CAT 5000
Page 2
...water level, additionally adjust all valves required to provide sophisticated control functions at an affordable price. ALL RIGHTS RESERVED The CAT 5000 chemical automation system has been engineered to provide you with substantially reduced chemical costs and maintenance, improved water quality, ...your location. Our technical support line can also be happy to determine coverage options for your earliest convenience. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. For the purposes of this manual, it is no more challenging than installation of a chemical feeder. FOREWORD ...
...water level, additionally adjust all valves required to provide sophisticated control functions at an affordable price. ALL RIGHTS RESERVED The CAT 5000 chemical automation system has been engineered to provide you with substantially reduced chemical costs and maintenance, improved water quality, ...your location. Our technical support line can also be happy to determine coverage options for your earliest convenience. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. For the purposes of this manual, it is no more challenging than installation of a chemical feeder. FOREWORD ...
CAT 5000
Page 4
... hourly at best. The following graph compares typical chlorine levels when chemistry is adjusted manually versus automatically with the CAT 5000 The CAT 5000 revolutionizes the manner in which water quality can monitor water quality, print charts, graphs and logs, change controller ...email, cell phone or PDA. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. The results include elimination of "human error", accurate and reliable maintenance of chemical usage and costs. Monthly charges apply. WATER QUALITY with the CAT 5000 controller: 1 The POOLCOMM website is a subscription based...
... hourly at best. The following graph compares typical chlorine levels when chemistry is adjusted manually versus automatically with the CAT 5000 The CAT 5000 revolutionizes the manner in which water quality can monitor water quality, print charts, graphs and logs, change controller ...email, cell phone or PDA. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. The results include elimination of "human error", accurate and reliable maintenance of chemical usage and costs. Monthly charges apply. WATER QUALITY with the CAT 5000 controller: 1 The POOLCOMM website is a subscription based...
CAT 5000
Page 10
TYPICAL CAT 5000 INSTALLATION DIAGRAM CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. ALL RIGHTS RESERVED POOLCOMM WATER QUALITY MANAGEMENT pH ORP Flow CAT PR015 CAT PR025 pH SENSOR ORP SENSOR pH ORP WATER QUALITY CONTROLLER CAT 5000 pH Feed Cl/Br Feed Alarm MENU UP DOWN ENTER TRANSMIT POOLCOMM CAT CONTROLLERS Influent (to Return Line) Effluent (to Suction) Sample Stream...
TYPICAL CAT 5000 INSTALLATION DIAGRAM CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. ALL RIGHTS RESERVED POOLCOMM WATER QUALITY MANAGEMENT pH ORP Flow CAT PR015 CAT PR025 pH SENSOR ORP SENSOR pH ORP WATER QUALITY CONTROLLER CAT 5000 pH Feed Cl/Br Feed Alarm MENU UP DOWN ENTER TRANSMIT POOLCOMM CAT CONTROLLERS Influent (to Return Line) Effluent (to Suction) Sample Stream...
CAT 5000
Page 12
... Menu is intended for the enduser to manage settings which are accessed on a frequent basis, while the Configuration Menu is divided into two sections; CAT 5000 SETUP & PROGRAMMING The CAT 5000 features a bright, menu-driven vacuum-flourescent display which truly customize the controller to navigate vertically up within the menu structure. UP Used to... web server. SECTION 7. The menu structure is used to setup advanced features which makes setup and programming simple in any lighting conditions. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. ALL RIGHTS RESERVED
... Menu is intended for the enduser to manage settings which are accessed on a frequent basis, while the Configuration Menu is divided into two sections; CAT 5000 SETUP & PROGRAMMING The CAT 5000 features a bright, menu-driven vacuum-flourescent display which truly customize the controller to navigate vertically up within the menu structure. UP Used to... web server. SECTION 7. The menu structure is used to setup advanced features which makes setup and programming simple in any lighting conditions. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. ALL RIGHTS RESERVED
CAT 5000
Page 14
... will automatically return to operate in normal operating mode: Press MENU. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. The sensed pH value as currently calibrated will resume. TO SELECT pH FEED MODE: The CAT 5000 is useful when servicing pH feed equipment, or if pH chemical supply has been depleted...manual on mode allows constant chemical feed for a fixed interval up to find the pH Feed Mode menu item. TO CALIBRATE pH: The CAT 5000 is far more accurate than most liquid test standards, but pH calibration is desired, as well as during initial balancing of the water. ...
... will automatically return to operate in normal operating mode: Press MENU. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. The sensed pH value as currently calibrated will resume. TO SELECT pH FEED MODE: The CAT 5000 is useful when servicing pH feed equipment, or if pH chemical supply has been depleted...manual on mode allows constant chemical feed for a fixed interval up to find the pH Feed Mode menu item. TO CALIBRATE pH: The CAT 5000 is far more accurate than most liquid test standards, but pH calibration is desired, as well as during initial balancing of the water. ...
CAT 5000
Page 16
.... CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. The controller will be required in the acid feed mode by default (when pH exceeds setpoint, the pH chemical feeder is programmed at the factory to the Operating Menu. TO CHANGE THE pH CONTROL MODE: The CAT 5000 is activated). Press ...: Press MENU. ADVANCED CONFIGURATION OPTIONS TO ENTER THE CONFIGURATION SETUP MENU: The configuration setup menu contains features which enable the CAT 5000 to be programmed as the digital flow meter are also activated through menu items. Press ENTER to select acid feed or base feed....
.... CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. The controller will be required in the acid feed mode by default (when pH exceeds setpoint, the pH chemical feeder is programmed at the factory to the Operating Menu. TO CHANGE THE pH CONTROL MODE: The CAT 5000 is activated). Press ...: Press MENU. ADVANCED CONFIGURATION OPTIONS TO ENTER THE CONFIGURATION SETUP MENU: The configuration setup menu contains features which enable the CAT 5000 to be programmed as the digital flow meter are also activated through menu items. Press ENTER to select acid feed or base feed....
CAT 5000
Page 22
Press ENTER to select Hard Reset. The CAT 5000 will reset and perform a diagnostic self-test: Diagnostic Self Check After 10 seconds, the controller will revert to the Configuration Setup Menu. From the Configuration ... and time as setpoints, alarms, pH calibration, etc. Level Sensor Press ENTER to select Input 3 Setup. Press ENTER to confirm the selection. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. DISPLAY SYSTEM INFORMATION: The Display System Info function is provided to the Configuration Setup Menu. From the Configuration Setup Menu: Press DOWN to...
Press ENTER to select Hard Reset. The CAT 5000 will reset and perform a diagnostic self-test: Diagnostic Self Check After 10 seconds, the controller will revert to the Configuration Setup Menu. From the Configuration ... and time as setpoints, alarms, pH calibration, etc. Level Sensor Press ENTER to select Input 3 Setup. Press ENTER to confirm the selection. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. DISPLAY SYSTEM INFORMATION: The Display System Info function is provided to the Configuration Setup Menu. From the Configuration Setup Menu: Press DOWN to...
CAT 5000
Page 24
SECTION 9. ALL RIGHTS RESERVED CAT 5000 MENU TREE Default Operating Mode pH Setpoint 7.0 to 8.0 (Default 7.5) pH Calibrate Plus or Minus 2.0 pH pH Feed Mode Automatic Off On for Specified Time ORP ... pH Setpoint 0.0 to 14.0 Default 7.5 Aux ORP Setpoint 400 to 995 mV Default 650 mV Alarm Setup Audible and Visual, Visual Only CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
SECTION 9. ALL RIGHTS RESERVED CAT 5000 MENU TREE Default Operating Mode pH Setpoint 7.0 to 8.0 (Default 7.5) pH Calibrate Plus or Minus 2.0 pH pH Feed Mode Automatic Off On for Specified Time ORP ... pH Setpoint 0.0 to 14.0 Default 7.5 Aux ORP Setpoint 400 to 995 mV Default 650 mV Alarm Setup Audible and Visual, Visual Only CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
CAT 5000
Page 26
...switch panel. For optimum controller performance, replace with Health Department requirements using a quality manual test kit. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. To maintain a consistent sanitizer residual in this manual. SENSOR MAINTENANCE The sensors must be used to calibrate...bather load and other facilityspecific characteristics. SECTION 10. Cleaning of most liquid-standard water testing kits. MAINTENANCE CAT 5000 CONTROLLER PACKAGE The CAT 5000 controller unit is important to note that the sensors are engineered to ORP. Therefore, it may need ...
...switch panel. For optimum controller performance, replace with Health Department requirements using a quality manual test kit. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. To maintain a consistent sanitizer residual in this manual. SENSOR MAINTENANCE The sensors must be used to calibrate...bather load and other facilityspecific characteristics. SECTION 10. Cleaning of most liquid-standard water testing kits. MAINTENANCE CAT 5000 CONTROLLER PACKAGE The CAT 5000 controller unit is important to note that the sensors are engineered to ORP. Therefore, it may need ...
CAT 5000
Page 28
...and enter the address to install it and press the transmit data button. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. ALL RIGHTS RESERVED To learn more or to be generated. Test w/ a CAT 5000 The best way to check for Reflex coverage at about half the broadcast power output of the... locations a portable does not. Check the Web Site Visit the Sky-Tel web site and enter the exact address of the CAT 5000. Place the CAT 5000 unit where you find your email address has been entered under Notifications and that location. SECTION 11. TESTING FOR NETWORK COVERAGE Check...
...and enter the address to install it and press the transmit data button. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC. ALL RIGHTS RESERVED To learn more or to be generated. Test w/ a CAT 5000 The best way to check for Reflex coverage at about half the broadcast power output of the... locations a portable does not. Check the Web Site Visit the Sky-Tel web site and enter the exact address of the CAT 5000. Place the CAT 5000 unit where you find your email address has been entered under Notifications and that location. SECTION 11. TESTING FOR NETWORK COVERAGE Check...
CAT 5000
Page 30
... The status symbol indicates the 24 hour alarm status of facilities automated with the latest data from the CAT 5000, click the Get Data link at the bottom page. This will bring up the Account Unit Management Screen, which... allows you to the CAT 5000 controller. Yellow: A warning condition has been corrected during the past 24 hours. From the Unit Profile, the ... Facility name, location and time zone information. Red: A warning condition currently exists. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
... The status symbol indicates the 24 hour alarm status of facilities automated with the latest data from the CAT 5000, click the Get Data link at the bottom page. This will bring up the Account Unit Management Screen, which... allows you to the CAT 5000 controller. Yellow: A warning condition has been corrected during the past 24 hours. From the Unit Profile, the ... Facility name, location and time zone information. Red: A warning condition currently exists. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
CAT 5000
Page 32
... compatible. ALL RIGHTS RESERVED Sprint PCS Your cell phone's e-mail address: 10-digit cell phone [email protected] The PCS Vision Plan will allow your CAT 5000 locations. T-Mobile Your cell phone's e-mail address: 10-digit cell phone [email protected] All phones are text message compatible. Verizon Wireless Your cell phone... phone [email protected] All phones are text message compatible. You can provide email alerts through every major cell phone provider. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
... compatible. ALL RIGHTS RESERVED Sprint PCS Your cell phone's e-mail address: 10-digit cell phone [email protected] The PCS Vision Plan will allow your CAT 5000 locations. T-Mobile Your cell phone's e-mail address: 10-digit cell phone [email protected] All phones are text message compatible. Verizon Wireless Your cell phone... phone [email protected] All phones are text message compatible. You can provide email alerts through every major cell phone provider. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
CAT 5000
Page 34
...is running and that water is still sounding check flow sensor for obstruction or calcification. KEY INSERTED When a service technician visits the CAT 5000 he may need to be increased to keep up with a flow sensor to prevent the controller from continuing to send a No ... feeder has become clogged or broken. ORP OVERFEED The ORP Overfeed timeout occurs when the CAT 5000 has been feeding chemical for immediate viewing and generates a service request alarm. NO FLOW The CAT 5000 is above the sensor, check the sensor for obstruction. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
...is running and that water is still sounding check flow sensor for obstruction or calcification. KEY INSERTED When a service technician visits the CAT 5000 he may need to be increased to keep up with a flow sensor to prevent the controller from continuing to send a No ... feeder has become clogged or broken. ORP OVERFEED The ORP Overfeed timeout occurs when the CAT 5000 has been feeding chemical for immediate viewing and generates a service request alarm. NO FLOW The CAT 5000 is above the sensor, check the sensor for obstruction. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
CAT 5000
Page 36
...CONTACT AUX 2 DRY CONTACT pH FEED L NE CL/BR FEED L NE LINE ! ADDENDUM FOR UL LISTED MODELS CAT 5000 - Disconnect power at circuit breaker. 2. Connect the CAT 5000 controller and powered outputs as shown in conformance with local and national electrical codes using 18 gauge solid copper wire....Block Wiring Instructions The CAT 5000 UL listed controller must be installed in the wiring diagram below : 1. SECTION 17. Reinstall the CAT 5000 cover, power on the controller, and test for line , powered pH feed, and powered CL/BR feed. 4. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
...CONTACT AUX 2 DRY CONTACT pH FEED L NE CL/BR FEED L NE LINE ! ADDENDUM FOR UL LISTED MODELS CAT 5000 - Disconnect power at circuit breaker. 2. Connect the CAT 5000 controller and powered outputs as shown in conformance with local and national electrical codes using 18 gauge solid copper wire....Block Wiring Instructions The CAT 5000 UL listed controller must be installed in the wiring diagram below : 1. SECTION 17. Reinstall the CAT 5000 cover, power on the controller, and test for line , powered pH feed, and powered CL/BR feed. 4. CONTENTS COPYRIGHT 2010 HAYWARD INDUSTRIES, INC.
CAT 5000
Page 37
...; makes no warranties, either expressed or implied, other than those stated above. After obtaining a Return Merchandise Authorization form, any respect. WARRANTY Hayward® warrants the CAT 5000 automated controller to be free of defects in material and workmanship for a period of five years from date of shipment from our factory or authorized ...
...; makes no warranties, either expressed or implied, other than those stated above. After obtaining a Return Merchandise Authorization form, any respect. WARRANTY Hayward® warrants the CAT 5000 automated controller to be free of defects in material and workmanship for a period of five years from date of shipment from our factory or authorized ...