Question posted by husnayamuth on February 12th, 2021

Error 56

Breaker tripped after 2 hours working

Current Answers

Answer #1: Posted by waelsaidani1 on February 13th, 2021 4:33 AM
This answer was accepted by the poster of the original question.
waelsaidani1

Member since:
May 12th, 2013

Points: 19,501,777
1,100
points
When the electric motors in your air conditioner left running for too long, the wire insulation can break down leading to an electrical short. More electricity passes through than the wires can handle, which then trips the breakers.

Related Haier AV10NMVERA Manual Pages

Design Manual - Page 7

... Capacity,10=10HP Product type : "V" stands for MRVII R410A outdoor Indoor unit: Model: A B 09 2 M C E R A Haier Air Conditioner Climate type: T1 Design number: A stands for fixed frequency type, H stands for inverter type, R stands for DC inverter and R410A type ...stands for duct type, "S" stands for wall mounted type, "F" stands for console type Haier Air Conditioner G R U P A d.o.o. 07
Design Manual - Page 8

... healthy module A: 220~240V, 50Hz B: 220~240V, 60Hz C: 380V, 50Hz D: 380V, 60Hz E: 110V, 50Hz F: 110V, 60Hz Air flow: m3/h Heat reclaimed ventilation unit outdoor capacity 8HP max. indoor unit quantity 39 43 46 50 53 56 59 63 total indoor capacity range (*100W) 340~ 884 365~ 400~ 949 1040 425~ 1105 450...
Design Manual - Page 11

..., outdoor temp is 350CDB/240CWB; c. outdoor temp is 70CDB/60CWB. b. The directive is error such as the previous state. 5.10 Reliable performance a. Auto diagnose function The PCB will check...nature. Haier MRVII has been designed to leak any refrigerant. Approved for every air conditioning manufacturer. The parts are the purchased aim for RoHS certificate All the parts...
Design Manual - Page 12

... type < Wall mounted type < Console type 12 G R U P A d.o.o. 5.11 Super comfortable a. Furthermore, the compressor is hermetically scroll type with the protection when temperature, current etc occur error. High efficiency compressor The compressor is with brushless internal motor, which runs faster, much more stable.
Design Manual - Page 24

...(KW) Fan type and Qty Fan Fan motor output(KW) characteris- static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) ...970*875*360 970*875*360 600*250 600*250 600*250 48/56 48/56 48/56 Wired controller/ wireless controller (optional) Use for installation 12.7 6.35...
Design Manual - Page 25

Standard airflow(m3/h) tics Standard static pressure(Pa) Max. G R U P A d.o.o. 25 static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(net/gross, Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/L AD302MHERA 9.0 10.0 ---8.0 ...
Design Manual - Page 27

...(KW) Electrical heating power(KW) /Current(A) Heating capacity at low temp.(KW) Electrical Power source chara- G R U P A d.o.o. 27 static pressure(Pa) Exterior dimensions(mm) Air outlet dimensions(mm) Weight(Kg) Controller Accessories Gas piping(mm) Piping dimension Liquid piping(mm) Drain hose(mm) Noise level(dB(A)) H/M/L AC092MCERA 2.8 3.2 AC122MCERA 3.6 4 AC162MCERA...
Design Manual - Page 31

... (Kg) 8 AV08NMVERA ** 22.6 25.0 21.2 3N~, 380~400V, 50Hz 8.7/10.5 5.28/6.34 9.7/11.3 5.89/6.85 5.57 0.7 990*750*1750 235 ivory scroll 10000 10.0 10 AV10NMVERA ** 28.0 31.5 25.6 12.2/15.6 7.36/9.45 13.2/15.8 7.97/10.2 6.73 0.7 990*750*1750 235 ivory scroll 10000 10.0 Piping dimension Gas piping(mm...
Design Manual - Page 34

... (Kg) Gas piping(mm) Liquid piping(mm) Equipoise/Oil equalization piping(mm) Noise level(dB(A)) 18 AV18NMVERA AV08+AV10 50.6 56.5 46.8 3N~, 380~400V, 50Hz 20.9/26.1 12.64/15.79 22.9/27.1 13.86/17.05 12.3 1.4 990*750...*1750 +990*750*1750 470 ivory scroll 20000 20 28.58 15.88 9.52 61 20 AV20NMVERA AV10+AV10 56.0 63.0 51.2 24.4/31.2 14.72/18.90 26.4/31.6 15.94/20.4 13.46 1.4 990*750*1750 ...
Design Manual - Page 37

...*750*1750 575 ivory scroll 24000 28 31.8 19.05 9.52 63 32 AV32NMVERA AV16+AV16 90 100 78.2 46.4/56.2 28.12/34 42.4/51.2 25.64/30.76 20.56 2.2 1390*750*1750 +1390*750*1750 600 ivory scroll 24000 32 31.8 19.05 9.52 63 Connection type of liquid...
Design Manual - Page 56

G R U P A d.o.o. b Wall mounted type indoor: a Haier c model AS072/092/122MCERA AS162/182MCERA a bc 795 265 182 928 45 60 50 50 60 bottom side AS242MAERA 60 70 200 55 right side 55 200 left side 56
Design Manual - Page 73

... 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 MODE FAN COOL DRY HEAT AUTO FAN SPEED AUTO HIGH MID LOW STANDBY FILTER SET FAILURE CHECK...
Design Manual - Page 85

... pipe length of single way (m) cooling compensation factor cooling compensation factor G R U P A d.o.o. E: Capacity compensation value at different piping length and drop AV08NMVERA liquid pipe:φ12.7 AV10NMVERA 1.00 gas pipe:φ22.22 1.00 liquid pipe:φ12.7 gas pipe:φ22.22 cooling compensation factor cooling compensation factor 0.95 0.95 0.90...
Design Manual - Page 92

... connection methods (unit: mm) A. Outdoor unit Model AV08NMVERA AV10NMVERA Gas pipe side Diameter Connecting method 19.05 22.22 Brazing... 6.35 9.52 9.52 9.52 9.52 9.52 5. Refrigerant charging and additional charging Diameter of liquid pipe Model AV08NMVERA AV10NMVERA AV12NMVERA AV14NMVERA AV16NMVERA additonal refrigerant charging per meter(kg/m) 22.22 19.05 15.88 12.7 9.52 6.35 0.35...
Design Manual - Page 98

... indoor pipe, for wall mounted unit, please refer to its specification) Indoor(×100W) Gas pipe Liquid pipe 22~28 φ9.52 φ6.35 36~56 φ12.7 φ6.35 71~140 φ15.88 φ9.52 b. a. (2) Pipe specification: e a a e e d b a outdoor gather pipe c the first branch...
Design Manual - Page 103

... be fixed firmly. Specs for power cable and communication wire (1) Outdoor power source and power cable model item power power cable section wire length circuit breaker(A) earthing wire source (mm2) (m) section(mm2) screw individual AV10NMVERA 3N~, 10 380V, power AV16NMVERA 50Hz 18 60 40 60 70 3.5 M5 a.
Design Manual - Page 108

... allowable voltage unbalance between phases is in the range. 3. fuse amps of circuit breaker MSC: Max. range 380 342-418 380 342-418 380 342-418 380 342.... (A) TOCA: Total over-current amps.(A) MFA: Max. Outdoor unit: units model phase AV08NMVERA 3 AV10NMVERA 3 AV12NMVERA 3 AV14NMVERA 3 AV16NMVERA 3 AV18NMVERA 3 AV20NMVERA 3 AV22NMVERA 3 AV24NMVERA 3 AV26NMVERA 3 AV28NMVERA...
Design Manual - Page 110

... each management system can connect 4 sets network server maximum by the distributor or the buyer. General information This management system suits for MRV II series air conditioner. 1.1 Gateway(Model:iGU01) Function:Communication BUS for indoor &Outdoor ,adopt the running status parameters,transmit the control signal .And convert the comminucaition protocal from Lonwokrs...
Design Manual - Page 113

... when there is no polarity requirement.. 113 HBM/HBM (HOMEBUS communication) port: connect ports P&Q of the communication terminal block of gateway. There cannt be any error when connecting, or the gateway will be burnt off. 2) LON/LON(LONWORKS communication) connector: connect with the output port of serial signal (CN35 ) of the...
Design Manual - Page 116

...system H-CACSII BMS system H-CACS transfer the data of air conditioner to the computer. 2. receive ammeter pulse signal; ...MRV II (R22 & R410A) system. 1.2 System combination 1. Inverter protocol adapter (IGU02): Transform the air conditioner protocol into protocol 485; One Microsoft can not work normally. 2. If the H-CACSII is HCM1. 1.3 Control range 1. range: -30¡ ¡&#...

Similar Questions

Commercial Cool Air Conditioner Model# Cwh12a
Where can I purchase a new Commercial Cool air conditioner from?
(Posted by williamsshannon984 2 years ago)
Air Conditioner Wont Turn On. It Worked Just Fine Two Days Ago
I have a Haeir air conditioner HPAC9M two days ago it worked fine but now it wont turn on
(Posted by alexisiam 3 years ago)
Portable Air Conditioner Keeps Shutting Off
my portable air conditioner keeps shutting down after running for about 10 min
(Posted by Buttercup2 6 years ago)
My Air Conditioner Go Off
when the air conditioner is funtion for only little time like 20 minute is going to signal the STOP ...
(Posted by haydeejose 7 years ago)
Ask a New Question
Use the box below to post a new question about this Haier product .
Points & Prizes
  • You can earn points for nearly everything you do on HelpOwl.com
  • You can trade in those points for gift cards at leading retailers such as Amazon.com and Walmart
  • It's that simple!
See How it Works
Create a Free Account

Haier Manuals

Find free Haier AV10NMVERA manuals and user guides available at ManualOwl.com. Try out our unique manual viewer allowing you to interact with manuals from directly within your browser!

Haier Reviews

View thousands of Haier user reviews and customer ratings available at ReviewOwl.com.

Contact Information

Complete Haier customer service contact information including steps to reach representatives, hours of operation, customer support links and more from ContactHelp.com.

Scoreboard Ratings

See detailed Haier customer service rankings, employee comments and much more from our sister site.

Haier Recalls

Find comprehensive Haier recall information updated hourly on RecallOwl.com.