Installation Guide
Page 20
...720 requires that the optional high-speed fan tray (FAN-MOD-3HS) be installed in the same chassis. - Note In systems with the smaller memory configuration is sufficient to run the configured features of the switch. Supervisor Engine 32 and Supervisor Engine...recommended, but are not supported by Supervisor Engine 720 and cannot be installed in standby mode. Catalyst 6503 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-1 Catalyst 6503 Switch Features (continued) Feature Supervisor engines Description • Supports Supervisor Engine 2, Supervisor Engine 32, ...
...720 requires that the optional high-speed fan tray (FAN-MOD-3HS) be installed in the same chassis. - Note In systems with the smaller memory configuration is sufficient to run the configured features of the switch. Supervisor Engine 32 and Supervisor Engine...recommended, but are not supported by Supervisor Engine 720 and cannot be installed in standby mode. Catalyst 6503 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-1 Catalyst 6503 Switch Features (continued) Feature Supervisor engines Description • Supports Supervisor Engine 2, Supervisor Engine 32, ...
Installation Guide
Page 22
...176;F (0° to 40°C) Designed and tested for operation: 32° to 130°F (0° to 55°C) Note The Catalyst 6500 series switches are triggered at 104°F (40°C) generating a minor alarm and at 131°F (55°C) generating a major alarm. -4... and 2 AC-input power supplies: 85.4 lb (38.7 kg). • FAN-MOD-3 (standard fan tray)-170 CFM • FAN-MOD-3HS (optional high-speed fan tray)-270 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that are equipped with internal air temperature sensors that you maintain a...
...176;F (0° to 40°C) Designed and tested for operation: 32° to 130°F (0° to 55°C) Note The Catalyst 6500 series switches are triggered at 104°F (40°C) generating a minor alarm and at 131°F (55°C) generating a major alarm. -4... and 2 AC-input power supplies: 85.4 lb (38.7 kg). • FAN-MOD-3 (standard fan tray)-170 CFM • FAN-MOD-3HS (optional high-speed fan tray)-270 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that are equipped with internal air temperature sensors that you maintain a...
Installation Guide
Page 32
... a 2500 W or higher capacity power supply when using the Supervisor Engine 32 or the Supervisor Engine 720 and the high-speed fan tray. 1-16 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 Slots are supported: - WS-CAC-3000W (3000 W AC-input power supply)...can be both AC-input, both DC-input, or one AC-input and one or two power supplies. Catalyst 6506 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-7 Catalyst 6506 Switch Features Feature Chassis Power supplies Descriptions Six horizontal slots. WS-CAC-1000W (1000 W AC-input power supply)...
... a 2500 W or higher capacity power supply when using the Supervisor Engine 32 or the Supervisor Engine 720 and the high-speed fan tray. 1-16 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 Slots are supported: - WS-CAC-3000W (3000 W AC-input power supply)...can be both AC-input, both DC-input, or one AC-input and one or two power supplies. Catalyst 6506 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-7 Catalyst 6506 Switch Features Feature Chassis Power supplies Descriptions Six horizontal slots. WS-CAC-1000W (1000 W AC-input power supply)...
Installation Guide
Page 33
... connections. Note The 2500 W power supply, when supporting the high-speed fan tray, can be the same model and have the resources to run the switch on the redundant supervisor engine in the chassis. Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6506 Switch Table 1-7 Catalyst 6506 Switch Features (continued) Feature Supervisor engines Descriptions • Supports Supervisor Engine 2, Supervisor...
... connections. Note The 2500 W power supply, when supporting the high-speed fan tray, can be the same model and have the resources to run the switch on the redundant supervisor engine in the chassis. Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6506 Switch Table 1-7 Catalyst 6506 Switch Features (continued) Feature Supervisor engines Descriptions • Supports Supervisor Engine 2, Supervisor...
Installation Guide
Page 35
... and the air intake on another chassis. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation Guide 1-19 Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6506 Switch Table 1-8 Catalyst 6506 Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating and storage Thermal... 130°F (0° to 55°C) Note The Catalyst 6500 series switches are equipped with 1 supervisor engine, 5 switching modules, and 2 power supplies: 156.6 lb (71.0 kg). • WS-C6K-6SLOT-FAN (Standard fan tray)-227 CFM. • WS-C6K-6SLOT-FAN2 (Optional ...
... and the air intake on another chassis. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation Guide 1-19 Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6506 Switch Table 1-8 Catalyst 6506 Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating and storage Thermal... 130°F (0° to 55°C) Note The Catalyst 6500 series switches are equipped with 1 supervisor engine, 5 switching modules, and 2 power supplies: 156.6 lb (71.0 kg). • WS-C6K-6SLOT-FAN (Standard fan tray)-227 CFM. • WS-C6K-6SLOT-FAN2 (Optional ...
Installation Guide
Page 42
... "Power Supply Specifications," in either redundant or nonredundant mode. • All Catalyst 6500 series AC-input power supplies require single-phase source AC. Catalyst 6509 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-11 Catalyst 6509 Switch Features Feature Chassis Power supplies Description Nine horizontal slots. Installed power supplies can also...a 2500 W or higher capacity power supply when using the Supervisor Engine 32 or the Supervisor Engine 720 and the high-speed fan tray. 1-26 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03
... "Power Supply Specifications," in either redundant or nonredundant mode. • All Catalyst 6500 series AC-input power supplies require single-phase source AC. Catalyst 6509 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-11 Catalyst 6509 Switch Features Feature Chassis Power supplies Description Nine horizontal slots. Installed power supplies can also...a 2500 W or higher capacity power supply when using the Supervisor Engine 32 or the Supervisor Engine 720 and the high-speed fan tray. 1-26 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03
Installation Guide
Page 43
...Catalyst 6509 Switch Table 1-11 Catalyst 6509 Switch Features (continued) Feature Supervisor engines Description • Supports Supervisor Engine 2, Supervisor Engine 32, Supervisor Engine 32 PISA, Supervisor Engine 720, and Supervisor Engine 720-10GE. - Supervisor Engine 32, Supervisor Engine 32 PISA, Supervisor Engine 720, and Supervisor Engine 720-10GE require that the high-speed fan tray...installed in the chassis to power the high-speed fan tray. Supervisor Engine 2 is sufficient to run the configured features of the switch. Supervisor Engine 32, Supervisor Engine 32 PISA, ...
...Catalyst 6509 Switch Table 1-11 Catalyst 6509 Switch Features (continued) Feature Supervisor engines Description • Supports Supervisor Engine 2, Supervisor Engine 32, Supervisor Engine 32 PISA, Supervisor Engine 720, and Supervisor Engine 720-10GE. - Supervisor Engine 32, Supervisor Engine 32 PISA, Supervisor Engine 720, and Supervisor Engine 720-10GE require that the high-speed fan tray...installed in the chassis to power the high-speed fan tray. Supervisor Engine 2 is sufficient to run the configured features of the switch. Supervisor Engine 32, Supervisor Engine 32 PISA, ...
Installation Guide
Page 45
...-FAN2 (Optional high-speed fan tray)-630 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that meet ANSI/EIA 310-D and ETS 300-119 standards. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation Guide 1-29 Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6509 Switch Table 1-12 Catalyst 6509 Switch Specifications Item Environmental Temperature...
...-FAN2 (Optional high-speed fan tray)-630 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that meet ANSI/EIA 310-D and ETS 300-119 standards. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation Guide 1-29 Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6509 Switch Table 1-12 Catalyst 6509 Switch Specifications Item Environmental Temperature...
Installation Guide
Page 55
...176;F (0° to 55°C) Note The Catalyst 6500 series switches are equipped with 1 supervisor engine, 8 switching modules, and 2 power supplies: 135 lb (61.2 kg). • WS-C6509-NEB-FAN (standard fan tray)-294 CFM • Optional high-speed fan tray1-630 CFM Note To maintain proper air ...circulation through the Catalyst switch chassis, we recommend that are triggered at 104°F (40°C) generating a minor...
...176;F (0° to 55°C) Note The Catalyst 6500 series switches are equipped with 1 supervisor engine, 8 switching modules, and 2 power supplies: 135 lb (61.2 kg). • WS-C6509-NEB-FAN (standard fan tray)-294 CFM • Optional high-speed fan tray1-630 CFM Note To maintain proper air ...circulation through the Catalyst switch chassis, we recommend that are triggered at 104°F (40°C) generating a minor...
Installation Guide
Page 60
...FAN-MOD-09 (high-speed fan tray)-760 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that you maintain a minimum 6-inch (15 cm) separation between the hot air exhaust on one chassis and the air intake on another chassis. On Catalyst... can be placed side-by-side. 1-44 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 Catalyst 6509-NEB-A Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-18 Catalyst 6509-NEB-A Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating ...
...FAN-MOD-09 (high-speed fan tray)-760 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that you maintain a minimum 6-inch (15 cm) separation between the hot air exhaust on one chassis and the air intake on another chassis. On Catalyst... can be placed side-by-side. 1-44 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 Catalyst 6509-NEB-A Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-18 Catalyst 6509-NEB-A Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating ...
Installation Guide
Page 64
...from front to back, the chassis may be placed side-by-side. 1-48 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 WS-C6509-V-E-FAN (High-speed fan tray-760 CFM). You should also allow a minimum separation of 12 inches (30.5 ...one chassis and the air intake on another chassis. Chassis only: 121 lb (54.9 kg). Catalyst 6509-V-E Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-20 Catalyst 6509-V-E Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating and storage Thermal transition Humidity (RH), ambient (...
...from front to back, the chassis may be placed side-by-side. 1-48 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 WS-C6509-V-E-FAN (High-speed fan tray-760 CFM). You should also allow a minimum separation of 12 inches (30.5 ...one chassis and the air intake on another chassis. Chassis only: 121 lb (54.9 kg). Catalyst 6509-V-E Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-20 Catalyst 6509-V-E Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating and storage Thermal transition Humidity (RH), ambient (...
Installation Guide
Page 66
...W or higher capacity power supply when using the Supervisor Engine 32 or the Supervisor Engine 720 and the high-speed fan tray. 1-50 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 WS-CAC-2500W (2500 W AC-input power supply) - Installed ... The 8700 W AC-input power supply is limited to (13) bottom. • Supports one DC-input. Catalyst 6513 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-21 Catalyst 6513 Switch Features Feature Chassis Power supplies Description Thirteen horizontal slots. WS-CAC-4000W-US (4000 W AC-input power supply...
...W or higher capacity power supply when using the Supervisor Engine 32 or the Supervisor Engine 720 and the high-speed fan tray. 1-50 Catalyst 6500 Series Ethernet Modules Installation Guide OL-6265-03 WS-CAC-2500W (2500 W AC-input power supply) - Installed ... The 8700 W AC-input power supply is limited to (13) bottom. • Supports one DC-input. Catalyst 6513 Switch Chapter 1 Catalyst 6500 Series Switch Chassis Overview Table 1-21 Catalyst 6513 Switch Features Feature Chassis Power supplies Description Thirteen horizontal slots. WS-CAC-4000W-US (4000 W AC-input power supply...
Installation Guide
Page 67
... (WS-C6500-SFM and WS-X6500-SFM2) are duplicated. Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6513 Switch Table 1-21 Catalyst 6513 Switch Features (continued) Feature Supervisor engines Description • Supports Supervisor Engine 2, Supervisor Engine 32, Supervisor Engine 32 PISA, ... power the high-speed fan tray. - Supervisor Engine 32 and Supervisor Engine 32 PISA do not support the Switch Fabric Modules ((WS-C6500-SFM and WS-X6500-SFM2). • The uplink ports are installed in the chassis. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation...
... (WS-C6500-SFM and WS-X6500-SFM2) are duplicated. Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6513 Switch Table 1-21 Catalyst 6513 Switch Features (continued) Feature Supervisor engines Description • Supports Supervisor Engine 2, Supervisor Engine 32, Supervisor Engine 32 PISA, ... power the high-speed fan tray. - Supervisor Engine 32 and Supervisor Engine 32 PISA do not support the Switch Fabric Modules ((WS-C6500-SFM and WS-X6500-SFM2). • The uplink ports are installed in the chassis. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation...
Installation Guide
Page 69
...air space can be placed side-by-side. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation Guide 1-53 Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6513 Switch Table 1-22 Catalyst 6513 Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating and storage Thermal transition... lb (127 kg). • WS-C6K-13SLOT-FAN (standard fan tray)-641 CFM • WS-C6K-13SLT-FAN2 (optional high-speed fan tray)-1090 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that you maintain a minimum 6-...
...air space can be placed side-by-side. OL-6265-03 Catalyst 6500 Series Ethernet Modules Installation Guide 1-53 Chapter 1 Catalyst 6500 Series Switch Chassis Overview Catalyst 6513 Switch Table 1-22 Catalyst 6513 Switch Specifications Item Environmental Temperature, operating Temperature, nonoperating and storage Thermal transition... lb (127 kg). • WS-C6K-13SLOT-FAN (standard fan tray)-641 CFM • WS-C6K-13SLT-FAN2 (optional high-speed fan tray)-1090 CFM Note To maintain proper air circulation through the Catalyst switch chassis, we recommend that you maintain a minimum 6-...
Installation Guide
Page 167
...Support for additional information on page B-8 in Appendix B for the Catalyst 6509-NEB-A chassis requires two FAN-MOD-09 fan trays. • Dual switch-fabric connections: - Not all types of the WS-X6708-10GE with a fan tray 2 and a 2500 W or larger power supply, the configuration...Cisco IOS Release 12.2(18)SXF5. Note The WS-6708-10GE does not support X2 transceivers shipped prior to the release of X2 transceivers may be supported. Refer to your software release notes to 55°C). • When the WS-X6708-10G module is installed in the Catalyst 6513 chassis. OL-6265-03 Catalyst...
...Support for additional information on page B-8 in Appendix B for the Catalyst 6509-NEB-A chassis requires two FAN-MOD-09 fan trays. • Dual switch-fabric connections: - Not all types of the WS-X6708-10GE with a fan tray 2 and a 2500 W or larger power supply, the configuration...Cisco IOS Release 12.2(18)SXF5. Note The WS-6708-10GE does not support X2 transceivers shipped prior to the release of X2 transceivers may be supported. Refer to your software release notes to 55°C). • When the WS-X6708-10G module is installed in the Catalyst 6513 chassis. OL-6265-03 Catalyst...
Installation Guide
Page 171
... Not supported in the Catalyst 6503 chassis. • Supported only in slots 9-13 in the Catalyst 6513 chassis and does not power up in slots 1-8. • When the WS-X6716-10G module is installed in a Catalyst 6500-E series chassis or a Catalyst 6509-NEB-A chassis, the... configuration is NEBS 3 compliant (chassis supports operating temperatures up to 40°C only). • Support in the Catalyst 6509-NEB-A chassis requires two FAN-MOD-09 fan trays. • Dual switch-fabric connections: - Fabric...
... Not supported in the Catalyst 6503 chassis. • Supported only in slots 9-13 in the Catalyst 6513 chassis and does not power up in slots 1-8. • When the WS-X6716-10G module is installed in a Catalyst 6500-E series chassis or a Catalyst 6509-NEB-A chassis, the... configuration is NEBS 3 compliant (chassis supports operating temperatures up to 40°C only). • Support in the Catalyst 6509-NEB-A chassis requires two FAN-MOD-09 fan trays. • Dual switch-fabric connections: - Fabric...
Installation Guide
Page 175
...)SXI4 Queues per port Chassis/slot restrictions • Not supported in the Catalyst 6503 chassis or the Catalyst 6509-NEB chassis • Supported only in slots 9-13 in the Catalyst 6513 chassis and does not power up in slots 1-8. • When the ...chassis supports operating temperatures up to 40°C only). • Support in the Catalyst 6509-NEB-A chassis requires two FAN-MOD-09 fan trays be installed. Rx-8q4t per port • Oversubscription mode: - Fabric connection • Dual switch-fabric connections: - Tx-1p7q4t per port - Fabric channel 1: Ports 1-8 -...
...)SXI4 Queues per port Chassis/slot restrictions • Not supported in the Catalyst 6503 chassis or the Catalyst 6509-NEB chassis • Supported only in slots 9-13 in the Catalyst 6513 chassis and does not power up in slots 1-8. • When the ...chassis supports operating temperatures up to 40°C only). • Support in the Catalyst 6509-NEB-A chassis requires two FAN-MOD-09 fan trays be installed. Rx-8q4t per port • Oversubscription mode: - Fabric connection • Dual switch-fabric connections: - Tx-1p7q4t per port - Fabric channel 1: Ports 1-8 -...
Installation Guide
Page 240
...) 1-7 humidity, operating 1-10 physical characteristics 1-10 port densities supported 1-9 slot numbering 1-8 specifications table 1-7 supervisor engines supported 1-8 temperature, operating 1-10 weight 1-10 Catalyst 6503 switches airflow 1-6 altitude, operating 1-6 chassis, dimensions 1-6 environmental specifications 1-6 fan trays supported 1-6 features table 1-2 form factor, front view (figure) 1-2 form factor, rear view (figure) 1-2 humidity, operating 1-6 physical characteristics 1-6 port densities supported 1-5 slot...
...) 1-7 humidity, operating 1-10 physical characteristics 1-10 port densities supported 1-9 slot numbering 1-8 specifications table 1-7 supervisor engines supported 1-8 temperature, operating 1-10 weight 1-10 Catalyst 6503 switches airflow 1-6 altitude, operating 1-6 chassis, dimensions 1-6 environmental specifications 1-6 fan trays supported 1-6 features table 1-2 form factor, front view (figure) 1-2 form factor, rear view (figure) 1-2 humidity, operating 1-6 physical characteristics 1-6 port densities supported 1-5 slot...
Installation Guide
Page 242
Index supervisor engines supported 1-47 temperature, operating 1-48 weight 1-48 Catalyst 6513-E switches airflow 1-58 altitude, operating 1-58 chassis dimensions 1-58 environmental specifications 1-58 fan trays supported 1-58 features table 1-54 form factor (figure) 1-54 humidity, ...55 specifications table 1-54 supervisor engines supported 1-56 temperature, operating 1-58 weight 1-58 Catalyst 6513 switches airflow 1-53 altitude, operating 1-53 chassis dimensions 1-53 environmental specifications 1-53 fan trays supported 1-53 features table 1-49 form factor (figure) 1-49 humidity, operating 1-53...
Index supervisor engines supported 1-47 temperature, operating 1-48 weight 1-48 Catalyst 6513-E switches airflow 1-58 altitude, operating 1-58 chassis dimensions 1-58 environmental specifications 1-58 fan trays supported 1-58 features table 1-54 form factor (figure) 1-54 humidity, ...55 specifications table 1-54 supervisor engines supported 1-56 temperature, operating 1-58 weight 1-58 Catalyst 6513 switches airflow 1-53 altitude, operating 1-53 chassis dimensions 1-53 environmental specifications 1-53 fan trays supported 1-53 features table 1-49 form factor (figure) 1-49 humidity, operating 1-53...