Series racks. HP racks are designed be populated...
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 5
... for overhead data center cabling. • Split rear doors provide greater efficiency with respect to service access. • A removable access panel on the rear door provides added flexibility for cable routing out the rear and bottom of the rack. • Velcro straps for accommodating... option. 3 NOTE The following 10000 Series rack models are discontinued: • 10622 • 10636 • 10642 • 10647 • 10842 Specifications The 10000 and 10000 G2 Series racks are graphite-metallic in color and are included in Table 2. Product availability The 10000 Series rack Model ...
... for overhead data center cabling. • Split rear doors provide greater efficiency with respect to service access. • A removable access panel on the rear door provides added flexibility for cable routing out the rear and bottom of the rack. • Velcro straps for accommodating... option. 3 NOTE The following 10000 Series rack models are discontinued: • 10622 • 10636 • 10642 • 10647 • 10842 Specifications The 10000 and 10000 G2 Series racks are graphite-metallic in color and are included in Table 2. Product availability The 10000 Series rack Model ...
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 7
M5&10-32 supported 742 mm Not applicable Not applicable HP 10000 G2 Series racks 10636 G2 10642 G2 10647 G2 Type D Type D Type D 1735.78 mm 2003.5 mm 2285 mm 36U D=1520... distance Overall rack/extension depth Nominal distance from front mtg flange to inside of rear door with extension 10622 G2 Type D 1113.48 mm 22U D=1045# S=1045# 597.3 mm 612.77 mm 1015 mm 63% 915...Rack height max. M6 supplied; weight capacity D=Dynamic/S=Static Rack width: no side panels Rack width: with side panels Rack depth: front to rear door Front door percentage open space Nominal distance from front...
M5&10-32 supported 742 mm Not applicable Not applicable HP 10000 G2 Series racks 10636 G2 10642 G2 10647 G2 Type D Type D Type D 1735.78 mm 2003.5 mm 2285 mm 36U D=1520... distance Overall rack/extension depth Nominal distance from front mtg flange to inside of rear door with extension 10622 G2 Type D 1113.48 mm 22U D=1045# S=1045# 597.3 mm 612.77 mm 1015 mm 63% 915...Rack height max. M6 supplied; weight capacity D=Dynamic/S=Static Rack width: no side panels Rack width: with side panels Rack depth: front to rear door Front door percentage open space Nominal distance from front...
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 10
.... also shipped with the rack provides documentation for installing and optimizing the rack. HP 10000 G2 Series rack front doors All 10000 and 10000 G2 Series rack Models ship with split rear doors). this locking requirement. HP Side Panel Option Kit Side panels aid in providing proper front to have all other rack models. Rear split...
.... also shipped with the rack provides documentation for installing and optimizing the rack. HP 10000 G2 Series rack front doors All 10000 and 10000 G2 Series rack Models ship with split rear doors). this locking requirement. HP Side Panel Option Kit Side panels aid in providing proper front to have all other rack models. Rear split...
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 14
...installed on management arms must not violate their minimum bend radius - HP general guidelines for many reasons including proper airflow. A list of the rack. NOTE 800-mm racks include vertical filler panels for 10000 and 10000 G2 Series racks) may experience abnormally high failure rates. Fiber cables must...a crease in the rack. • Avoid dressing cabling tightly over sharp edges of railing or panels. • Avoid pinching of systems has very few hard rules. The 10000 and 10000 G2 Series rack air flows from the front to installation. • For good visual reference, do not...
...installed on management arms must not violate their minimum bend radius - HP general guidelines for many reasons including proper airflow. A list of the rack. NOTE 800-mm racks include vertical filler panels for 10000 and 10000 G2 Series racks) may experience abnormally high failure rates. Fiber cables must...a crease in the rack. • Avoid dressing cabling tightly over sharp edges of railing or panels. • Avoid pinching of systems has very few hard rules. The 10000 and 10000 G2 Series rack air flows from the front to installation. • For good visual reference, do not...
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 15
... of each rack. It is a CRT or Flat-panel design. Most customers prefer placement of other system components below it is recommended to follow when physically placing components in a 10000 or 10000 G2 Series Rack. For information on the HP Modular Cooling System refer to serviceability of the video system... high in the rack, especially in a single rack, refer to the white paper on high-density deployment on the HP 10000 Series Rack support and ...
... of each rack. It is a CRT or Flat-panel design. Most customers prefer placement of other system components below it is recommended to follow when physically placing components in a 10000 or 10000 G2 Series Rack. For information on the HP Modular Cooling System refer to serviceability of the video system... high in the rack, especially in a single rack, refer to the white paper on high-density deployment on the HP 10000 Series Rack support and ...
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 31
...assemblies or that may not protect the rack and server components in transit. Special shipping considerations Additional requirements for nonqualified components for shipment in a HP 10000 and 10000 G2 Racks mounted on a CTO shock pallet: • The shock pallet is easily installed from potentially falling on a shock pallet are listed below... cantilevered chassis with little or no rear support or any large chassis with hex- Ensure that should be utilized in all front panel mounting hardware and rail/slide connections to any free movement of the component while mounted in the rack.
...assemblies or that may not protect the rack and server components in transit. Special shipping considerations Additional requirements for nonqualified components for shipment in a HP 10000 and 10000 G2 Racks mounted on a CTO shock pallet: • The shock pallet is easily installed from potentially falling on a shock pallet are listed below... cantilevered chassis with little or no rear support or any large chassis with hex- Ensure that should be utilized in all front panel mounting hardware and rail/slide connections to any free movement of the component while mounted in the rack.
Best practices for HP 10000 Series and HP 10000 G2 Series Racks
Page 35
... is to move large equipment racks by yourself. WARNING To reduce the risk of the rack tipping. Pallet jacks may be rolled across a parking area, panels of the receiving site is preferred for a truck to stabilize the rack during movement, or hire professional equipment riggers. 33 For products with adequate height...
... is to move large equipment racks by yourself. WARNING To reduce the risk of the rack tipping. Pallet jacks may be rolled across a parking area, panels of the receiving site is preferred for a truck to stabilize the rack during movement, or hire professional equipment riggers. 33 For products with adequate height...
HP 10000 G2 Series Rack Options Installation Guide
Page 4
...tools ...49 Installing the ground bonding rack option kit on HP 10000 G2 Series Racks 49 Installing the ground bonding rack option kit on HP 10000 G2 Series Rack side panels 55 Installing the ground bonding rack option kit on HP 10000 G2 Series Rack fan kits 57 Installing the ground bonding rack ...option kit on HP 10000 G2 Series Rack 150-mm extension kits ......... 59 Installing ...
...tools ...49 Installing the ground bonding rack option kit on HP 10000 G2 Series Racks 49 Installing the ground bonding rack option kit on HP 10000 G2 Series Rack side panels 55 Installing the ground bonding rack option kit on HP 10000 G2 Series Rack fan kits 57 Installing the ground bonding rack ...option kit on HP 10000 G2 Series Rack 150-mm extension kits ......... 59 Installing ...
HP 10000 G2 Series Rack Options Installation Guide
Page 55
Insert a T-25 Torx screw through the end of the 36.83-cm (14.5-in ) grounding strap over the grounding lug on the bottom side panel and tighten. Place the end of the rail) M8 hex nut M8 Belleville toothed washer Facility ground (not included with connectors together. 2. The ...to the middle system chassis rail. 3. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on HP 10000 G2 Series Rack side panels From the middle system chassis rail to a building facility, contact your building supervisor for this kit) M8 x 20 bolt Installing the ground...
Insert a T-25 Torx screw through the end of the 36.83-cm (14.5-in ) grounding strap over the grounding lug on the bottom side panel and tighten. Place the end of the rail) M8 hex nut M8 Belleville toothed washer Facility ground (not included with connectors together. 2. The ...to the middle system chassis rail. 3. Place an M8 internal serrated lock washer and an M8 hex nut over the grounding lug on HP 10000 G2 Series Rack side panels From the middle system chassis rail to a building facility, contact your building supervisor for this kit) M8 x 20 bolt Installing the ground...
HP 10000 G2 Series Rack Options Installation Guide
Page 57
Installing the ground bonding rack option kit on HP 10000 G2 Series Rack fan kits From the grounding lug on the rack top to the grounding lug on the top side panel. 4. Place one end of a 15.24-cm ... M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the top side panel and tighten. 5. Repeat steps 1 through 4 for the other end of the 15.24-cm (6-in )... grounding strap over the grounding lug on the perforated panel. Place the end of the same grounding strap over the grounding lug on the rack top and tighten....
Installing the ground bonding rack option kit on HP 10000 G2 Series Rack fan kits From the grounding lug on the rack top to the grounding lug on the top side panel. 4. Place one end of a 15.24-cm ... M8 internal serrated lock washer and an M8 hex nut over the grounding lug on the top side panel and tighten. 5. Repeat steps 1 through 4 for the other end of the 15.24-cm (6-in )... grounding strap over the grounding lug on the perforated panel. Place the end of the same grounding strap over the grounding lug on the rack top and tighten....
HP 10000 G2 Series Rack Options Installation Guide
Page 59
.... Installing the ground bonding rack option kit on the extension kit. 3. Place the other end of the same grounding strap over the grounding lug on HP 10000 G2 Series Rack 150-mm extension kits 1. Insert a T-25 Torx screw through one end of the 36.83-cm (14.5 in ) grounding strap, and ... extension kit. Insert a T-25 Torx screw through the end of a 15.24-cm (6-in ) grounding strap, and secure it to the bottom rack side panel: 1. Place an M8 hex nut over the grounding lug on HP 10000 G2 Series Rack 200-mm extension kits From the extension kit to the rear rack chassis. 2.
.... Installing the ground bonding rack option kit on the extension kit. 3. Place the other end of the same grounding strap over the grounding lug on HP 10000 G2 Series Rack 150-mm extension kits 1. Insert a T-25 Torx screw through one end of the 36.83-cm (14.5 in ) grounding strap, and ... extension kit. Insert a T-25 Torx screw through the end of a 15.24-cm (6-in ) grounding strap, and secure it to the bottom rack side panel: 1. Place an M8 hex nut over the grounding lug on HP 10000 G2 Series Rack 200-mm extension kits From the extension kit to the rear rack chassis. 2.
HP 10000 G2 Series Rack Options Installation Guide
Page 116
Side Panel kit 116 Required tools No tools are required for your convenience. Side Panel kit About this procedure. Kit contents Item Top side panel Middle side panel Bottom side panel Key Quantity 2 2 2 2 This kit might contain extra hardware for this device The HP Side Panel kit enables you to attach side panels to HP 10000 G2 Series Racks.
Side Panel kit 116 Required tools No tools are required for your convenience. Side Panel kit About this procedure. Kit contents Item Top side panel Middle side panel Bottom side panel Key Quantity 2 2 2 2 This kit might contain extra hardware for this device The HP Side Panel kit enables you to attach side panels to HP 10000 G2 Series Racks.
HP Modular Cooling System: water cooling technology for high-density server installations
Page 10
...when a wheel of specified diameter and width is expressed in the "For more information" section. This value is rolled across the panel Computed by dividing total equipment weight by the area of the HP MCS. There are moved into position. Floor loading in raised floor facilities Weight is one of each... floor panel) that is not only a function of the weight, but also of the positioning of the HP MCS, which includes all packaging materials such as they are two basic ways to deploy the HP MCS: • As a stand-alone unit • Adjacent to an existing row of HP 10000 Series G2 cabinets ...
...when a wheel of specified diameter and width is expressed in the "For more information" section. This value is rolled across the panel Computed by dividing total equipment weight by the area of the HP MCS. There are moved into position. Floor loading in raised floor facilities Weight is one of each... floor panel) that is not only a function of the weight, but also of the positioning of the HP MCS, which includes all packaging materials such as they are two basic ways to deploy the HP MCS: • As a stand-alone unit • Adjacent to an existing row of HP 10000 Series G2 cabinets ...
HP 10000 G2 Series Rack User Guide
Page 3
...Removing the rack doors ...11 Removing the front door ...11 Removing the rear doors ...13 Removing the side panels ...13 Stabilizing requirements ...15 Rack stabilizer option kit...16 Rack baying option kit ...17 Rack tie-down ...HP G2 rack specifications ...25 HP 10622 G2 Rack specifications...25 HP 10636 G2 Rack specifications...25 HP 10642 G2 Rack specifications...25 HP 10647 G2 Rack specifications...25 HP 10642 1200 mm Full Frame Rack specifications 25 HP 10647 1200 mm Full Frame Rack specifications 26 HP 10842 G2 Rack specifications...26 HP 10642 Extended Depth Rack specifications 26 HP...
...Removing the rack doors ...11 Removing the front door ...11 Removing the rear doors ...13 Removing the side panels ...13 Stabilizing requirements ...15 Rack stabilizer option kit...16 Rack baying option kit ...17 Rack tie-down ...HP G2 rack specifications ...25 HP 10622 G2 Rack specifications...25 HP 10636 G2 Rack specifications...25 HP 10642 G2 Rack specifications...25 HP 10647 G2 Rack specifications...25 HP 10642 1200 mm Full Frame Rack specifications 25 HP 10647 1200 mm Full Frame Rack specifications 26 HP 10842 G2 Rack specifications...26 HP 10642 Extended Depth Rack specifications 26 HP...
HP 10000 G2 Series Rack User Guide
Page 6
Check the TMRA for each piece of components in the HP 10000 G2 Series Rack: Configuration factors 6 Do not block the ventilation apertures. Populating your new rack Before populating your rack configuration: • The power load must ...gaps with that option. Power requirements When planning for power distribution requirements for your new rack, you must plan the placement of each component. Blanking panels If the front of Electronic Computer/Data Processing Equipment (NFPA-75, 1992). This equipment is not completely filled with local and regional electrical regulations ...
Check the TMRA for each piece of components in the HP 10000 G2 Series Rack: Configuration factors 6 Do not block the ventilation apertures. Populating your new rack Before populating your rack configuration: • The power load must ...gaps with that option. Power requirements When planning for power distribution requirements for your new rack, you must plan the placement of each component. Blanking panels If the front of Electronic Computer/Data Processing Equipment (NFPA-75, 1992). This equipment is not completely filled with local and regional electrical regulations ...
HP 10000 G2 Series Rack User Guide
Page 13
Unlock the doors and open them from damage. Lift the rear doors off of the hinge brackets, and remove them . 2. Removing the side panels NOTE: The side panels come preinstalled on the bottom hinge pin for component installation 13 Preparing the rack for each door. 3. Store the doors in an upright position, taking care to protect them from the rack (2). Open the hinge brackets (1) by pulling up on the top hinge pin and pulling down on all HP 10622 G2 Racks. Removing the rear doors 1.
Unlock the doors and open them from damage. Lift the rear doors off of the hinge brackets, and remove them . 2. Removing the side panels NOTE: The side panels come preinstalled on the bottom hinge pin for component installation 13 Preparing the rack for each door. 3. Store the doors in an upright position, taking care to protect them from the rack (2). Open the hinge brackets (1) by pulling up on the top hinge pin and pulling down on all HP 10622 G2 Racks. Removing the rear doors 1.