Owner's Manual for 3-Phase UPS 932764
Page 2
... Features 6 4 Front and Rear Panel Features 7 5 Cabinet Installation 9 3 5-1 Preparation 9 5-2 Unpacking 9 5-3 Placement 10 46 Internal Battery Connection (SU40K Only) 11 6-1 Internal Battery Wiring Diagrams 11 6-2 Internal Battery Connection Procedure 13 5 7 Wiring 16 7-1 Wiring Warnings 16 7-2 Wiring Preparation 16 7-3...UPS) 25 9-3 Normal Start-Up Procedure (Single UPS) 25 9-4 Battery Start-Up Procedure (Single UPS) 26 11 9-5 Manual Bypass Procedure (Single UPS) 27 9-6 Shutdown Procedure (Single UPS) 27 9-7 Preliminary Checklist (Parallel UPS) 28 9-8 Start-...
... Features 6 4 Front and Rear Panel Features 7 5 Cabinet Installation 9 3 5-1 Preparation 9 5-2 Unpacking 9 5-3 Placement 10 46 Internal Battery Connection (SU40K Only) 11 6-1 Internal Battery Wiring Diagrams 11 6-2 Internal Battery Connection Procedure 13 5 7 Wiring 16 7-1 Wiring Warnings 16 7-2 Wiring Preparation 16 7-3...UPS) 25 9-3 Normal Start-Up Procedure (Single UPS) 25 9-4 Battery Start-Up Procedure (Single UPS) 26 11 9-5 Manual Bypass Procedure (Single UPS) 27 9-6 Shutdown Procedure (Single UPS) 27 9-7 Preliminary Checklist (Parallel UPS) 28 9-8 Start-...
Owner's Manual for 3-Phase UPS 932764
Page 4
... eventually causing product damage not covered under warranty. 6 • Do not install the UPS system near magnetic storage media, as this manual. It also must be performed by trained, qualified electricians only. 12 • Due to all applicable national and local electrical wiring codes... Safety Instructions 1 SAVE THESE INSTRUCTIONS 2 All sections of this equipment can reasonably be expected to cause the failure of this manual contains instructions and warnings that have the potential to provide long-term support for proper ventilation. For best results, maintain indoor ...
... eventually causing product damage not covered under warranty. 6 • Do not install the UPS system near magnetic storage media, as this manual. It also must be performed by trained, qualified electricians only. 12 • Due to all applicable national and local electrical wiring codes... Safety Instructions 1 SAVE THESE INSTRUCTIONS 2 All sections of this equipment can reasonably be expected to cause the failure of this manual contains instructions and warnings that have the potential to provide long-term support for proper ventilation. For best results, maintain indoor ...
Owner's Manual for 3-Phase UPS 932764
Page 6
... indicate that the UPS system is in auto bypass mode. An audible alarm will be charged for data entry in bypass mode (auto bypass or manual bypass). Available diagnostic information will also sound. • C 6 • D "BYPASS" LED: This amber light illuminates when the UPS system is still charging as required. •...
... indicate that the UPS system is in auto bypass mode. An audible alarm will be charged for data entry in bypass mode (auto bypass or manual bypass). Available diagnostic information will also sound. • C 6 • D "BYPASS" LED: This amber light illuminates when the UPS system is still charging as required. •...
Owner's Manual for 3-Phase UPS 932764
Page 7
...UPS system during manual bypass operation. 12 •F Bypass Input Circuit Breaker Switch (Q2): Controls AC input power to the UPS system during online (normal) operation. •H Levelers: The levelers provide long-term support for the UPS system. 13 •I H 9 SU40K shown (front)...panel allows the operator to provide long-term support. 14 7 The number of N+1 redundancy. 11 •C Internal Battery Pack Compartment (SU40K only): Internal batteries must be replaced in the field without powering down connected equipment loads. See Section 6 - Use the levelers to ...
...UPS system during manual bypass operation. 12 •F Bypass Input Circuit Breaker Switch (Q2): Controls AC input power to the UPS system during online (normal) operation. •H Levelers: The levelers provide long-term support for the UPS system. 13 •I H 9 SU40K shown (front)...panel allows the operator to provide long-term support. 14 7 The number of N+1 redundancy. 11 •C Internal Battery Pack Compartment (SU40K only): Internal batteries must be replaced in the field without powering down connected equipment loads. See Section 6 - Use the levelers to ...
Owner's Manual for 3-Phase UPS 932764
Page 11
... 12V, 9AH, 10PCS RED RED W1 W2 W3 W4 BLACK BLACK 12V, 9AH, 10PCS 12V, 9AH, 10PCS RED RED W1 W2 W3 W4 BLACK BLACK SU40K shown 6 7 8 9 10 11 12 13 14 11 Read Section 2 - The UPS system can accept up to a UPS system. Potentially lethal high ... Q2 MAIN INPUT Q1 AC/DC B+ N B- Battery connection should be performed by qualified service personnel only, following all the precautions listed in this manual and adhering to connecting the internal batteries. Each internal battery pack consists of two strings of 10 batteries). LETHAL HIGH VOLTAGE HAZARD! each pack consists...
... 12V, 9AH, 10PCS RED RED W1 W2 W3 W4 BLACK BLACK 12V, 9AH, 10PCS 12V, 9AH, 10PCS RED RED W1 W2 W3 W4 BLACK BLACK SU40K shown 6 7 8 9 10 11 12 13 14 11 Read Section 2 - The UPS system can accept up to a UPS system. Potentially lethal high ... Q2 MAIN INPUT Q1 AC/DC B+ N B- Battery connection should be performed by qualified service personnel only, following all the precautions listed in this manual and adhering to connecting the internal batteries. Each internal battery pack consists of two strings of 10 batteries). LETHAL HIGH VOLTAGE HAZARD! each pack consists...
Owner's Manual for 3-Phase UPS 932764
Page 16
... has VNG>0, install an isolation transformer before installing cables or making electrical connections. • Use flexible cable of at least 3.95 N·m (35 in this manual and all line conductors and the neutral conductor. Failure to observe proper phase will damage the UPS system and create a serious risk of the UPS...
... has VNG>0, install an isolation transformer before installing cables or making electrical connections. • Use flexible cable of at least 3.95 N·m (35 in this manual and all line conductors and the neutral conductor. Failure to observe proper phase will damage the UPS system and create a serious risk of the UPS...
Owner's Manual for 3-Phase UPS 932764
Page 20
Second, confirm that the manual bypass circuit breaker switch Q3 is off . Cabling should be protected by connecting R to R, S to S, T to T and N to expose the circuit breakers. Warning: Observe proper ...
Second, confirm that the manual bypass circuit breaker switch Q3 is off . Cabling should be protected by connecting R to R, S to S, T to T and N to expose the circuit breakers. Warning: Observe proper ...
Owner's Manual for 3-Phase UPS 932764
Page 22
...eliminated, the UPS system switches 9 back to connected equipment. MAIN Q2 Q1 XFMR Q4 LOAD XFMR CB5 STS Q4 LOAD XFMR CB5 STS 10 8-4 Manual Bypass Mode (Single UPS) If UPS system maintenance or repair is present, stop the inverter by shutting it down . Q3 MAIN Q2 Q1 XFMR 7...to precision-regulated, pure sine wave AC power that 11 bypass power is required, you can bypass the UPS system and enable bypass power manually. The inverter transforms the DC power 6 to precision-regulated, pure sine wave AC power that conforms to normal parameters, then the UPS system...
...eliminated, the UPS system switches 9 back to connected equipment. MAIN Q2 Q1 XFMR Q4 LOAD XFMR CB5 STS Q4 LOAD XFMR CB5 STS 10 8-4 Manual Bypass Mode (Single UPS) If UPS system maintenance or repair is present, stop the inverter by shutting it down . Q3 MAIN Q2 Q1 XFMR 7...to precision-regulated, pure sine wave AC power that 11 bypass power is required, you can bypass the UPS system and enable bypass power manually. The inverter transforms the DC power 6 to precision-regulated, pure sine wave AC power that conforms to normal parameters, then the UPS system...
Owner's Manual for 3-Phase UPS 932764
Page 24
Operating Modes (continued) 1 8-8 Manual Bypass Mode (Parallel UPS) Similar to manual bypass mode for a single UPS system (Section 8-4), 2 except with parallel (1+1) UPS systems. Note: Both UPS systems must be switched into manual bypass mode. 3 Q3 MAIN Q2 XFMR Q1 Q3 4 MAIN Q2 XFMR Q1 5 Q4 XFMR CB5 STS UPS1 LOAD Q4 XFMR CB5 STS UPS2 6 7 8 9 10 11 12 13 14 24 8 -
Operating Modes (continued) 1 8-8 Manual Bypass Mode (Parallel UPS) Similar to manual bypass mode for a single UPS system (Section 8-4), 2 except with parallel (1+1) UPS systems. Note: Both UPS systems must be switched into manual bypass mode. 3 Q3 MAIN Q2 XFMR Q1 Q3 4 MAIN Q2 XFMR Q1 5 Q4 XFMR CB5 STS UPS1 LOAD Q4 XFMR CB5 STS UPS2 6 7 8 9 10 11 12 13 14 24 8 -
Owner's Manual for 3-Phase UPS 932764
Page 25
On the SU40K, turn ON the battery breaker on the back of the UPS.... Button ( ) •I ON Button •J OFF Button •K "EPO" (Emergency Power Off) Button •L Output Circuit Breaker Switch •M Manual Bypass Circuit Breaker Switch •N Bypass Input Circuit Breaker Switch •O Main Input Circuit Breaker Switch A E FI K 2 B G C D 3 ... Panel) 6 9-2 Preliminary Checklist (Single UPS) • All circuit breaker switches should be off . Q3 Output Manual Bypass Main Bypass Input Input 2 12 13 14 25 9 - After a successful self-test, the UPS system ...
On the SU40K, turn ON the battery breaker on the back of the UPS.... Button ( ) •I ON Button •J OFF Button •K "EPO" (Emergency Power Off) Button •L Output Circuit Breaker Switch •M Manual Bypass Circuit Breaker Switch •N Bypass Input Circuit Breaker Switch •O Main Input Circuit Breaker Switch A E FI K 2 B G C D 3 ... Panel) 6 9-2 Preliminary Checklist (Single UPS) • All circuit breaker switches should be off . Q3 Output Manual Bypass Main Bypass Input Input 2 12 13 14 25 9 - After a successful self-test, the UPS system ...
Owner's Manual for 3-Phase UPS 932764
Page 26
... is an external battery cabinet connected, switch on the main input circuit breaker switch Q1 . Q3 Output Manual Bypass Bypass Input Main Input A 14 3 26 9 - On the SU40K, turn on the battery breaker on the bypass input breaker switch Q2 and then output circuit breaker switch ...Q4. Q4 Output Manual Bypass 5 4 • 5 6 Press the ON button A for 3 seconds (until you hear a beep), then release the ...
... is an external battery cabinet connected, switch on the main input circuit breaker switch Q1 . Q3 Output Manual Bypass Bypass Input Main Input A 14 3 26 9 - On the SU40K, turn on the battery breaker on the bypass input breaker switch Q2 and then output circuit breaker switch ...Q4. Q4 Output Manual Bypass 5 4 • 5 6 Press the ON button A for 3 seconds (until you hear a beep), then release the ...
Owner's Manual for 3-Phase UPS 932764
Page 27
...loads are turned off for the internal battery) is ON; The UPS should transfer to recharge. Start-Up, Shutdown and Bypass (continued) 1 9-5 Manual Bypass Procedure (Single UPS) Warning: Placing the UPS system in BYPASS mode (amber Bypass LED is on periodically to allow the batteries to Bypass.... 3 5 4 goes blank (this may take a minute or two), then turn OFF the Q4 Q3 Q2 Q1 BATTERY BREAKER (on the SU40K unit, the BATTERY BREAKER is on and the batteries should be energized. Note: Some external battery cabinets may cause irreversible battery damage. 14 27
...loads are turned off for the internal battery) is ON; The UPS should transfer to recharge. Start-Up, Shutdown and Bypass (continued) 1 9-5 Manual Bypass Procedure (Single UPS) Warning: Placing the UPS system in BYPASS mode (amber Bypass LED is on periodically to allow the batteries to Bypass.... 3 5 4 goes blank (this may take a minute or two), then turn OFF the Q4 Q3 Q2 Q1 BATTERY BREAKER (on the SU40K unit, the BATTERY BREAKER is on and the batteries should be energized. Note: Some external battery cabinets may cause irreversible battery damage. 14 27
Owner's Manual for 3-Phase UPS 932764
Page 28
... • Each UPS must have its parallel group set to 2 and a different "Parallel ID" that indicates the UPS systems are running in MANUAL BYPASS (the MANUAL BYPASS circuit breaker Q3 is now supported by conditioned battery back-up , the UPS systems will transfer to the connected equipment load. 13 14... 28 Confirm the amber BYPASS LED is on the SU20K and SU40K units, the BATTERY BREAKER is ON. Turn OFF the MANUAL BYPASS circuit breaker Q3 . Turn ON the MAIN INPUT circuit breaker Q1 . Confirm there are noted, contact your ...
... • Each UPS must have its parallel group set to 2 and a different "Parallel ID" that indicates the UPS systems are running in MANUAL BYPASS (the MANUAL BYPASS circuit breaker Q3 is now supported by conditioned battery back-up , the UPS systems will transfer to the connected equipment load. 13 14... 28 Confirm the amber BYPASS LED is on the SU20K and SU40K units, the BATTERY BREAKER is ON. Turn OFF the MANUAL BYPASS circuit breaker Q3 . Turn ON the MAIN INPUT circuit breaker Q1 . Confirm there are noted, contact your ...
Owner's Manual for 3-Phase UPS 932764
Page 29
... 3 4 2 •3 Switch on the external battery cabinet circuit breaker switch A of each UPS system, see Section 10-4. 10 A 11 12 13 Output Manual Bypass Main 6 Bypass Input Input 14 29 9 - See Section 10-5-5. When the inverter of each UPS system. The "BYPASS" LED will darken and the..."Parallel ID" is different for each UPS and that the parallel group is operating normally, they will illuminate. 5 6 Q2 7 Output Manual Bypass Main 3 Bypass Input Input •4 Switch on checking the output voltage of the UPS systems for 3 seconds (until you hear a...
... 3 4 2 •3 Switch on the external battery cabinet circuit breaker switch A of each UPS system, see Section 10-4. 10 A 11 12 13 Output Manual Bypass Main 6 Bypass Input Input 14 29 9 - See Section 10-5-5. When the inverter of each UPS system. The "BYPASS" LED will darken and the..."Parallel ID" is different for each UPS and that the parallel group is operating normally, they will illuminate. 5 6 Q2 7 Output Manual Bypass Main 3 Bypass Input Input •4 Switch on checking the output voltage of the UPS systems for 3 seconds (until you hear a...
Owner's Manual for 3-Phase UPS 932764
Page 30
...- If the other UPS system's LCD screen will eliminate the AC power output for all loads 2 are turned off or place the UPS systems in manual bypass mode to keep loads powered by a single UPS system, both UPS systems will shut down their 4 inverters and switch to bypass mode, and their... A for an extended period of each battery pack. 9 Note: If the UPS system remains off the bypass input circuit breaker switch Q2 . 7 Output Manual Bypass Bypass Input Main Input Q2 8 •4 When the UPS system is too large to be handled by the bypass power source. •1 For the...
...- If the other UPS system's LCD screen will eliminate the AC power output for all loads 2 are turned off or place the UPS systems in manual bypass mode to keep loads powered by a single UPS system, both UPS systems will shut down their 4 inverters and switch to bypass mode, and their... A for an extended period of each battery pack. 9 Note: If the UPS system remains off the bypass input circuit breaker switch Q2 . 7 Output Manual Bypass Bypass Input Main Input Q2 8 •4 When the UPS system is too large to be handled by the bypass power source. •1 For the...
Owner's Manual for 3-Phase UPS 932764
Page 31
... A for the second UPS system you hear a beep), then release the button. A 11 •6 In this mode, only the manual bypass path (including the manual bypass circuit breaker Q3 , the load terminals of the output circuit breaker switch Q4 and the terminal block B contain hazardous voltage, allowing ...loads alone, the UPS system that both UPS systems will shut down its inverter and its LCD screen will read "ON MANUAL BYPASS". Q4 Q2 9 Output Manual Bypass Main 4 Bypass Input Input •5 If the UPS systems have external battery cabinets connected, 10 switch off the bypass...
... A for the second UPS system you hear a beep), then release the button. A 11 •6 In this mode, only the manual bypass path (including the manual bypass circuit breaker Q3 , the load terminals of the output circuit breaker switch Q4 and the terminal block B contain hazardous voltage, allowing ...loads alone, the UPS system that both UPS systems will shut down its inverter and its LCD screen will read "ON MANUAL BYPASS". Q4 Q2 9 Output Manual Bypass Main 4 Bypass Input Input •5 If the UPS systems have external battery cabinets connected, 10 switch off the bypass...
Owner's Manual for 3-Phase UPS 932764
Page 32
...Start-Up, Shutdown and Bypass (continued) 1 9-11 Switching from Manual Bypass to online (normal) mode at the same time. 3 8 Q1 9 Output Manual Bypass Main 4 Bypass Input Input 5 10 Q4 Q2 Output Manual Bypass Bypass Input Main Input Q3 Output Manual Bypass Bypass Input Main Input A 11 12 13 14 32 ... breaker switch Q4 of each UPS system. 5 •3 Confirm that the LCD screens of both UPS systems read "ON MANUAL BYPASS", then switch off the manual bypass input circuit breaker switch Q3 of the first UPS systems for 3 seconds (until you hear 7 a beep), then ...
...Start-Up, Shutdown and Bypass (continued) 1 9-11 Switching from Manual Bypass to online (normal) mode at the same time. 3 8 Q1 9 Output Manual Bypass Main 4 Bypass Input Input 5 10 Q4 Q2 Output Manual Bypass Bypass Input Main Input Q3 Output Manual Bypass Bypass Input Main Input A 11 12 13 14 32 ... breaker switch Q4 of each UPS system. 5 •3 Confirm that the LCD screens of both UPS systems read "ON MANUAL BYPASS", then switch off the manual bypass input circuit breaker switch Q3 of the first UPS systems for 3 seconds (until you hear 7 a beep), then ...
Owner's Manual for 3-Phase UPS 932764
Page 33
...•B "BATTERY" (Amber) LED: Illuminated when the UPS is in Battery Backup mode. •C "BYPASS" (Amber) LED: Illuminated when the UPS is in Manual Bypass mode. •D "FAULT" (Red) LED: Illuminated when any fault occurs. •E LCD Status Display: Multi-language display. •F "ESC" (Escape... EPO button will completely remove power from the UPS output. 2 E FI K A B G C 3 D HJ 4 Control Panel 5 6 10-2 LCD Status Display The Tripp Lite E3 Series UPS features a user-friendly LCD screen to show messages and display UPS Status screens. 7 8 9 10 11 12 13 14 33 10 -
...•B "BATTERY" (Amber) LED: Illuminated when the UPS is in Battery Backup mode. •C "BYPASS" (Amber) LED: Illuminated when the UPS is in Manual Bypass mode. •D "FAULT" (Red) LED: Illuminated when any fault occurs. •E LCD Status Display: Multi-language display. •F "ESC" (Escape... EPO button will completely remove power from the UPS output. 2 E FI K A B G C 3 D HJ 4 Control Panel 5 6 10-2 LCD Status Display The Tripp Lite E3 Series UPS features a user-friendly LCD screen to show messages and display UPS Status screens. 7 8 9 10 11 12 13 14 33 10 -
Owner's Manual for 3-Phase UPS 932764
Page 34
... the default screen. 10-3-1 Status Display 11 •1 The UPS system output is no further message, the screen will return to automatic UPS shutdown or manually switching off the output circuit breaker switch. Display and Configuration (continued) 1 10-3 Default Display • 1 2 After the UPS system starts up and completes the self... will show the default display. flashes. You can press " " to the next message. Possible causes: 12 • The UPS automatically shuts down by itself. • Manually switch off and the connected equipment loads are not powered.
... the default screen. 10-3-1 Status Display 11 •1 The UPS system output is no further message, the screen will return to automatic UPS shutdown or manually switching off the output circuit breaker switch. Display and Configuration (continued) 1 10-3 Default Display • 1 2 After the UPS system starts up and completes the self... will show the default display. flashes. You can press " " to the next message. Possible causes: 12 • The UPS automatically shuts down by itself. • Manually switch off and the connected equipment loads are not powered.
Owner's Manual for 3-Phase UPS 932764
Page 37
...;8 The UPS system is operating in economy mode, and connected equipment loads are being powered by the bypass source. 2 3 4 5 8 •9 The UPS system is in manual bypass mode in order to allow qualified service personnel to access the main menu. Press the scroll down button ( ) or the scroll up button 10...
...;8 The UPS system is operating in economy mode, and connected equipment loads are being powered by the bypass source. 2 3 4 5 8 •9 The UPS system is in manual bypass mode in order to allow qualified service personnel to access the main menu. Press the scroll down button ( ) or the scroll up button 10...