Find answers below for this question about Hunter 44272.Need a Hunter 44272 manual? We have 3 online manuals for this item!
Question posted by philippmaradanas on February 3rd, 2017
Diplay
Current Answers
Answer #1: Posted by Troubleshooter101 on February 3rd, 2017 10:51 PM
Caution: High voltage testing on the transformers primary power side should only be done by a professional electrician or irrigation contractor.
If you have power at the outlet, the next thing to check is the transformer output. Use a voltmeter to check the voltage either on the two transformer wires or at the two AC screw terminals on the controller. The transformer should have an output in the range of 24VAC to 28VAC.
If the wall outlet has 110VAC and the transformer has no voltage output, you need to replace the transformer.
If you have voltage at both the wall outlet and the transformer output and you still have a blank display, try cycling the power on the controller. To cycle the power on the controller:
- Remove the 9-volt battery.
- Remove power by unplugging the transformer from the wall outlet or by turning off the circuit at the breaker box.
- Wait 4-5 minutes.
- Plug the controller transformer back into the electrical receptacle, or turn the breaker panel switch back on.
If this doesn't restore the display, the controller will need to be replaced.
Thanks
Please respond to my effort to provide you with the best possible solution by using the "Acceptable Solution" and/or the "Helpful" buttons when the answer has proven to be helpful. Please feel free to submit further info for your question, if a solution was not provided. I appreciate the opportunity to serve you!