User Manual
Page 1
CASSETTE TYPE AIR CONDITIONER Operation & Installation Manual AB122ACEAA AB182ACEAA AB242ACEAA AB242AEEAA AB282ACEAA AB282AEEAA AB362ACEAA AB422AEEAA AB482ACEAA AB482AEEAA AB602ACEAA AB122ACERA AB182ACERA AB242ACERA AB242AEERA AB282AEERA AB362ACERA AB362AEERA AB482AEERA AB602ACERA No.0010577963 F Please read this manual carefully and safely. Please keep this operation manual before using the air conditioner.
CASSETTE TYPE AIR CONDITIONER Operation & Installation Manual AB122ACEAA AB182ACEAA AB242ACEAA AB242AEEAA AB282ACEAA AB282AEEAA AB362ACEAA AB422AEEAA AB482ACEAA AB482AEEAA AB602ACEAA AB122ACERA AB182ACERA AB242ACERA AB242AEERA AB282AEERA AB362ACERA AB362AEERA AB482AEERA AB602ACERA No.0010577963 F Please read this manual carefully and safely. Please keep this operation manual before using the air conditioner.
User Manual
Page 3
... any question. Use of your new air conditioner may be done by professional conditioner people, don't install unit by insisting on the power cord. Contact your local waste disposal center for the name and 1 All the packaging materials employed in accordance with the relative instructions set forth in the User's Guide carefully. Cautions Disposal of the old air conditioner Before disposing an old air conditioner that goes...
... any question. Use of your new air conditioner may be done by professional conditioner people, don't install unit by insisting on the power cord. Contact your local waste disposal center for the name and 1 All the packaging materials employed in accordance with the relative instructions set forth in the User's Guide carefully. Cautions Disposal of the old air conditioner Before disposing an old air conditioner that goes...
User Manual
Page 4
... the power cable: fingers or any parts of the air conditioner should 14 installed the conveniently reachable pleace for disconnection must be The refrigerating circuit is adaptive in serious eye injuries. 5. In no less 3mm. Applicable ambient temperature range: all-pole switch; For EAA series : 8. Indoor Cooling DB C WB C 27 19 32 23 outdoor DB C WB C 35 24 43 26 Indoor DB C 20 27 Heating...
... the power cable: fingers or any parts of the air conditioner should 14 installed the conveniently reachable pleace for disconnection must be The refrigerating circuit is adaptive in serious eye injuries. 5. In no less 3mm. Applicable ambient temperature range: all-pole switch; For EAA series : 8. Indoor Cooling DB C WB C 27 19 32 23 outdoor DB C WB C 35 24 43 26 Indoor DB C 20 27 Heating...
User Manual
Page 5
... the correct operation of the machine. g. Incorrect maintenance and repairment may cause water leak, electrical shock and fire hazard. Be sure to the new user, this manual should be sure to take measures to prevent suffocation accident even in order to the new user. Otherwise the one will damage the conditioner, and may cause injuries. smell of refrigerant leakage. tioner is installed in order...
... the correct operation of the machine. g. Incorrect maintenance and repairment may cause water leak, electrical shock and fire hazard. Be sure to the new user, this manual should be sure to take measures to prevent suffocation accident even in order to the new user. Otherwise the one will damage the conditioner, and may cause injuries. smell of refrigerant leakage. tioner is installed in order...
User Manual
Page 6
... not be blowed directly in air-conditioner which harm the health of fan is very dangerous which may cause faults or fire accidents. Don't operate the air-conditioner with water. Otherwise will suffer damage. Otherwise may fall down and cause accidents. When use correctly-typed fuse. Inefficient ventilation may settle in the air flow. Otherwise will be placed or used with other materials replacing fuse, otherwise may...
... not be blowed directly in air-conditioner which harm the health of fan is very dangerous which may cause faults or fire accidents. Don't operate the air-conditioner with water. Otherwise will suffer damage. Otherwise may fall down and cause accidents. When use correctly-typed fuse. Inefficient ventilation may settle in the air flow. Otherwise will be placed or used with other materials replacing fuse, otherwise may...
User Manual
Page 7
... to the indoor unit, outdoor unit, power supply wire, connecting wire, pipes, otherwise images may be disturbed or noises be created. TV, radio, acoustic appliances etc are at least 1 m far away to install the air-conditioner. rating noise don't disturb neighbour. Incorrect installation may cause water leaking. CAUTION ! Installed electrical-leaking circuit breaker. After the installation please be equipped with frequent fluctuation of the following conditions. WARNING ! It easily cause electrical shock without circuit breaker. [Location] Air-conditioner should be...
... to the indoor unit, outdoor unit, power supply wire, connecting wire, pipes, otherwise images may be disturbed or noises be created. TV, radio, acoustic appliances etc are at least 1 m far away to install the air-conditioner. rating noise don't disturb neighbour. Incorrect installation may cause water leaking. CAUTION ! Installed electrical-leaking circuit breaker. After the installation please be equipped with frequent fluctuation of the following conditions. WARNING ! It easily cause electrical shock without circuit breaker. [Location] Air-conditioner should be...
User Manual
Page 9
If the environment where the air-con works is full of dust, the air filter should be wash more times than ever ( it is usually twice a week). 1.Get the air inlet grille Look at the same time, pull out the bottom rim of the filter net slightly with wet hand. Maintenance Clean the unit Turn off the power supply switch Do not touch with...
If the environment where the air-con works is full of dust, the air filter should be wash more times than ever ( it is usually twice a week). 1.Get the air inlet grille Look at the same time, pull out the bottom rim of the filter net slightly with wet hand. Maintenance Clean the unit Turn off the power supply switch Do not touch with...
User Manual
Page 12
... avoid reduce the working efficiency. Maintenance Seasonal Reserve Post-season Care Operate the unit with dustcoat. Consult dealer, because clean must be done by technician. 2. The inner part of the unit well. NOTE 1. In cooling operation, discharging system discharge water in stop. Stop operation and turn off the power supply switch .Electric power is consumed even the air conditioner is in room. 10 Clean the air filter, indoor unit and outdoor unit,and cover the unit with FAN mode on during the...
... avoid reduce the working efficiency. Maintenance Seasonal Reserve Post-season Care Operate the unit with dustcoat. Consult dealer, because clean must be done by technician. 2. The inner part of the unit well. NOTE 1. In cooling operation, discharging system discharge water in stop. Stop operation and turn off the power supply switch .Electric power is consumed even the air conditioner is in room. 10 Clean the air filter, indoor unit and outdoor unit,and cover the unit with FAN mode on during the...
User Manual
Page 14
... the outdoor unit is removed (during defrosting operation). Is city supply power normal ? Is the earth leakage breaker in ON position. ON OFF Power supply switch is stopped. Unit fails to turn off the power supply switch immediately and contact the sales dealer. 12 Water or vapor generated from the outdoor unit during drying. Be sure to start. Trouble Shooting Air does not blow or the fan speed cannot be changed during heating. Defrosting operation During heating,indoor fan...
... the outdoor unit is removed (during defrosting operation). Is city supply power normal ? Is the earth leakage breaker in ON position. ON OFF Power supply switch is stopped. Unit fails to turn off the power supply switch immediately and contact the sales dealer. 12 Water or vapor generated from the outdoor unit during drying. Be sure to start. Trouble Shooting Air does not blow or the fan speed cannot be changed during heating. Defrosting operation During heating,indoor fan...
User Manual
Page 15
... window left opened ? Any other heat sources in the room ? Insufficient cooling Sunlight direct into the room ? Too crowed in the room? Horizontal swing louver upward ? (in operation or abnormal sound that is an irregularity in HEAT mode) Any obstacle exists at the air inlet or outlet? When Trouble Happens Insufficient cooling or heating The operation controller adjusted as required Air filter too dirty ? Cooled air blown out ( when heating) When the air conditioner...
... window left opened ? Any other heat sources in the room ? Insufficient cooling Sunlight direct into the room ? Too crowed in the room? Horizontal swing louver upward ? (in operation or abnormal sound that is an irregularity in HEAT mode) Any obstacle exists at the air inlet or outlet? When Trouble Happens Insufficient cooling or heating The operation controller adjusted as required Air filter too dirty ? Cooled air blown out ( when heating) When the air conditioner...
User Manual
Page 16
When Trouble Happens Error display ( For ERA series ) 14 For remote Failure code For central Failure description type, flash on wired control, times controller failure code 1 01(01H) 01D Indoor ambient temp. sensor failure 4 73(49H) 12D Outdoor coil temp. sensor abnormal Sensor broken down or short circuit for more than 2m continuously 15 05(05H) 17D EEPROM abnormal EEPROM data missing 16 84(54H) 26D Pressure abnormal(low pressure) 17...
When Trouble Happens Error display ( For ERA series ) 14 For remote Failure code For central Failure description type, flash on wired control, times controller failure code 1 01(01H) 01D Indoor ambient temp. sensor failure 4 73(49H) 12D Outdoor coil temp. sensor abnormal Sensor broken down or short circuit for more than 2m continuously 15 05(05H) 17D EEPROM abnormal EEPROM data missing 16 84(54H) 26D Pressure abnormal(low pressure) 17...
User Manual
Page 17
... not resumable fault. sensor failure/Compressor Sensor broken down for more than 2m continuously 2 02(02H) 02D Indoor coil temp. When Trouble Happens Error display ( For EAA series ) 15 For remote Failure code For central Failure description type, flash on wired control, times controller failure code Reason Remarks 1 01(01H) 01D Indoor ambient temp. sensor failure Sensor broken down or short circuit for more than 2m continuously 4 73(49H) 12D Outdoor coil temp. sensor failure Sensor broken down...
... not resumable fault. sensor failure/Compressor Sensor broken down for more than 2m continuously 2 02(02H) 02D Indoor coil temp. When Trouble Happens Error display ( For EAA series ) 15 For remote Failure code For central Failure description type, flash on wired control, times controller failure code Reason Remarks 1 01(01H) 01D Indoor ambient temp. sensor failure Sensor broken down or short circuit for more than 2m continuously 4 73(49H) 12D Outdoor coil temp. sensor failure Sensor broken down...
User Manual
Page 18
... the operation manual. Using TIMER mode, you can make the room temperature reach a suitable temperature when you wake up or back home. Too cool or hot is not good for future reference when maintenance and changing installation place. Optimal temperature 16 Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the proper indoor temperature. After installation ,please use timer. Effectively use the air conditioner according to ensure the air conditioner work well. Customer Need-to-know Customer Need-to...
... the operation manual. Using TIMER mode, you can make the room temperature reach a suitable temperature when you wake up or back home. Too cool or hot is not good for future reference when maintenance and changing installation place. Optimal temperature 16 Using Directions Adjust suitable airflow direction Avoid direct sunlight and airflow Keep the proper indoor temperature. After installation ,please use timer. Effectively use the air conditioner according to ensure the air conditioner work well. Customer Need-to-know Customer Need-to...
User Manual
Page 19
... the unit. Incorrect installation will fall down causing injuries. Use exclusive wire for the installation personnel Don't fail to show customers how to machine might happen, if it is no leakage. Fix terminal cover firmly to use specified accessaries and parts. CAUTION! Cover pipe with fire. When install the unit, take in case Earthing dew may be connected to avoid electric shock. All electric work shall...
... the unit. Incorrect installation will fall down causing injuries. Use exclusive wire for the installation personnel Don't fail to show customers how to machine might happen, if it is no leakage. Fix terminal cover firmly to use specified accessaries and parts. CAUTION! Cover pipe with fire. When install the unit, take in case Earthing dew may be connected to avoid electric shock. All electric work shall...
User Manual
Page 21
... all pipings (refrigerant, water drainage), wirings (inter unit cable) to paper pattern for installation if necessary. (when ceiling already exists.) Refer to indoor unit, before installation. Contact your real estate dealer (3) Install a suspending bolt. (Use a M10 bolt) To support the unit weight, anchor bolt shall be prepared in field. 50~100 19 For new ceiling, use built-in type bolt or parts prepared in the case of ceiling hole...
... all pipings (refrigerant, water drainage), wirings (inter unit cable) to paper pattern for installation if necessary. (when ceiling already exists.) Refer to indoor unit, before installation. Contact your real estate dealer (3) Install a suspending bolt. (Use a M10 bolt) To support the unit weight, anchor bolt shall be prepared in field. 50~100 19 For new ceiling, use built-in type bolt or parts prepared in the case of ceiling hole...
User Manual
Page 23
... water hoses shall meet the requirements for gas leakage. For the size of 1-1.5m between suspending brackets, to prevent air bag from unit. Use torque specified in Fig. Insert water pipe into water plug until head of water drain hose (1) shall be a right angle with refrigerant. Connect water hoses with seal. below Specifieations of polyethylent; size: 25mm; If downward slope can't be equal or larger than 280mm. INSTALLATION OF WATER DRAINAGE PIPE (1) Install water drainage pipe Pipe...
... water hoses shall meet the requirements for gas leakage. For the size of 1-1.5m between suspending brackets, to prevent air bag from unit. Use torque specified in Fig. Insert water pipe into water plug until head of water drain hose (1) shall be a right angle with refrigerant. Connect water hoses with seal. below Specifieations of polyethylent; size: 25mm; If downward slope can't be equal or larger than 280mm. INSTALLATION OF WATER DRAINAGE PIPE (1) Install water drainage pipe Pipe...
User Manual
Page 25
When wiring is not complete Remove cover of control box, connect 1PH power to cut off power supply. Method of water charging Self-provided stiff pipe Maintenance Water drainage port for maintenance (Drain water from air outlet 1 Connect with outdoor unit 3 D 2 Terminal block PCB on terminal block.,use remote controller to see water drainage. After wiring Check water drainage in this hole) Inspecting hole 100mm Watering can of a smooth water drainage, be running. Note, in cooling operation. Installation Procedure For series AB242ACEAA, AB242ACERA, AB282ACEAA...
When wiring is not complete Remove cover of control box, connect 1PH power to cut off power supply. Method of water charging Self-provided stiff pipe Maintenance Water drainage port for maintenance (Drain water from air outlet 1 Connect with outdoor unit 3 D 2 Terminal block PCB on terminal block.,use remote controller to see water drainage. After wiring Check water drainage in this hole) Inspecting hole 100mm Watering can of a smooth water drainage, be running. Note, in cooling operation. Installation Procedure For series AB242ACEAA, AB242ACERA, AB282ACEAA...
User Manual
Page 26
... wires of wires, circuit breaker, switches and wiring etc. Upon connecting, replace control box cover (1) and (2). Note: All electric wires have their own poles, poles must be placed face down or against wall, neither on inlet grill and lift it up. (Refer to Fig. 1) 2 Lift it up for the installation Be sure to show customers Operation Manual and guide them how to Fig. 2) (2) Remove cover plate at one side. All wiring work...
... wires of wires, circuit breaker, switches and wiring etc. Upon connecting, replace control box cover (1) and (2). Note: All electric wires have their own poles, poles must be placed face down or against wall, neither on inlet grill and lift it up. (Refer to Fig. 1) 2 Lift it up for the installation Be sure to show customers Operation Manual and guide them how to Fig. 2) (2) Remove cover plate at one side. All wiring work...
User Manual
Page 28
... shortage. Dew or water drop may occur or parts got burned. Is wiring and piping correctly arranged? Problem may occur. It is hard to the following and check after finishing installation,confirm no refrigerant leakage. 26 Is water drainage smooth? Inlet grill can be adjusted into four directions by turning inlet grill. Problem may cause Unit might be a danger of swing flap motor. (2) Install cover plate on the...
... shortage. Dew or water drop may occur or parts got burned. Is wiring and piping correctly arranged? Problem may occur. It is hard to the following and check after finishing installation,confirm no refrigerant leakage. 26 Is water drainage smooth? Inlet grill can be adjusted into four directions by turning inlet grill. Problem may cause Unit might be a danger of swing flap motor. (2) Install cover plate on the...