User Manual
Page 1
1736/1738 Power Logger Users Manual September 2015 © 2015 Fluke Corporation. All rights reserved. Specifications are trademarks of their respective companies. All product names are subject to change without notice.
1736/1738 Power Logger Users Manual September 2015 © 2015 Fluke Corporation. All rights reserved. Specifications are trademarks of their respective companies. All product names are subject to change without notice.
User Manual
Page 4
1736/1738 Users Manual Function Selection Buttons 19 Meter ...19 Live Trend ...19 Scope ...19 Harmonics ...19 Measurement Configuration 20 Connection Verification and Correction 30 Power...31 Logger ...32 ...
1736/1738 Users Manual Function Selection Buttons 19 Meter ...19 Live Trend ...19 Scope ...19 Harmonics ...19 Measurement Configuration 20 Connection Verification and Correction 30 Power...31 Logger ...32 ...
User Manual
Page 11
With a built-in this manual show the 1738. All illustrations in touch screen and USB flash drive support... rotation indication, 2 dc channels (supports user-supplied external sensor for energy and power quality surveys. Introduction The 1736 and 1738 Power Loggers (the Logger or Product) is a compact device for other measurements such as temperature, humidity, and air speed... up to and including the 50th and Total Harmonic Distortion of Voltage and Current Fluke software, Energy Analyze Plus, is easy to configure, verify, and download measurement sessions without the need of the measurement...
With a built-in this manual show the 1738. All illustrations in touch screen and USB flash drive support... rotation indication, 2 dc channels (supports user-supplied external sensor for energy and power quality surveys. Introduction The 1736 and 1738 Power Loggers (the Logger or Product) is a compact device for other measurements such as temperature, humidity, and air speed... up to and including the 50th and Total Harmonic Distortion of Voltage and Current Fluke software, Energy Analyze Plus, is easy to configure, verify, and download measurement sessions without the need of the measurement...
User Manual
Page 12
...national safety codes. Look for cracks or missing plastic. To view, print, or download the latest manual supplement, visit http://us.fluke.com/usen/support/manuals. 1736/1738 Users Manual How to Contact Fluke To contact Fluke, use one of these telephone numbers: • USA: 1-800-760-4523 • Canada: ...1-800-36-FLUKE (1-800-363-5853) • Europe: +31 402-675-200 • Japan: +81-3-6714-3114 •...
...national safety codes. Look for cracks or missing plastic. To view, print, or download the latest manual supplement, visit http://us.fluke.com/usen/support/manuals. 1736/1738 Users Manual How to Contact Fluke To contact Fluke, use one of these telephone numbers: • USA: 1-800-760-4523 • Canada: ...1-800-36-FLUKE (1-800-363-5853) • Europe: +31 402-675-200 • Japan: +81-3-6714-3114 •...
User Manual
Page 14
1736/1738 Users Manual Table 1 is a list of the building's low-voltage MAINS installation. ... Category IV is classed as unsorted municipal waste. 4 WARNING. Spent batteries should be disposed of this manual. Risk of electric shock. Conforms to test and measuring circuits connected at the source of symbols used ...or in domestic household waste. Do not mix with the WEEE Directive marking requirements. Contact your authorized Fluke Service Center for recycling information. This product complies with the solid waste stream. Table 1. Symbols Symbol ...
1736/1738 Users Manual Table 1 is a list of the building's low-voltage MAINS installation. ... Category IV is classed as unsorted municipal waste. 4 WARNING. Spent batteries should be disposed of this manual. Risk of electric shock. Conforms to test and measuring circuits connected at the source of symbols used ...or in domestic household waste. Do not mix with the WEEE Directive marking requirements. Contact your authorized Fluke Service Center for recycling information. This product complies with the solid waste stream. Table 1. Symbols Symbol ...
User Manual
Page 15
Check www.fluke.com for your country. Note The WiFi/BLE adapter is included only when the radio certification is a list of 4 Magnet Probes for 4 mm Banana Plugs ... Card, Safety Information, Battery Pack Safety Information, iFlex Probe Safety Information) • 4 GB USB Flash Drive (includes Users Manual and PC application software, Fluke Energy Analyze Plus) Power Logger Before You Start The 1738 Power Logger also includes these items in the standard purchase list: • WiFi/BLE to USB Adapter • Magnet...
Check www.fluke.com for your country. Note The WiFi/BLE adapter is included only when the radio certification is a list of 4 Magnet Probes for 4 mm Banana Plugs ... Card, Safety Information, Battery Pack Safety Information, iFlex Probe Safety Information) • 4 GB USB Flash Drive (includes Users Manual and PC application software, Fluke Energy Analyze Plus) Power Logger Before You Start The 1738 Power Logger also includes these items in the standard purchase list: • WiFi/BLE to USB Adapter • Magnet...
User Manual
Page 16
... "Energy Analyze Plus" PC software. • Remote control via Virtual Network Computing (VNC). 1736/1738 Users Manual WiFi and WiFi/BLE-to-USB Adapter The USB adapter enables the wireless connectivity of the Logger: • Connection to the Fluke Connect™ smartphone app for more information about VNC. • Display and store data...
... "Energy Analyze Plus" PC software. • Remote control via Virtual Network Computing (VNC). 1736/1738 Users Manual WiFi and WiFi/BLE-to-USB Adapter The USB adapter enables the wireless connectivity of the Logger: • Connection to the Fluke Connect™ smartphone app for more information about VNC. • Display and store data...
User Manual
Page 18
... when subjected to large currents, such as those used to saturate, it . • It has an air core rather than an iron core. 1736/1738 Users Manual Thin-Flexi Current Probe The Thin-Flexi Current Probe works on the Rogowski coil (R-coil) principle that is a toroid of wire used in electric power...
... when subjected to large currents, such as those used to saturate, it . • It has an air core rather than an iron core. 1736/1738 Users Manual Thin-Flexi Current Probe The Thin-Flexi Current Probe works on the Rogowski coil (R-coil) principle that is a toroid of wire used in electric power...
User Manual
Page 20
...6000/3PK i17xx-flex 6000/4PK Fluke-17xx Test Lead Fluke-17xx Test Lead 3PHVL-1730 i40s-EL Current Clamp i40s-EL/3PK Fluke-1730-Hanger Kit 173x AUX Input Adapter C17xx FLUKE-1736/UPGRADE IEEE 519/REPORT ...3 Current Clamps, 40 A Hanger Kit Lithium-ion Battery Soft Case Upgrade Kit for 1736 to 1738 (includes: Hanger, Magnet Probes, 1736 to 1738 Upgrade Kit, and Software License) Software License for IEEE 519 Reporting WiFi/BLE to USB Adapter Set...included accessories is a list of 4 Magnet Probes for the Logger. 1736/1738 Users Manual Accessories Table 2 is 1 year. For the most up-to www...
...6000/3PK i17xx-flex 6000/4PK Fluke-17xx Test Lead Fluke-17xx Test Lead 3PHVL-1730 i40s-EL Current Clamp i40s-EL/3PK Fluke-1730-Hanger Kit 173x AUX Input Adapter C17xx FLUKE-1736/UPGRADE IEEE 519/REPORT ...3 Current Clamps, 40 A Hanger Kit Lithium-ion Battery Soft Case Upgrade Kit for 1736 to 1738 (includes: Hanger, Magnet Probes, 1736 to 1738 Upgrade Kit, and Software License) Software License for IEEE 519 Reporting WiFi/BLE to USB Adapter Set...included accessories is a list of 4 Magnet Probes for the Logger. 1736/1738 Users Manual Accessories Table 2 is 1 year. For the most up-to www...
User Manual
Page 22
... the mains cord to the ac input socket on an internal rechargeable Lithium-ion battery. Fit the power supply to the Logger or use . 1736/1738 Users Manual How to Charge Battery The Logger also operates on the power supply. 2. Note • Li-ion batteries keep a charge longer if stored at room...
... the mains cord to the ac input socket on an internal rechargeable Lithium-ion battery. Fit the power supply to the Logger or use . 1736/1738 Users Manual How to Charge Battery The Logger also operates on the power supply. 2. Note • Li-ion batteries keep a charge longer if stored at room...
User Manual
Page 26
Mains Power Source 1. See Table 5 for power: mains, measurement line, and battery. The Logger automatically turns on the power supply to the Logger or use in Attach the power supply to access the mains socket and connect the power cord into the Logger. Move the slide-cover on and is ready to use the dc power cord to connect the power supply to the Logger. 2. The front panel LED shows the status. 1736/1738 Users Manual Power ON/OFF The Logger has several options for more information.
Mains Power Source 1. See Table 5 for power: mains, measurement line, and battery. The Logger automatically turns on the power supply to the Logger or use in Attach the power supply to access the mains socket and connect the power cord into the Logger. Move the slide-cover on and is ready to use the dc power cord to connect the power supply to the Logger. 2. The front panel LED shows the status. 1736/1738 Users Manual Power ON/OFF The Logger has several options for more information.
User Manual
Page 28
... parameters, touch a target on the display, use . Push to take a screen shot. Basic Navigation When an option menu shows on the display. 1736/1738 Users Manual Touch Screen The touch screen lets you interact directly with insulating gloves on (resistive touch). Touch targets are easy to 100 % when the Logger is...
... parameters, touch a target on the display, use . Push to take a screen shot. Basic Navigation When an option menu shows on the display. 1736/1738 Users Manual Touch Screen The touch screen lets you interact directly with insulating gloves on (resistive touch). Touch targets are easy to 100 % when the Logger is...
User Manual
Page 30
...screens. 20 Use the feature to record data in the Measurement Configuration. The number of available phases and the Neutral current depends on 1738 or 1736 with 1736/Upgrade on installation of interest. Push (Trend only) to expand the trend chart to access the ...; (Show Menu) to display and confirm with . The standard is selected in logging sessions and perform standard compliance measurements. 1736/1738 Users Manual to select the parameter of the IEEE 519/Report license. Note This screen provides quick feedback about how to start a logging session, ...
...screens. 20 Use the feature to record data in the Measurement Configuration. The number of available phases and the Neutral current depends on 1738 or 1736 with 1736/Upgrade on installation of interest. Push (Trend only) to expand the trend chart to access the ...; (Show Menu) to display and confirm with . The standard is selected in logging sessions and perform standard compliance measurements. 1736/1738 Users Manual to select the parameter of the IEEE 519/Report license. Note This screen provides quick feedback about how to start a logging session, ...
User Manual
Page 32
Single Phase Example: Branch circuit at an outlet. Examples of these diagrams are shown on the Logger. Energy Study hcf040.eps hcf041.eps Load Study (no voltage measurement) 22 A diagram is shown on the following pages. 1736/1738 Users Manual Topology (Distribution System) Select the appropriate system. A connection diagram for the voltage test leads and current sensors is also available with (Connection diagram) from the Change Configuration menu.
Single Phase Example: Branch circuit at an outlet. Examples of these diagrams are shown on the Logger. Energy Study hcf040.eps hcf041.eps Load Study (no voltage measurement) 22 A diagram is shown on the following pages. 1736/1738 Users Manual Topology (Distribution System) Select the appropriate system. A connection diagram for the voltage test leads and current sensors is also available with (Connection diagram) from the Change Configuration menu.
User Manual
Page 34
Example: Industrial power in countries that use the IT (Isolated Terra) system, such as Norway. Typical commercial building power. 3-Ф Wye IT The logger has a galvanic isolation between the voltage inputs and ground based signals like USB and mains input. Energy Study hcf045.eps Energy Study hcf047.eps hcf046.eps Load Study (no voltage measurement) 24 hcf048.eps Load Study (no voltage measurement) 1736/1738 Users Manual 3-Ф Wye Example: Also called "Star" or four-wire connection.
Example: Industrial power in countries that use the IT (Isolated Terra) system, such as Norway. Typical commercial building power. 3-Ф Wye IT The logger has a galvanic isolation between the voltage inputs and ground based signals like USB and mains input. Energy Study hcf045.eps Energy Study hcf047.eps hcf046.eps Load Study (no voltage measurement) 24 hcf048.eps Load Study (no voltage measurement) 1736/1738 Users Manual 3-Ф Wye Example: Also called "Star" or four-wire connection.
User Manual
Page 36
... directed towards the load to provide positive power values. Energy Study hcf055.eps Energy Study hcf053.eps hcf056.eps Load Study (no voltage measurement) 1736/1738 Users Manual 2 Element Delta (Aron/Blondel) Example: Blondel or Aron connection, simplifies the connection by the use of only two current sensors. 3-Ф Delta Open Leg...
... directed towards the load to provide positive power values. Energy Study hcf055.eps Energy Study hcf053.eps hcf056.eps Load Study (no voltage measurement) 1736/1738 Users Manual 2 Element Delta (Aron/Blondel) Example: Blondel or Aron connection, simplifies the connection by the use of only two current sensors. 3-Ф Delta Open Leg...
User Manual
Page 38
... with the voltage connections such as the power line frequency, 50 Hz or 60 Hz. High Range is in the list, enter a custom voltage. 1736/1738 Users Manual Nominal Voltage Select a nominal voltage from the list. Wrap the iFlex sensor around the primary conductor, for dips, swells, and interruptions. Voltage Ratio (only...
... with the voltage connections such as the power line frequency, 50 Hz or 60 Hz. High Range is in the list, enter a custom voltage. 1736/1738 Users Manual Nominal Voltage Select a nominal voltage from the list. Wrap the iFlex sensor around the primary conductor, for dips, swells, and interruptions. Voltage Ratio (only...