Question posted by bearman123 on December 22nd, 2013
Ourrth110b100 Would Not Come On Replaced Batteries And Still Will Not Come On
Current Answers
Answer #1: Posted by BusterDoogen on January 5th, 2014 12:19 PM
If you have difficulty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily.
Display is blank • Check circuit breaker and reset if necessary.
• Make sure heating & cooling power switches are on.
• Make sure equipment door is securely closed.
• If battery powered, make sure fresh AA alkaline batteries are installed.
Temperature
settings do not
change
Make sure heating and cooling temperatures are set to acceptable ranges:
• Heat: 40° to 90°F (4.5° to 32°C).
• Cool: 50° to 99°F (10° to 37°C).
Heating system
does not respond
(“Heat On”
appears on
screen)
• Check for 24 Vac at the equipment on the secondary side of the transformer
between power and common. If voltage is not present, check the
heating equipment to find the cause of the problem.
• Check for 24 Vac between the heat terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the heating
equipment.
Cooling system
does not respond
(“Cool On”
appears on
screen)
• Check for 24 Vac at the equipment on the secondary side of the transformer
between power and common. If voltage is not present, check the
cooling equipment to find the cause of the problem
• Check for 24 Vac between the cooling terminal (Y) and the transformer
common. If 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
• Check for loose or broken wires between the thermostat and the cooling
equipment.
“Cool On” or
“Heat On”
is flashing
• Compressor protection timeout is engaged. Wait 5 minutes for the
system to restart safely, without damage to the compressor.
“Heat On” is
not displayed
• Set the System switch to Heat, and set the temperature level above the
current room temperature.
“Cool On” is
not displayed
• Set the System switch to Cool, and set the temperature level below the
current room temperature.
I hope this is helpful to you!
Please respond to my effort to provide you with the best possible solution by using the "Acceptable Solution" and/or the "Helpful" buttons when the answer has proven to be helpful. Please feel free to submit further info for your question, if a solution was not provided. I appreciate the opportunity to serve you!
Related Honeywell TH3210D1004 Manual Pages
Similar Questions
my thermostat digitial display is blank and might need new battery how to replace battery