Design Manual
Page 3
Lineup of MRVII system 1.1 Indoor/outdoor models Indoor units Type 4-way cassette type PB-700IB 4-way cassette type PB-950JB 4-way cassette type PB-950IB AB*MCERA 092 AB*MCERA 182 AB*MEERA 182 Low ESP duct type AD*MLERA 072 Model 122 162 242 282 302 382 482 242 282 302 382 482 092 122 162 182 242 Med ESP ...*MHERA 182 242 282 302 382 482 722 962 Convertible type AC*MC/FERA 092 122 162 182 242 382 482 Wall mounted type AS*MC/AERA 072 092 122 162 182 242 Console type AF*MAERA 072 092 122 182 Outdoor units Type Model 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 28HP 30HP AV*MVERA 08N...
Lineup of MRVII system 1.1 Indoor/outdoor models Indoor units Type 4-way cassette type PB-700IB 4-way cassette type PB-950JB 4-way cassette type PB-950IB AB*MCERA 092 AB*MCERA 182 AB*MEERA 182 Low ESP duct type AD*MLERA 072 Model 122 162 242 282 302 382 482 242 282 302 382 482 092 122 162 182 242 Med ESP ...*MHERA 182 242 282 302 382 482 722 962 Convertible type AC*MC/FERA 092 122 162 182 242 382 482 Wall mounted type AS*MC/AERA 072 092 122 162 182 242 Console type AF*MAERA 072 092 122 182 Outdoor units Type Model 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 28HP 30HP AV*MVERA 08N...
Design Manual
Page 7
Products code explanation Outdoor unit: Model: A V 10 N M V E R A Climate type: T1 Design number: A stands for fixed frequency type, H stands for inverter type, R stands for DC inverter and R410A type Cooling or heating, and refrigerant: E stands for heat pump type, refrigerant is R410a Appearance character Product series: M stands for MRV II R410A Applicable voltage: 2 stands for 220~230V/50Hz, N stand for 380~400VAC/50Hz Capacity,10=10HP Product type : "V" stands for MRVII R410A outdoor Indoor unit: Model: A B 09 2 M C E R A Haier Air Conditioner Climate...
Products code explanation Outdoor unit: Model: A V 10 N M V E R A Climate type: T1 Design number: A stands for fixed frequency type, H stands for inverter type, R stands for DC inverter and R410A type Cooling or heating, and refrigerant: E stands for heat pump type, refrigerant is R410a Appearance character Product series: M stands for MRV II R410A Applicable voltage: 2 stands for 220~230V/50Hz, N stand for 380~400VAC/50Hz Capacity,10=10HP Product type : "V" stands for MRVII R410A outdoor Indoor unit: Model: A B 09 2 M C E R A Haier Air Conditioner Climate...
Design Manual
Page 9
... efficiency compressor The compressor is high efficiency and low noise. And the built-in part is made of capacity control to follow variation in cooling and heating mode. Stable operation and reliable performance. 5.4 Intelligent electric control, with the inverter controller and able to change the rotation rate to meet load fluctuation and indoor unit individual control. 5.2 Large diameter fan blade The 3-blade fan on outdoor unit is protected by the DC bruchless motor...
... efficiency compressor The compressor is high efficiency and low noise. And the built-in part is made of capacity control to follow variation in cooling and heating mode. Stable operation and reliable performance. 5.4 Intelligent electric control, with the inverter controller and able to change the rotation rate to meet load fluctuation and indoor unit individual control. 5.2 Large diameter fan blade The 3-blade fan on outdoor unit is protected by the DC bruchless motor...
Design Manual
Page 10
In cooling mode, the refrigerant will be cooled further after being condensed to enhance the over cooling state. And the indoor total capacity can be 50%~130% of indoor can be chosen for different requirements. If there are multiple outdoors, the outdoors will be in running by turns, much longer life. Multiple types of outdoor capacity. up to 64 sets of indoor 5.7 More optional outdoor capacity The...
In cooling mode, the refrigerant will be cooled further after being condensed to enhance the over cooling state. And the indoor total capacity can be 50%~130% of indoor can be chosen for different requirements. If there are multiple outdoors, the outdoors will be in running by turns, much longer life. Multiple types of outdoor capacity. up to 64 sets of indoor 5.7 More optional outdoor capacity The...
Design Manual
Page 11
... on the restrictions of the use of hazardous substances in conformance with RoHS directive. c. Heating operation condition: indoor temp is 200DB, outdoor temp is 270CDB/190CWB; outdoor temp is error such as the previous state. 5.10 Reliable performance a. b. Auto diagnose function The PCB will indicate failure code via the LED or the wired controller. G R U P A d.o.o. 11 High COP High efficiency and great energy saving are the purchased aim...
... on the restrictions of the use of hazardous substances in conformance with RoHS directive. c. Heating operation condition: indoor temp is 200DB, outdoor temp is 270CDB/190CWB; outdoor temp is error such as the previous state. 5.10 Reliable performance a. b. Auto diagnose function The PCB will indicate failure code via the LED or the wired controller. G R U P A d.o.o. 11 High COP High efficiency and great energy saving are the purchased aim...
Design Manual
Page 16
Heating capacity at low temp.(KW) 2.5 3.2 5.0 6.3 ---- (2.1/9.55) 4.0 5.0 Electri- Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Specifications Indoor units 4-way cassette type Model AB092MCERA AB122MCERA AB162MCERA AB182MEERA Nominal cooling capacity(KW) 2.8 3.6 4.5 5.6 Nominal heating capacity(KW) 3.2 4.0 Electrical heating power(KW) /Current(A) ---- ---- Exterior dimensions(mm) 660*570*260 660*570*260 660*570*260 840*840*240 Panel exterior dimensions(mm) 700*700*60 700*700*60...
Heating capacity at low temp.(KW) 2.5 3.2 5.0 6.3 ---- (2.1/9.55) 4.0 5.0 Electri- Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Specifications Indoor units 4-way cassette type Model AB092MCERA AB122MCERA AB162MCERA AB182MEERA Nominal cooling capacity(KW) 2.8 3.6 4.5 5.6 Nominal heating capacity(KW) 3.2 4.0 Electrical heating power(KW) /Current(A) ---- ---- Exterior dimensions(mm) 660*570*260 660*570*260 660*570*260 840*840*240 Panel exterior dimensions(mm) 700*700*60 700*700*60...
Design Manual
Page 17
... Fan type and Qty centrifugal*1 Fan Fan motor output(KW) characteris- static pressure(Pa) ---- ---- ---- ---- ---- Indoor units 4-way cassette type Model AB242MEERA AB282MEERA AB302MEERA AB382MEERA AB482MEERA Nominal cooling capacity(KW) 7.1 8.0 9.0 11.2 14.0 Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) 8.0 (2.1/9.55) 9.0 (2.1/9.55) 10.0 (2.7/12.3) 12.5 (2.7/12.3) 16.0 (2.7/12.3) Heating capacity at low temp.(KW) 6.3 7.1 8.0 10.0 12.5 Electrical Power source(PH,V,Hz) chara- Norminal condition: indoor temperature (cooling...
... Fan type and Qty centrifugal*1 Fan Fan motor output(KW) characteris- static pressure(Pa) ---- ---- ---- ---- ---- Indoor units 4-way cassette type Model AB242MEERA AB282MEERA AB302MEERA AB382MEERA AB482MEERA Nominal cooling capacity(KW) 7.1 8.0 9.0 11.2 14.0 Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) 8.0 (2.1/9.55) 9.0 (2.1/9.55) 10.0 (2.7/12.3) 12.5 (2.7/12.3) 16.0 (2.7/12.3) Heating capacity at low temp.(KW) 6.3 7.1 8.0 10.0 12.5 Electrical Power source(PH,V,Hz) chara- Norminal condition: indoor temperature (cooling...
Design Manual
Page 18
... Weight(panel, net/gross, Kg) 6/9 6/9 6/9 6/9 Expansion mode Electronic expansion valve Controller Wired controller/ wireless controller (optional) Gas piping(mm) 12.7 Piping dimension Liquid piping(mm) 6.35 Drain hose(mm) 32 15.88 9.52 32 15.88 9.52 32 15.88 9.52 32 Noise level(dB(A)) H/M/L 34/32/30 35/34/31 37/35/31 37/35/31 G R U P A d.o.o. static pressure(Pa) ---- ---- ---- ---- Operating current(A) cteristics Power consumption(KW) Fan type...
... Weight(panel, net/gross, Kg) 6/9 6/9 6/9 6/9 Expansion mode Electronic expansion valve Controller Wired controller/ wireless controller (optional) Gas piping(mm) 12.7 Piping dimension Liquid piping(mm) 6.35 Drain hose(mm) 32 15.88 9.52 32 15.88 9.52 32 15.88 9.52 32 Noise level(dB(A)) H/M/L 34/32/30 35/34/31 37/35/31 37/35/31 G R U P A d.o.o. static pressure(Pa) ---- ---- ---- ---- Operating current(A) cteristics Power consumption(KW) Fan type...
Design Manual
Page 19
... condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Indoor units 4-way cassette type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power...
... condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Indoor units 4-way cassette type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power...
Design Manual
Page 20
... condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Operating current(A) cteristics Power consumption(KW) Fan characteristic Fan type Fan motor output(KW) Standard airflow(m3/h) Standard static pressure(Pa) Max. Indoor units Ceiling concealed type Model...
... condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Operating current(A) cteristics Power consumption(KW) Fan characteristic Fan type Fan motor output(KW) Standard airflow(m3/h) Standard static pressure(Pa) Max. Indoor units Ceiling concealed type Model...
Design Manual
Page 21
...) Max. Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Indoor units Ceiling concealed type Model AD162MLERA AD182MLERA AD242MLERA Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at...
...) Max. Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Indoor units Ceiling concealed type Model AD162MLERA AD182MLERA AD242MLERA Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at...
Design Manual
Page 22
Indoor units Med static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- Standard airflow(m3/h) tics Standard static pressure(Pa) Max. Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB ...
Indoor units Med static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- Standard airflow(m3/h) tics Standard static pressure(Pa) Max. Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB ...
Design Manual
Page 23
... condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level. Indoor units Med static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating...
... condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level. Indoor units Med static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating...
Design Manual
Page 24
... Standard static pressure(Pa) Max. Indoor units High static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- It is a sound pressure noise level. static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/L AD182MHERA 5.6 6.3 2.6/11.9 5.0 AD242MHERA...
... Standard static pressure(Pa) Max. Indoor units High static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- It is a sound pressure noise level. static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/L AD182MHERA 5.6 6.3 2.6/11.9 5.0 AD242MHERA...
Design Manual
Page 25
Indoor units High static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/L AD302MHERA 9.0 10.0 ---8.0 AD382MHERA 11.2 12.5 ---10.0 1PH, 220~230V, 50Hz AD482MHERA 14.0 16.0 ---12...
Indoor units High static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/L AD302MHERA 9.0 10.0 ---8.0 AD382MHERA 11.2 12.5 ---10.0 1PH, 220~230V, 50Hz AD482MHERA 14.0 16.0 ---12...
Design Manual
Page 26
It is a sound pressure noise level. Indoor units High static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/L AD722MHERA 22.6 25 ----1PH, 220~230V, 50Hz AD962MHERA 28...
It is a sound pressure noise level. Indoor units High static pressure duct type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/L AD722MHERA 22.6 25 ----1PH, 220~230V, 50Hz AD962MHERA 28...
Design Manual
Page 27
... Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Standard airflow(m3/h) tics Standard static pressure(Pa) Max. Indoor units Convertible type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power...
... Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Standard airflow(m3/h) tics Standard static pressure(Pa) Max. Indoor units Convertible type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power...
Design Manual
Page 28
.../49 Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Indoor units Convertible type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara...
.../49 Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Indoor units Convertible type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara...
Design Manual
Page 29
... Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Indoor units Wall mounted type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Heating capacity...
... Norminal condition: indoor temperature (cooling): 270CDB/190CWB, indoor temperature (heating): 200CDB/14.50CWB Outdoor temperature(cooling): 350CDB/240CWB, outdoor temperature(heating): 70CDB/60CWB The noise level will be measured in the third octave band limited values in the semi-anechoic chamber, using a Real Time Analyser calibrated sound intensity meter. Operating current(A) cteristics Power consumption(KW) Fan type and Qty Fan Fan motor output(KW) characteris- Indoor units Wall mounted type Model Nominal cooling capacity(KW) Nominal heating capacity(KW) Heating capacity...
Design Manual
Page 116
... adapter. 3. range: -30¡ ¡«52¡ Ambient temperature of controller: -30¡ ¡«52¡ Ambient humidity of system in group as the request; Set the parameter of controller: -30¡ ¡«52¡ Save temp. start or stop a certain indoor individually, or in time; Management system H-CACSII BMS system H-CACS transfer the data of air conditioner...
... adapter. 3. range: -30¡ ¡«52¡ Ambient temperature of controller: -30¡ ¡«52¡ Ambient humidity of system in group as the request; Set the parameter of controller: -30¡ ¡«52¡ Save temp. start or stop a certain indoor individually, or in time; Management system H-CACSII BMS system H-CACS transfer the data of air conditioner...