Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 2
...door according to EN60529 Protection by using 2 clamps only) The testers are also easy to use . The most complete testers The Fluke 1623 and 1625 are distinctive earth ground testers that can perform all inside a rugged Fluke carrying case. 1623 Specifications General Display:1999 digit LCD User interface... mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in) 1.1 kg (2.43 lb) including batteries 2 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers max. 50 V to earth IEC 61326-1:1997 Class A Developed, designed and manufactured according to DIN ISO 9001 V ext, max = 24 V (dc, ac < ...
...door according to EN60529 Protection by using 2 clamps only) The testers are also easy to use . The most complete testers The Fluke 1623 and 1625 are distinctive earth ground testers that can perform all inside a rugged Fluke carrying case. 1623 Specifications General Display:1999 digit LCD User interface... mm x 133 mm x 187 mm (9.75 in x 5.25 in x 7.35 in) 1.1 kg (2.43 lb) including batteries 2 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers max. 50 V to earth IEC 61326-1:1997 Class A Developed, designed and manufactured according to DIN ISO 9001 V ext, max = 24 V (dc, ac < ...
Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 3
... • •RS[k7]/RA[7 0.2 % Measurement is not performed if the current through the current clamp is too low 3 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers RA 3-pole ground resistance measurement (IEC 1557-5) Switch position Resolution Measuring range RA 3-pole 0.001 7 to 10 7 0.001 7 to 19.99 k7... selection Max. 100 k7 Max. 100 k7 Measurement is not performed if the current through the current clamp is too low RA 4-pole ground resistance measurement (IEC 1557-5) Switch position RA 4-pole Resolution 0.001 7 to 10 7 Measuring range 0.001 7 to 19.99 k7 Measuring...
... • •RS[k7]/RA[7 0.2 % Measurement is not performed if the current through the current clamp is too low 3 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers RA 3-pole ground resistance measurement (IEC 1557-5) Switch position Resolution Measuring range RA 3-pole 0.001 7 to 10 7 0.001 7 to 19.99 k7... selection Max. 100 k7 Max. 100 k7 Measurement is not performed if the current through the current clamp is too low RA 4-pole ground resistance measurement (IEC 1557-5) Switch position RA 4-pole Resolution 0.001 7 to 10 7 Measuring range 0.001 7 to 19.99 k7 Measuring...
Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 4
...2 A (ac) (RA > 20 7) Automatic range selection The information regarding stakeless ground loop measurements is only valid when used in closed loops using two current transformers Measuring ...ground loop measurement ( ) Switch position RA 4-pole Resolution 0.001 7 to 0.1 7 Measuring range 0.001 7 to 199.9 7 Intrinsic error ± (7 % rdg + 3 d) Operating error ± (10 % rdg + 5 d) Measuring principle: Stakeless measurement of resistance in conjunction with the recommended current clamps at the minimum distance specified. 4 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers...
...2 A (ac) (RA > 20 7) Automatic range selection The information regarding stakeless ground loop measurements is only valid when used in closed loops using two current transformers Measuring ...ground loop measurement ( ) Switch position RA 4-pole Resolution 0.001 7 to 0.1 7 Measuring range 0.001 7 to 199.9 7 Intrinsic error ± (7 % rdg + 3 d) Operating error ± (10 % rdg + 5 d) Measuring principle: Stakeless measurement of resistance in conjunction with the recommended current clamps at the minimum distance specified. 4 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers...
Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 5
... instrument with a mains supply and/or measuring equipment deriving its output voltage directly from the distribution system. 5 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers and 4-pole with dc 4 digit (2999 Digit) - 7 segment liquid crystal display, digit size 18 mm (0.71 in) with dc... Temperature coefficient ± 0.1 % of four temperature ranges for measuring equipment with additional functions Interference voltage and frequency, earthing resistance 3- and 4-pole with/without clip-on current transformer, resistance 2-pole with Table 1 in accordance with ac, 2-
... instrument with a mains supply and/or measuring equipment deriving its output voltage directly from the distribution system. 5 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers and 4-pole with dc 4 digit (2999 Digit) - 7 segment liquid crystal display, digit size 18 mm (0.71 in) with dc... Temperature coefficient ± 0.1 % of four temperature ranges for measuring equipment with additional functions Interference voltage and frequency, earthing resistance 3- and 4-pole with/without clip-on current transformer, resistance 2-pole with Table 1 in accordance with ac, 2-
Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 6
... Range 1 V to 50 V Display Range 0.0 V to 50 V Resolution 0.1 V Frequency Range dc/ac 45 Hz to 50 V Limits of Error ± (1 % of rdg + 2 digit) Earthing resistance (RE) Measuring method Open circuit voltage Short circuit current Measuring frequency Noise rejection Max. overload approx. 4 measurements/s approx. 1.5 M7 Urms = 250 V Measurement of interference..., designed and manufactured to EN60529 ! socket to socket Urms = 0 V Sockets " " to each other in function R* 120 dB (162/3, 50 , 60, 400 Hz) Urms = 250 V 6 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers
... Range 1 V to 50 V Display Range 0.0 V to 50 V Resolution 0.1 V Frequency Range dc/ac 45 Hz to 50 V Limits of Error ± (1 % of rdg + 2 digit) Earthing resistance (RE) Measuring method Open circuit voltage Short circuit current Measuring frequency Noise rejection Max. overload approx. 4 measurements/s approx. 1.5 M7 Urms = 250 V Measurement of interference..., designed and manufactured to EN60529 ! socket to socket Urms = 0 V Sockets " " to each other in function R* 120 dB (162/3, 50 , 60, 400 Hz) Urms = 250 V 6 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers
Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 7
...Fluke Corporation 1623 and 1625 GEO Earth Ground Testers Operating Error ± ( 5 % of rdg + 5 digit ) Measuring time Additional error because of probe-, auxiliary earth electrode- with AFC and complete cycle of all measuring frequencies Measuring error of RH and RS Max. probe resistance Max. and earthing... error or influence quantity Intrinsic error Position Supply voltage Temperature Series interference voltage Resistance of the probes and auxiliary earth electrodes System frequency System voltage Operating error A= En = R= T= intrinsic error variations routine test type test ...
...Fluke Corporation 1623 and 1625 GEO Earth Ground Testers Operating Error ± ( 5 % of rdg + 5 digit ) Measuring time Additional error because of probe-, auxiliary earth electrode- with AFC and complete cycle of all measuring frequencies Measuring error of RH and RS Max. probe resistance Max. and earthing... error or influence quantity Intrinsic error Position Supply voltage Temperature Series interference voltage Resistance of the probes and auxiliary earth electrodes System frequency System voltage Operating error A= En = R= T= intrinsic error variations routine test type test ...
Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 8
... of all measuring frequencies 0.5 mA With transformer (1000:1) 0.1 mA With transformer (200:1) 3A With a transformer (1000:1) 8 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers and auxiliary earth typ. Urms = 250 V (measurement will not be measured Max. Automatic switchover of measuring resolution in dependence to 29.99 k7...Range 0.020 7 to 30 k7 Display range 0.001 to 2.999 7 3.00 to 29.99 7 30.0 to 299.9 7 0.300 to 2.999 k7 3.00 to auxiliary earth electrode resistance RH RH with Umeas = 48 V < 300 7 RH with Umeas = 20 V < 250 7 Resolution 1 m7 < 6 k7 < 2.5 k7 10 m7...
... of all measuring frequencies 0.5 mA With transformer (1000:1) 0.1 mA With transformer (200:1) 3A With a transformer (1000:1) 8 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers and auxiliary earth typ. Urms = 250 V (measurement will not be measured Max. Automatic switchover of measuring resolution in dependence to 29.99 k7...Range 0.020 7 to 30 k7 Display range 0.001 to 2.999 7 3.00 to 29.99 7 30.0 to 299.9 7 0.300 to 2.999 k7 3.00 to auxiliary earth electrode resistance RH RH with Umeas = 48 V < 300 7 RH with Umeas = 20 V < 250 7 Resolution 1 m7 < 6 k7 < 2.5 k7 10 m7...
Fluke 1623 and 1625 Geo Earth Ground Testers Datasheet
Page 9
....0 7 to 299.9 7 300 7 to 29.99 7 by means of measured value R = R - Resistances > 1 7 in functions RE 3-pole, RE 4-pole Formation of measuring adjustment. 2-pole 9 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers incl. R * display measured compensated , R~ , and R * Value of setpoint entry RK = 0.000 7, variable from 0.000 to 2999 7 Resolution 0.001 7 0.01 7 0.1 7 17 Intrinsic error ±...
....0 7 to 299.9 7 300 7 to 29.99 7 by means of measured value R = R - Resistances > 1 7 in functions RE 3-pole, RE 4-pole Formation of measuring adjustment. 2-pole 9 Fluke Corporation 1623 and 1625 GEO Earth Ground Testers incl. R * display measured compensated , R~ , and R * Value of setpoint entry RK = 0.000 7, variable from 0.000 to 2999 7 Resolution 0.001 7 0.01 7 0.1 7 17 Intrinsic error ±...
FE 1625 Users Manual
Page 1
Printed in USA All product names are trademarks of their respective companies. ® 1625 Earth/Ground Tester Users Manual January 2006 © 2006 Fluke Corporation, All rights reserved.
Printed in USA All product names are trademarks of their respective companies. ® 1625 Earth/Ground Tester Users Manual January 2006 © 2006 Fluke Corporation, All rights reserved.
FE 1625 Users Manual
Page 7
... Figures Figure Title Page 1. Measurement of Single Earth Electrode Resistances in Mesh Operated Earthing Systems 36 12. 3-pole/4-pole Measurement of Earth Electrode Connecting Lead ...... 44 16. Compensation of Single Earth Electrode Resistances 37 13. Fluke 1625 Earth/Ground Tester 2 2. Operating Elements 21 5. Display Elements 23 6. Measurement of Measuring Lead Resistance 51 v Earth Resistance - Compensation of Interference - Description of Soil...
... Figures Figure Title Page 1. Measurement of Single Earth Electrode Resistances in Mesh Operated Earthing Systems 36 12. 3-pole/4-pole Measurement of Earth Electrode Connecting Lead ...... 44 16. Compensation of Single Earth Electrode Resistances 37 13. Fluke 1625 Earth/Ground Tester 2 2. Operating Elements 21 5. Display Elements 23 6. Measurement of Measuring Lead Resistance 51 v Earth Resistance - Compensation of Interference - Description of Soil...
FE 1625 Users Manual
Page 9
..., high and medium voltage power pylons, railway tracks, tanks, vats, foundations and lightning protection systems. The effectiveness of grounding systems should be checked using a ground test instruments such as the 1625 which must be checked regularly. There are taken correctly. Earth/Ground Tester Introduction At locations involving the generation, distribution and consumption of connections to the...
..., high and medium voltage power pylons, railway tracks, tanks, vats, foundations and lightning protection systems. The effectiveness of grounding systems should be checked using a ground test instruments such as the 1625 which must be checked regularly. There are taken correctly. Earth/Ground Tester Introduction At locations involving the generation, distribution and consumption of connections to the...
FE 1625 Users Manual
Page 10
...; Selective measurements are described in the main section of this manual. • For stakeless earth resistance measurements, the EI-1625 must be purchased. (The EI-1625 comes standard with the 1625 Kit). Figure 1 displays the Fluke 1625 Earth/Ground Tester: START TEST 1625 EARTH / GROUND TESTER ST H /C2 DISPLAY MENU Earth/Ground Resistance 300 k RA CHANGE ITEM 4 POLE 3 POLE 4 POLE 3 POLE AC Resistance 300 k R DC...
...; Selective measurements are described in the main section of this manual. • For stakeless earth resistance measurements, the EI-1625 must be purchased. (The EI-1625 comes standard with the 1625 Kit). Figure 1 displays the Fluke 1625 Earth/Ground Tester: START TEST 1625 EARTH / GROUND TESTER ST H /C2 DISPLAY MENU Earth/Ground Resistance 300 k RA CHANGE ITEM 4 POLE 3 POLE 4 POLE 3 POLE AC Resistance 300 k R DC...
FE 1625 Users Manual
Page 11
Basic (Includes manual, 2 leads and 2 clips) Earth Ground Tester - Earth/Ground Tester Models and Accessories Table 1. Models and Accessories Table 1 lists the models and accessories. Models and Accessories Description Earth Ground Tester - Fully Loaded (Includes manual, 2 leads and 2 clips, ES162P4, EI-1623) Service Replacement Kit... 2-3 Wire Adapter Cable for 1625 for EI162AC Current Transformer Earth Stake Cable Reel w/25m Wire Cable Reel w/50m Wire 1625 Users Manual Item/Part Number Fluke-1625 Fluke-1625 Kit Fluke-162x-7001 ES-162P3 ES-162P4 EI-1625 EI-162X 2539195 EI-162AC ...
Basic (Includes manual, 2 leads and 2 clips) Earth Ground Tester - Earth/Ground Tester Models and Accessories Table 1. Models and Accessories Table 1 lists the models and accessories. Models and Accessories Description Earth Ground Tester - Fully Loaded (Includes manual, 2 leads and 2 clips, ES162P4, EI-1623) Service Replacement Kit... 2-3 Wire Adapter Cable for 1625 for EI162AC Current Transformer Earth Stake Cable Reel w/25m Wire Cable Reel w/50m Wire 1625 Users Manual Item/Part Number Fluke-1625 Fluke-1625 Kit Fluke-162x-7001 ES-162P3 ES-162P4 EI-1625 EI-162X 2539195 EI-162AC ...
FE 1625 Users Manual
Page 13
... to safety engineering standards in the care and main tenance of adequate safety equipment. • training in order to make optimum use of the instrument. Earth/Ground Tester Setup Qualified Staff Consists of persons familiar with the setting up, assembly, starting up and operation of the product and possess the qualifications required for...
... to safety engineering standards in the care and main tenance of adequate safety equipment. • training in order to make optimum use of the instrument. Earth/Ground Tester Setup Qualified Staff Consists of persons familiar with the setting up, assembly, starting up and operation of the product and possess the qualifications required for...
FE 1625 Users Manual
Page 15
The auxiliary power supply consists of two parts: 1. Earth/Ground Tester Assembly Assembly The instrument is made up of 6 x 1.5 V batteries (IEC R6 or LR6 or type AA). Four rubber buttons, which contains the measuring electronics. ... system DIN ISO 9001. This design enables quick and clear one-hand operation. The measured values are displayed on the left hand side of the 1625 Earth/Ground Tester. 7 Various additional special characters indicate measuring mode, operating condition and error messages. This device has been developed, designed and manufactured in compliance with...
The auxiliary power supply consists of two parts: 1. Earth/Ground Tester Assembly Assembly The instrument is made up of 6 x 1.5 V batteries (IEC R6 or LR6 or type AA). Four rubber buttons, which contains the measuring electronics. ... system DIN ISO 9001. This design enables quick and clear one-hand operation. The measured values are displayed on the left hand side of the 1625 Earth/Ground Tester. 7 Various additional special characters indicate measuring mode, operating condition and error messages. This device has been developed, designed and manufactured in compliance with...
FE 1625 Users Manual
Page 17
...measurement is measured and stored. Giving messages if set limit values are exceeded. 2. Selective Measurement of Earthing Resistance (RE A) Measurement of a single earth electrode in beeper has two functions: 1. Resistance Measurement (R~) The resistance is determined by DC current ...and a frequency of 94, 105, 111 or 128 Hz. Indicating dangerous conditions or maloperation. Earth/Ground Tester Description of Functions Measurement of Earthing Resistance (RE) The earthing resistance is determined by an optical or acoustical signal. The frequency can be selected manually or automatically...
...measurement is measured and stored. Giving messages if set limit values are exceeded. 2. Selective Measurement of Earthing Resistance (RE A) Measurement of a single earth electrode in beeper has two functions: 1. Resistance Measurement (R~) The resistance is determined by DC current ...and a frequency of 94, 105, 111 or 128 Hz. Indicating dangerous conditions or maloperation. Earth/Ground Tester Description of Functions Measurement of Earthing Resistance (RE) The earthing resistance is determined by an optical or acoustical signal. The frequency can be selected manually or automatically...
FE 1625 Users Manual
Page 19
... instrument exist to satisfy European Standards requirements; The operating error applies under the rated operating conditions given in accordance with d.c. The r.m.s. Earth/Ground Tester Specifications Operation: Central rotary switch and function keys Working temperature range: -10 °C ... +50 °C Operating temperature range: Nominal...four temperature ranges for battery door according to EN 60529 11 the instrument can be 3 V; • resistance of the auxiliary earth electrode and of the probes: 0 to 100 x RA but ≤ 50 kΩ; • system voltages between 85 %...
... instrument exist to satisfy European Standards requirements; The operating error applies under the rated operating conditions given in accordance with d.c. The r.m.s. Earth/Ground Tester Specifications Operation: Central rotary switch and function keys Working temperature range: -10 °C ... +50 °C Operating temperature range: Nominal...four temperature ranges for battery door according to EN 60529 11 the instrument can be 3 V; • resistance of the auxiliary earth electrode and of the probes: 0 to 100 x RA but ≤ 50 kΩ; • system voltages between 85 %...
FE 1625 Users Manual
Page 21
... frequency: 94 , 105 , 111 , 128 Hz selected manually or automatic.(AFC) 55 Hz in function R* Noise rejection: 120 dB ( 16 2/3, 50 , 60, 400 Hz ) Max. Earth/Ground Tester Specifications Measurement of Interference Voltage DC + AC (UST) Measuring method: fullwave rectification Measuring Range Display Range Resolution Frequency Range Limits of Error 1...50 V 0.0...50 V 0.1 V DC...
... frequency: 94 , 105 , 111 , 128 Hz selected manually or automatic.(AFC) 55 Hz in function R* Noise rejection: 120 dB ( 16 2/3, 50 , 60, 400 Hz ) Max. Earth/Ground Tester Specifications Measurement of Interference Voltage DC + AC (UST) Measuring method: fullwave rectification Measuring Range Display Range Resolution Frequency Range Limits of Error 1...50 V 0.0...50 V 0.1 V DC...
FE 1625 Users Manual
Page 23
A = intrinsic error En = variations R = routine test T = type test Earth/Ground Tester Specifications B[%] = ± B x 100% fiducial value Measuring Range Display Range 0.020 Ω 300 kΩ 0.001 Ω...2.999 Ω 3.00 Ω...29.99 Ω 30.0 Ω......a measurement of mv +5 digit ) Measuring time: typ. 8 sec. max. with AFC and complete cycle of all measuring frequencies Additional error because of probe-and auxiliary earth electrode resistance: Measuring error of RH and RS: RH (RS + 2000Ω) ×1.25 ×10−6% + 5digits RE typ. 10 % of the in...
A = intrinsic error En = variations R = routine test T = type test Earth/Ground Tester Specifications B[%] = ± B x 100% fiducial value Measuring Range Display Range 0.020 Ω 300 kΩ 0.001 Ω...2.999 Ω 3.00 Ω...29.99 Ω 30.0 Ω......a measurement of mv +5 digit ) Measuring time: typ. 8 sec. max. with AFC and complete cycle of all measuring frequencies Additional error because of probe-and auxiliary earth electrode resistance: Measuring error of RH and RS: RH (RS + 2000Ω) ×1.25 ×10−6% + 5digits RE typ. 10 % of the in...
FE 1625 Users Manual
Page 25
and auxiliary earth typ.electrode resistance: RH (RS + 2000Ω) ×1.25 ×10−6% + 5digits RETOTAL Measuring error of RH and RS: typ.of 10% of m.v. +5 digit)...0.1 Ω 1 Ω ± (7 % of m.v. +2 digit) ± (10% of RETOTAL + RS + RH Measuring time: typ. 8 sec. with additional current transformer (patent applied for). Earth/Ground Tester Specifications Selective Measurement of the Earthing Resistance (REA) Measuring method: Current and voltage measurement with probe as per EN61557-5 and current measurement in the individual branch with a fixed frequency...
and auxiliary earth typ.electrode resistance: RH (RS + 2000Ω) ×1.25 ×10−6% + 5digits RETOTAL Measuring error of RH and RS: typ.of 10% of m.v. +5 digit)...0.1 Ω 1 Ω ± (7 % of m.v. +2 digit) ± (10% of RETOTAL + RS + RH Measuring time: typ. 8 sec. with additional current transformer (patent applied for). Earth/Ground Tester Specifications Selective Measurement of the Earthing Resistance (REA) Measuring method: Current and voltage measurement with probe as per EN61557-5 and current measurement in the individual branch with a fixed frequency...