Service Manual - Page 3

... working condition Type of Conditioner Cooling Only Heat pump Air T1 18 ℃~43℃ -7℃~43℃ Electricity Heating ~43℃ Climate type T2 10℃~35℃ -7℃~35℃ ~35℃ T3 21℃~52℃ -7℃~52℃ ~52℃ 1.3 Operating Range of Air Conditioners Temp. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA...
Service Manual - Page 4

Long-life& high efficiency air purify filter Low temperature cooling realized, super low temperature heating ..., which is protective for you. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA 1.4 Product features Adopt the much friendlier refrigerant R410a The air conditioner system adopts the greatly friendly refrigerant R410a, which can be controlled by the...
Service Manual - Page 5

...) Synthetic oil (POE oil) Synthetic oil (POE oil) Pressure ratio 1 ■Operation flow Approx. 1.6 Approx. 1.1 prepare work schedule refrigerant inspection operation chart preparation 1. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA 1.5 New friendly refrigerant R410A introduction: ■R410A The working pressure of the specified thickness 2.
Service Manual - Page 6

... additional Gas leakage detector Gas leakage test ■Work precautions charging Refrigerant check: Before work requires a number of special tools (* symbol). Additional refrigerant: Charge a suitable amount of refrigerant piping to the refrigerant. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA ■Piping material 1. For the pipe wall thickness...
Service Manual - Page 7

SPECIFICATION item Mode Function Capacity kW Sensible heat ratio Total power input W ...215;199 1150×750×300 PVC 18/20 Remote 46/44/42 28.3/34.3 7 Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA 2. power input W EER or COP W/W Dehumidifying capacity 10‐³×m³/h Power cable Power source N, V, Hz Running A / A ...
Service Manual - Page 8

...Four way valve SHF-4-10A material of reduce noise XPE crankcase heater power Weight(Net / Shipping) Refrigerant Type / Charge Recharge quantity W kg / kg g g/m 37 39/43 R410A 1300 30... a sound pressure noise level. 8 Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA Item Model Function Capacity kW Sensible heat ratio Total power input W Max.
Service Manual - Page 10

... the following information in some cases may result in injuries or machine damages; Incorrect maintenance and repairment may cause electrical shock or fire hazard. CAUTION! Incorrect operations may cause serious consequences. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA 3. Don't dismantle the outlet of firing), please cut off After the unit...
Service Manual - Page 11

...correct earthing may cause fire hazard. Earthing wire should be connected to ensure efficient discharge. Incorrect pipe use may cause accidents. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA WARNING! Installed electrical-leaking circuit breaker. Earthing Use discharge pipe correctly to the gas pipe, water pipe, lightning rod or phone line, in the...
Service Manual - Page 14

Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA 5. Accessories "Edging" for protection of overhead space is needed for installation. Place where noise and hot air may not be discharged. Place surrounded at the same time, obtain a consent from an opening edge. Place where air circulates. Place where there is a possibility. A 1m or more of ...
Service Manual - Page 17

... crimped terminal lugs with the indoor units, see the corresponding indoor operation and instruction manual. For the detailed wiring connection with insulated grip on the ends of power ... Wiring connection Make wiring to supply power to the terminal block. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA Electric wiring WARNING! Precautions for the indoor unit is ...
Service Manual - Page 22

... the drain hose in (Fig.3). (Fig. 3) Arrange the drain hose lower than this direction.) 22 Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA 5.2.2 AC122ACERA INSTALLATION PROCEDURE Install the room air conditioning unit as Fig.4, at the position shown. (Fig. 4) Wall 7cm Indoor unit 6mm outdoor unit 2. DRILLING FOR PIPING The piping and drain can exit...
Service Manual - Page 33

sensor Tci compressor 2-way stop valve (air side) 33 Refrigerant circuit Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA defrost temp. sensor Tc evaporator indoor ambient temp. sensor Tao assistant main ... condenser outdoor ambient temp. sensor Tai 3-way stop valve (liquid side) indoor coil temp. Commercial Air Conditioner 8. sensor Td low pressure switch condenser...
Service Manual - Page 41

Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA Trouble description Display of LED borad Analyze and diagnose LED 5-4-3-2-1 IPM failure 00001 IPM failure Abnormal of DC moter Communication error between indoor and outdoor unit Compressor discharging temprerture protection Spdu / IPM module over current protection Abnormal of outdoor ambient sensor Abnormal of ...
Service Manual - Page 58

... failure is switched on for 3 times continously. Commercial Air Conditioner Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA 3) Outdoor DC motor abnormal Alarm condition: outdoor DC motor is normal yes replace sensor replace PCB 58 outdoor indicator indicate the above failure yes check if refrigerant is too much or too less adjust refrigerant no check if the system piping is blocked...
Service Manual - Page 60

Commercial Air Conditioner 10) Communication failure between outdoor PCB and module outdoor indicator flashes 22 times Model: AU122AEERA AB122ACERA AC122ACERA AD122ALERA no compressor not start up, outdoor alarms, check if there is other failure yes no check if the wiring between outdoor PCB and module is correct yes replace PCB eliminate other failures adjust wiring no...

Haier AU122AEERA Reviews

Do you have an experience with the Haier AU122AEERA that you would like to share?
Earn 750 points for your review!
We have not received any reviews for Haier yet.

Popular Haier AU122AEERA Search Terms

The following terms are frequently used to search for Haier AU122AEERA support:

Ask a New Question
Use the box below to post a new question about Haier AU122AEERA.
Manuals / Documents
Download any of our Haier AU122AEERA manuals for free!

We have the following 1 documents available for the Haier AU122AEERA:
  • Service Manual

Points & Prizes
  • You can earn points for nearly everything you do on HelpOwl.com
  • You can trade in those points for gift cards at leading retailers such as Amazon.com and Walmart
  • It's that simple!
See How it Works
Create a Free Account

Haier Manuals

Find free Haier AU122AEERA manuals and user guides available at ManualOwl.com. Try out our unique manual viewer allowing you to interact with manuals from directly within your browser!

Haier Reviews

View thousands of Haier AU122AEERA user reviews and customer ratings available at ReviewOwl.com.

Contact Information

Complete Haier customer service contact information including steps to reach representatives, hours of operation, customer support links and more from ContactHelp.com.

Scoreboard Ratings

See detailed Haier customer service rankings, employee comments and much more from our sister site.

Haier Recalls

Find comprehensive Haier recall information updated hourly on RecallOwl.com.