Get support for Sanyo CMH3172 - 30,600 BTU Ductless Multi-Split Air Cond/Heat Pump

Sanyo CMH3172 Support Question

Sanyo CMH3172 Support Question

Find answers below for this question about Sanyo CMH3172 - 30,600 BTU Ductless Multi-Split Air Cond/Heat Pump.
Need a Sanyo CMH3172 manual? We have 1 online manual for this item!
Question posted by brockemail on March 25th, 2015

Cm3172 Vs Cmh3172

what is the difference in these units and are the control boards interchangeable?

Current Answers

Answer #1: Posted by TechSupport101 on March 28th, 2015 6:31 AM
This answer was accepted by the poster of the original question.
TechSupport101

Member since:
May 24th, 2013

Points: 12,171,285
1,100
points
CM3172's control PCB part# CB-CM2572

CMH3172's control PCB part# CB-CMH3172

Sadly not interchangeble

Related Sanyo CMH3172 Manual Pages

Service Manual - Page 1

TECHNICAL & SERVICE MANUAL OUTDOOR UNIT : CM1972 CM2472 CM3172 FILE NO. Destination: North America DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity at 230V 19,700 BTU/h 25,400 BTU/h 30,600 BTU/h Outdoor Model No. REFERENCE NO. SM700666-04 CM1972 CM2472 CM3172 Product Code No. 1 852 330 27 1 852 330 28 1 852 330 29 CM1972 CM2472 < Applicable Indoor Units > ●Wall mounted type ...
Service Manual - Page 4

APPLICABLE INDOOR UNITS Indoor Unit Multi-Outdoor Unit KMS0772 3-Room CM1972 YES 4-Room CM2472 YES 4-Room CM3172 YES KMS0972 YES YES YES KMS1272 YES YES YES KMS1872 YES YES YES KMS2472 NO YES YES NOTE The table lists the wall-mounted type of indoor units as representative models. 4
Service Manual - Page 6

... Indoor Units Number of Operatable Indoor Units Voltage Rating Performance Electrical Rating Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan...
Service Manual - Page 7

... Indoor Units Number of Operatable Indoor Units Voltage Rating Performance Electrical Rating Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan...
Service Manual - Page 8

... Indoor Units Number of Operatable Indoor Units Voltage Rating Performance Electrical Rating Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan...
Service Manual - Page 9

... Indoor Units Number of Operatable Indoor Units Voltage Rating Performance Electrical Rating Total Capacity Sensible Capacity Latent Capacity Air Circulation (High) Available Voltage Range Running Amperes Power Input Power Factor EER SEER Compressor Locked Rotor Amperes Fuse or Circuit Breaker Capacity BTU/h kW BTU/h BTU/h ft3/min (m3/h) V A W % BTU/h/W BTU/Wh A A Features Control Fan...
Service Manual - Page 10

... (kg) Ibs (kg) cu.ft (m3) < 230V > 4-Room Multi Outdoor Unit 4 4 230V Single-Phase 60Hz Cooling 30,600 ( 9,800 to 30,600 ) 9.00 ( 2.90 to 9.00 ) 25,800 4,800 1,942 (3,300) 187 to the "Unit Combination Tables" in performance section and electrical rating section above are : Cooling : Indoor air temp. 80°F D.B./ 67°F W.B. Rating conditions are based...
Service Manual - Page 11

....ft (m3) < 208V > 4-Room Multi Outdoor Unit 4 4 208V Single-Phase 60Hz Cooling 28,600 ( 9,800 to 28,600 ) 8.40 ( 2.90 to 8.40 ) 24,200 4,400 1,942 (3,300) 187 to the "Unit Combination Tables" in performance section and electrical rating section above are : Cooling : Indoor air temp. 80°F D.B./ 67°F W.B. Outdoor Unit CM3172 Indoor Unit KMS0972 × 4 Type Number...
Service Manual - Page 21

... Unit CM3172 Indoor unit Wide tube O.D.3/8" O.D.3/8" O.D.1/2" O.D.1/2" Service valve on narrow tube DN Electric expansion valve M CN M BN M AN M Strainer Header Heat exchanger Compressor Cooling cycle Insulation of Refrigerant Tubing IMPORTANT Because capillary tubing is used in the outdoor unit, both tubes must be a min.5/16"(8 mm). The thickness of this air conditioner...
Service Manual - Page 38

Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B. : Outdoor Ambient Temp. 95 °F (35 °C) D.B. 2. TEMP. °F (°C) W.B. Above data does not take Freeze Prevention Protection during cooling operation into account. D.B. 30,600 BTU/h 65 (18.3) TC 31,170 AIR FLOW RATE: OUTDOOR AMBIENT TEMP. °F (°C)...
Service Manual - Page 42

... of CM3172 and the values are different from the other models. Positioning of the outdoor unit electric expansion valve is ON. If automatic operation mode has been selected with the remote controller, operation begins in parentheses are an example of automatic COOL operation. Depending on the operational mode, refer to the indoor and outdoor unit control...
Service Manual - Page 47

... electronic circuits. For example, if the outdoor control circuit board fuse has blown, approximately 30 minutes will be required for the charge to dissipate if it is normal, approximately 180 seconds will be trouble with the outdoor control circuit board. High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). Be careful not to discharge...
Service Manual - Page 63

... (for Test Run) I Pump Down 5. Connecting Indoor Units 2-3. Outer Dimensions of the air conditioner that you are based on Wiring 5-2. AIR PURGING 18 I Air Purging with Unit 1-3. GENERAL 3 1-1. INSTALLATION SITE SELECTION 4 2-1. General Precautions on the typical appearance of Refrigerant Tubing 3-7. Inverter Multi Split System Air Conditioner - Caution before...
Service Manual - Page 77

... the Flaring Method Many of the inter-unit cables to locations that are flared at the...30 to bind refrigerant tubing and inter-unit cables together with flare nuts. 3-3. 3. Installation Process 3-1. G Be sure to 50 cm) longer than 85 ft.) # ... AWG (American Wire Gauge) G Be sure to apply the provided labels to both ends of the conventional split system air conditioners...
Service Manual - Page 84

... sure to comply with local codes on terminals of electric shock, each air conditioner unit must be firmly connected. D. G Place a dedicated ground more than 3'4" (1 m) from the power cable and wires between the indoor and outdoor units. G Do not run wiring for units using inverter circuits, in the wiring diagram. Electrical noise may be required by...
Service Manual - Page 90

... concurrently may cause a malfunction. Otherwise, the air conditioner may not run properly and trouble may result in Table 1 and Table 2 are possible provided that the following holds true Rated cooling capacity of CM1972 outdoor unit: C=19700 (BTU/h) Rated cooling capacity of indoor units: K1, K2, ... (BTU/h) Then: C x 2 (200%) K1 + K2 + ....... 19700 x 2 7500 + 11900 + 17500 39400 36900...
Service Manual - Page 93

Save this combination is therefore possible to the multi outdoor unit. Otherwise, the air conditioner may not run properly and trouble may cause ..., since this , shut down at 230V If the following holds true Rated cooling capacity of CM2472 outdoor unit: C=25400 (BTU/h) Rated cooling capacity of indoor units: K1, K2, ... (BTU/h) Then: C x 2 (200%) K1 + K2 + ....... 25400 x 2 7500 + 7500 +...
Service Manual - Page 94

Otherwise, the air conditioner may be operated concurrently. The table lists the wall-mounted type of operatable indoor units > Voltage Rating : 230V 60Hz CM2472 (Rated cooling capacity at 230V: 25400 BTU/h) NOTE 7500 : KMS0772 9000 : KMS0972 11900 : KMS1272 17500 : KMS1872 24200 : KMS2472 Table 1 Indoor Unit Capacity (BTU/h) Indoor Unit Combination COOLING Room Room Room Room Total ...
Service Manual - Page 95

... models. -3- Otherwise, the air conditioner may be operated concurrently. The table lists the wall-mounted type of 4 indoor units prohibited) This multi outdoor unit allows up to four indoor units to three indoor units may not run properly. Up to be operated concurrently. Voltage Rating : 208V 60Hz CM2472 (Rated cooling capacity at 208V: 24400 BTU/h) NOTE 7500 : KMS0772...
Service Manual - Page 96

... true Rated cooling capacity of CM3172 outdoor unit: C=28600 (BTU/h) Rated cooling capacity of indoor units: K1, K2, ... (BTU/h) Then: C x 2 ...units concurrently may cause a malfunction. Otherwise, the air conditioner may not run properly and trouble may result in the 4-room operation column of the indoor units to be connected must not be connected to connect 4 units with only a single unit...

Similar Questions

Can The Fan On The Exterior Unit Be Replaced? My Fan Blade Has Fractured
can the fan blade be replaced on the exterior unit? Mod#CMH317
(Posted by gshecknauer 2 years ago)
How Can I Buy A Circuit Board Modelcm3172 Serial Number 0057874 Sku6231917735
I have this model split for 15 years with no problems. Need the circuit board
(Posted by almar117 2 years ago)
Cmh3172 Circuit Board
Power Light And Error Lights Do Not Light Up On Outside Unit. Inside Units Light Up Amd Remote Contr...
(Posted by Rmaxvance 4 years ago)
Why Does The Warning Light Blinks In Intervals Of 30 Mins?
The projector goes off in less than 30 minutes of showing and the warning light starts blinking. wha...
(Posted by semugenyijacobson 13 years ago)
Ask a New Question
Use the box below to post a new question about this Sanyo product .
Points & Prizes
  • You can earn points for nearly everything you do on HelpOwl.com
  • You can trade in those points for gift cards at leading retailers such as Amazon.com and Walmart
  • It's that simple!
See How it Works
Create a Free Account

Sanyo Manuals

Find free Sanyo CMH3172 - 30,600 BTU Ductless Multi-Split Air Cond/Heat Pump manuals and user guides available at ManualOwl.com. Try out our unique manual viewer allowing you to interact with manuals from directly within your browser!

Sanyo Reviews

View thousands of Sanyo user reviews and customer ratings available at ReviewOwl.com.

Contact Information

Complete Sanyo customer service contact information including steps to reach representatives, hours of operation, customer support links and more from ContactHelp.com.

Scoreboard Ratings

See detailed Sanyo customer service rankings, employee comments and much more from our sister site.

Sanyo Recalls

Find comprehensive Sanyo recall information updated hourly on RecallOwl.com.