FE 1520 Users Manual
Page 1
® 1520 MegOhmMeter Users Manual September 2000 Rev.2, 2/03 © 2000-2003 Fluke Corporation. All rights reserved. Printed in USA All product names are trademarks of their respective companies.
® 1520 MegOhmMeter Users Manual September 2000 Rev.2, 2/03 © 2000-2003 Fluke Corporation. All rights reserved. Printed in USA All product names are trademarks of their respective companies.
FE 1520 Users Manual
Page 8
Y Risk of electric shock J Earth W See manual I Fuse T Equipment protected by double or reinforced Insulation D AC or DC M Battery Recycling information P CAT III Conforms to CSA C22.2 No 1010.1-92 + Amendment 2...Conforms to EU directives VDE t Conforms to VDE EN61010 (Pending) Conforms to UL 3111.1 OVERVOLTAGE (Installation) CATEGORY ,,,, Pollution Degree 2 per IEC1010-1 refers to the user. A Warning identifies conditions and actions that may damage the Meter. International symbols on the Meter and in fixed installations (e.g., electricity meter and primary over-current...
Y Risk of electric shock J Earth W See manual I Fuse T Equipment protected by double or reinforced Insulation D AC or DC M Battery Recycling information P CAT III Conforms to CSA C22.2 No 1010.1-92 + Amendment 2...Conforms to EU directives VDE t Conforms to VDE EN61010 (Pending) Conforms to UL 3111.1 OVERVOLTAGE (Installation) CATEGORY ,,,, Pollution Degree 2 per IEC1010-1 refers to the user. A Warning identifies conditions and actions that may damage the Meter. International symbols on the Meter and in fixed installations (e.g., electricity meter and primary over-current...
FE 1520 Users Manual
Page 9
Fluke 1520 Users Manual W Safety Information Use of additional operating circuits connected in a manner not specified by the manufacturer may impair safety features/protection provided by transient currents. • ...
Fluke 1520 Users Manual W Safety Information Use of additional operating circuits connected in a manner not specified by the manufacturer may impair safety features/protection provided by transient currents. • ...
FE 1520 Users Manual
Page 11
... applies the test current to the circuit to be tested. this button until the main reading is stable. To unlock: press LOCK or TEST again. 6 Fluke 1520 Users Manual Key functions Table 1. The beeper sounds every 2 seconds to be tested. To lock: press and hold this mode continuously applies the test voltage to the...
... applies the test current to the circuit to be tested. this button until the main reading is stable. To unlock: press LOCK or TEST again. 6 Fluke 1520 Users Manual Key functions Table 1. The beeper sounds every 2 seconds to be tested. To lock: press and hold this mode continuously applies the test voltage to the...
FE 1520 Users Manual
Page 13
Fluke 1520 Users Manual Display Table 2 and Figure 2 describe the display. Display Description 1 Voltage applied to a function. Displays briefly when the Meter is first switched to the probes in ...
Fluke 1520 Users Manual Display Table 2 and Figure 2 describe the display. Display Description 1 Voltage applied to a function. Displays briefly when the Meter is first switched to the probes in ...
FE 1520 Users Manual
Page 15
Fluke 1520 Users Manual Using the Meter Connecting to be measured. Warning To prevent electric shock when performing resistance tests, remove all W power from the circuit to the Circuit Under Test W Figure 3 shows the proper connections. Warning To prevent electric shock, first connect the test leads to the Meter inputs before you make connection to the circuit under test. 10
Fluke 1520 Users Manual Using the Meter Connecting to be measured. Warning To prevent electric shock when performing resistance tests, remove all W power from the circuit to the Circuit Under Test W Figure 3 shows the proper connections. Warning To prevent electric shock, first connect the test leads to the Meter inputs before you make connection to the circuit under test. 10
FE 1520 Users Manual
Page 17
This may include exposed bonded metalwork. • Before proceeding, ensure that the installation is correctly wired and no personnel are endangered by any tests. 12 W Measuring Insulation Resistance Warning • Measuring insulation resistance requires the application of potentially dangerous voltages to the desired function. To turn the meter back on, turn the rotary switch to OFF, then to the circuit. In Lo Ohms mode, the meter turns off after 5 minutes of non-use . Fluke 1520 Users Manual Auto-Shut-Off The Meter automatically turns off after 15 minutes of non-use .
This may include exposed bonded metalwork. • Before proceeding, ensure that the installation is correctly wired and no personnel are endangered by any tests. 12 W Measuring Insulation Resistance Warning • Measuring insulation resistance requires the application of potentially dangerous voltages to the desired function. To turn the meter back on, turn the rotary switch to OFF, then to the circuit. In Lo Ohms mode, the meter turns off after 5 minutes of non-use . Fluke 1520 Users Manual Auto-Shut-Off The Meter automatically turns off after 15 minutes of non-use .
FE 1520 Users Manual
Page 19
... maximum display range, the meter reacts as the main display. The circuit now discharges through the Meter, while the main reading shows the decreasing voltage. Fluke 1520 Users Manual The Meter beeps when the reading is selected, the display reads >4000 MΩ. 4. Keep the probes touched to the test points until a new test is...
... maximum display range, the meter reacts as the main display. The circuit now discharges through the Meter, while the main reading shows the decreasing voltage. Fluke 1520 Users Manual The Meter beeps when the reading is selected, the display reads >4000 MΩ. 4. Keep the probes touched to the test points until a new test is...
FE 1520 Users Manual
Page 21
... or a different function is > 30 V ac or dc, remove the voltage from the circuit under test before proceeding with the next step. Fluke 1520 Users Manual Measuring Low Resistance To measure low resistance: 1. Zero out the test lead resistance (see Table 1). 2. Warning A repetitive beep and the flashing ...high voltage symbol (Y) warn the user if voltage more than 40 Ω, >40 Ω is displayed. 4. Press and hold the TEST button. W If voltage is present on the...
... or a different function is > 30 V ac or dc, remove the voltage from the circuit under test before proceeding with the next step. Fluke 1520 Users Manual Measuring Low Resistance To measure low resistance: 1. Zero out the test lead resistance (see Table 1). 2. Warning A repetitive beep and the flashing ...high voltage symbol (Y) warn the user if voltage more than 40 Ω, >40 Ω is displayed. 4. Press and hold the TEST button. W If voltage is present on the...
FE 1520 Users Manual
Page 23
If the voltage is higher than 4000 Ω, >4000 Ω is present, then switch to be measured. If the resistance is displayed. Fluke 1520 Users Manual Measuring Resistance 1. Measuring Voltage 1. Connect the probes to the circuit to ensure that no hazardous voltage is displayed. Warning The Meter indicates either ac or ...
If the voltage is higher than 4000 Ω, >4000 Ω is present, then switch to be measured. If the resistance is displayed. Fluke 1520 Users Manual Measuring Resistance 1. Measuring Voltage 1. Connect the probes to the circuit to ensure that no hazardous voltage is displayed. Warning The Meter indicates either ac or ...
FE 1520 Users Manual
Page 25
Remove any residue afterwards. Fluke 1520 Users Manual Maintaining the Meter This section provides basic maintenance information, including fuse and battery replacement instructions. Cleaning Clean only with a damp cloth and mild detergent. Caution Do not attempt to repair or service your Meter unless you are qualified to do so and have the relevant calibration, performance test, and service information. Periodically wipe the case with soap and water. Do not use abrasives or solvents. 20
Remove any residue afterwards. Fluke 1520 Users Manual Maintaining the Meter This section provides basic maintenance information, including fuse and battery replacement instructions. Cleaning Clean only with a damp cloth and mild detergent. Caution Do not attempt to repair or service your Meter unless you are qualified to do so and have the relevant calibration, performance test, and service information. Periodically wipe the case with soap and water. Do not use abrasives or solvents. 20
FE 1520 Users Manual
Page 27
Fluke 1520 Users Manual 4. Lift the battery access lid away from the Meter. 6. Secure the battery access lid back in Figure 5. Place the Meter face down on a nonabrasive surface and loosen the two screws with the two screws. 22 Replace the C cells as shown in position with a flat-blade screwdriver. 5. Observe the battery polarity shown in the battery compartment. 7.
Fluke 1520 Users Manual 4. Lift the battery access lid away from the Meter. 6. Secure the battery access lid back in Figure 5. Place the Meter face down on a nonabrasive surface and loosen the two screws with the two screws. 22 Replace the C cells as shown in position with a flat-blade screwdriver. 5. Observe the battery polarity shown in the battery compartment. 7.
FE 1520 Users Manual
Page 29
... "Replacement Parts and Optional Accessories" section. The display should indicate approximately 0.5 Ω. Connect the test leads to the Meter, install ONLY Fluke specified fuse identified in the next section. Fluke 1520 Users Manual W Testing and Replacing the Fuse Warning To avoid electric shock, disconnect the test leads from the inputs before opening the Meter for...
... "Replacement Parts and Optional Accessories" section. The display should indicate approximately 0.5 Ω. Connect the test leads to the Meter, install ONLY Fluke specified fuse identified in the next section. Fluke 1520 Users Manual W Testing and Replacing the Fuse Warning To avoid electric shock, disconnect the test leads from the inputs before opening the Meter for...
FE 1520 Users Manual
Page 33
... world: +1-425-446-5500 28 Fluke 1520 Users Manual Principle of Measurement for Resistance The Meter measures resistance by performing the following calculation: R = V (Ohm's Law) I Service Centers To locate an authorized service center, visit us on the World Wide Web: www.fluke.com or call Fluke using any of the phone numbers... listed below: USA: 1-888-99-FLUKE (1-888-993-5853) Canada: 1-800-36-FLUKE (1-800-363-5853) Europe: +31 402-678-200 Japan: +81-3-3434-0181 ...
... world: +1-425-446-5500 28 Fluke 1520 Users Manual Principle of Measurement for Resistance The Meter measures resistance by performing the following calculation: R = V (Ohm's Law) I Service Centers To locate an authorized service center, visit us on the World Wide Web: www.fluke.com or call Fluke using any of the phone numbers... listed below: USA: 1-888-99-FLUKE (1-888-993-5853) Canada: 1-800-36-FLUKE (1-800-363-5853) Europe: +31 402-678-200 Japan: +81-3-3434-0181 ...
FE 1520 Users Manual
Page 35
Fluke 1520 Users Manual Size Weight Drop requirement Shock and Vibration Electrical Safety Maximum Operating Voltage Protection Levels Immunity & Emmissions ESD Mechanical Specifications 23,4 x 10 x 6,4 cm (9.2 x 3.9 x 2.5 in) 1 kg (2.2 lbs.) ...
Fluke 1520 Users Manual Size Weight Drop requirement Shock and Vibration Electrical Safety Maximum Operating Voltage Protection Levels Immunity & Emmissions ESD Mechanical Specifications 23,4 x 10 x 6,4 cm (9.2 x 3.9 x 2.5 in) 1 kg (2.2 lbs.) ...
FE 1520 Users Manual
Page 37
Fluke 1520 Users Manual Test Voltages Accuracy Nominal Current Number of measurements Circuitry Protection Display Range Measurement Range Accuracy Resolution Analog Bar Graph Open Circuit Voltage Short Circuit Current ...
Fluke 1520 Users Manual Test Voltages Accuracy Nominal Current Number of measurements Circuitry Protection Display Range Measurement Range Accuracy Resolution Analog Bar Graph Open Circuit Voltage Short Circuit Current ...
FE 1520 Users Manual
Page 39
...operation or handling. Following warranty repair, the product will be returned to 34 Fluke assumes no authority to extend a greater or different warranty on new and unused products to end-user customers only but have no risk for repair in another country. Following repair...a defective product which , in transit. The warranty period is three years and begins on non-defective media. Fluke 1520 Users Manual Limited Warranty & Limitation of Liability Each Fluke product is warranted to be free from defects in material and workmanship under normal use outside of the product's ...
...operation or handling. Following warranty repair, the product will be returned to 34 Fluke assumes no authority to extend a greater or different warranty on new and unused products to end-user customers only but have no risk for repair in another country. Following repair...a defective product which , in transit. The warranty period is three years and begins on non-defective media. Fluke 1520 Users Manual Limited Warranty & Limitation of Liability Each Fluke product is warranted to be free from defects in material and workmanship under normal use outside of the product's ...